9 Modbus/TCP
9.1 Protocol Configuration
For Modbus/TCP, three IP addresses need to be set via parameters:
●
IP address H3.03
●
Subnet mask H3.04
●
Gateway address H3.05
A Modbus/TCP client can connect to default TCP port 502. Additionally, a user
can specify another port by writing a port number to parameter H3.51. However,
only one client connection is accepted by the MEP card.
9.2 System Configuration
The process data configuration is setting via the parameters H3.30 and H3.31,
respectively for the input and output.
The following Modbus/TCP transactions are supported by the MEP card:
Modbus Function Code
Transaction Name
Max. Value of N
3
Read N register words
16
6
Write one register word
-
16
Write N register words
16
23
Read / write N register words
16 / 16
43
(sub-function code 14)
Read Device Identification
-
Tab. 9-1: Modbus / TCP transactions
Besides accessing parameters by their function code virtual address, there are
some special register addresses, that can be used, e.g. for reading/writing the
complete process data image. The following table gives an overview:
Register Address
Contents
0x7F00
Control word H0.00
0x7F01
Frequency command value H0.10
0x7FA0
Status word H0.01
0x7FE0
Input Process Data Image as specified by H3.30
0x7FF0
Output Process Data Image as specified by H3.31
Tab. 9-2: Overview of special register addresses
Bosch Rexroth AG
Modbus/TCP
Multi-Ethernet Card
46/61
DOK-RCON0*-XFCX610*MUL-IT02-EN-P
Содержание efc series
Страница 1: ...Frequency Converter Multi Ethernet Card Instruction Manual R912006860 Edition 02 ...
Страница 6: ...Bosch Rexroth AG Multi Ethernet Card IV DOK RCON0 XFCX610 MUL IT02 EN P ...
Страница 48: ...Fig 7 15 Example code_2 Bosch Rexroth AG SERCOS III Multi Ethernet Card 42 61 DOK RCON0 XFCX610 MUL IT02 EN P ...
Страница 65: ...Multi Ethernet Card Bosch Rexroth AG DOK RCON0 XFCX610 MUL IT02 EN P 59 61 ...
Страница 66: ...Bosch Rexroth AG Multi Ethernet Card 60 61 DOK RCON0 XFCX610 MUL IT02 EN P ...
Страница 67: ...Notes Multi Ethernet Card Bosch Rexroth AG ...