Control terminals description
Digital inputs
Terminal
Signal function
Description
Signal requirement
X1...X5
Multi-function
digital inputs
See Group E1
Inputs via opto-electric couplers:
24 VDC, 8 mA / 12 VDC, 4 mA
Pulse input: Max. 50.0 kHz
X5
(multiplex)
Pulse input
SC
Shared connection
Shared connection for isola-
tion opto-electric couplers
–
+24 V
Power supply for
digital inputs
COM is reference
Isolated from GND
Max. output current: 100 mA
COM
Analog inputs
Terminal
Signal function
Description
Signal requirement
+10 V
Power supply for
analog inputs
GND is reference
Max. output current: 30 mA
+5 V
Max. output current: 10 mA
AI1
Analog voltage input 1/
Analog current input 1
Analog voltage / current in-
puts are used as external fre-
quency setting channels
To switch between voltage
and current or to set the input
related functions, see Group
E1
Voltage input range: 0/2...10 V
Input impedance: 40 kΩ
Resolution: 1/1,000
Current input range: 0/4...20 mA
Input impedance: 500 Ω
Resolution: 1/1,000
AI2
Analog voltage input 2/
Analog current input 2
GND
Shared connection
Isolated from COM
–
Shielding connection
Connected with grounding
terminals on heatsink inter-
nally
–
EFC x610 Series
Bosch Rexroth AG
Frequency Converter Wiring
DOK-RCON03-EFC-X610***-IT05-EN-P
55/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...