Description of Diagnostic Letters F... and E...
4-33
DOK-DIAX04-ELS-06VRS**-WA01-EN-P
•
The same holds for Relative Positioning commands, where the sum of
the commanded pos the start position should be less than the
maximum allowed position.
•
Check
the
position limit values
. Moreover, the positive position limit
value must be greater than the negative position limit value.
•
If you don’t need the position limit check, de-activate it, e.g. in modulo
mode.
See also the functional description: "Mode: Drive Internal Interpolation".
E255 Feedrate-override S-0-0108 = 0
With the parameter
S-0-0108, Feedrate override
, the travel velocity of all
drive-controlled travel commands can be changed proportionally (in %). If
the value of this parameter is 0, the travel velocity is also 0. With velocity
= 0, the motor remains stationary despite having a commanded value.
Cause:
1. The parameter
S-0-0108, Feedrate override
is 0.
2. For devices with analog inputs: Feedrate override via analog input is
activated, and the voltage at the analog input is 0.
3. The
feed potentiometer
of the connected control system is at 0 or is
being evaluated incorrectly.
Remedies for:
1. Set
Feedrate override > 0
, so that the drive moves. Full speed is
attained with 100 %.
2. Apply a voltage >
0 proportional to the desired speed, +10
V
corresponds to 100 % (full) speed. Alternative: De-activate Feedrate
override.
3. Turn the feed potentiometer cautiously, check the analog signal and
the evaluation for it.
See also the functional description: "Drive-Controlled Homing".
E257 Continuous current limit active
The thermal controller work load is monitored. If a command current
profile is demanded from the drive controller and this profile is too high a
load for the power transistors in the long run (too high temperature rise of
the power output stage), the drive reacts by dynamically reducing the
effective peak current. While doing this, this warning is output. The
parameter
P-0-4046, Active peak current
is reduced. Before this real
peak current limitation occurs, the pre-warning
E261 Continuous current
limit pre-warning
should have been generated.
Cause:
The drive controller has been overloaded.
Remedy:
1. Check the amplifier dimensioning.
2. Reduce the acceleration.
3. Check the sense of rotation of the motor encoder.
Содержание DIAX04
Страница 4: ...About this Documentation DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Страница 14: ...1 4 Diagnostic Message Descriptions DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Страница 28: ...3 12 Safety Instructions for Electric Drives and Controls DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Страница 68: ...4 40 Description of Diagnostic Letters F and E DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Страница 104: ...5 36 Description of diagnostic letters F and E DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Страница 106: ...6 2 Index DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P W Warning symbols 3 1...
Страница 113: ......
Страница 114: ...Printed in Germany 2 9 1 6 2 8...