PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS
14 SEER — High Efficiency — Single Phase
(1) Operating Voltage Range: 187v min. - 253v max.
(2) HACR Type Circuit Breakers may be used.
(3) Requires 7/8" to 1-1/8" reducer from line to unit.
Notes:
Additional charge for line sets above 15 feet.
Values based on suction line as follows with 3/8" liquid line.
a) 3/4" = 0.6 oz. per additional foot.
b) 7/8" = 0.7 oz. per additional foot.
c) 1 1/8" = 0.8 oz. per additional foot.
Model Number RSH1(B,Q)E
18K
24K
30K
36K
42K
48K
Electrical Data
Volts-Cycles-Phase (1)
208/230-60-1
Total Amps
9.9
14.4
13.7
15.1
19.4
21.3
Delay Fuse Max. (2)
20
30
25
30
40
45
Min. Circuit Ampacity
12.1
17.7
16.9
18.6
23.9
26.3
Fan Motor
Type
PSC
Amps
0.9
0.9
0.9
1.0
1.5
1.5
HP
0.13
0.13
0.13
0.20
0.25
0.25
Compressor Data
RLA
9.0
13.4
12.8
14.1
17.9
19.8
LRA
46.0
58.3
64.0
77.0
112.0
109.0
Refrigerant suction line O.D.
NOTE: Liquid line is 3/8" O.D. for entire
length."
0-24 ft.
3/4"
3/4"
3/4"
7/8"
7/8"
7/8"
25-39 ft.
3/4"
3/4"
3/4"
7/8"
7/8"
7/8"
40-75 ft.
3/4"
3/4"
3/4"
7/8"
7/8"
7/8"
Approximate Weight (lbs.)
Net
185
192
208
212
252
234
Ship
196
203
220
225
245
247
Sound Rating db
75
75
75
76
79
79
RSH1(B,Q)E ACCESSORIES
Description
Part Number
Start Assist Kit - Provides additional starting torque for the compressor motor when operating
with low line voltage or high operating temperatures.
912933
Fan Delay Kit (TDR) - 80-second fan delay.
918476
Insulated Pre-Charged Line Sets - A line set consists of a liquid line, an insulated suction line,
service gaugeports, and the quick-connect coupling. 15, 20, 25, 30, 40, and 50 ft. lengths are
available. Lines are factory pre-charged such that no additional refrigerant charge is required
on matched systems.
Outdoor Thermostat - Two-stage logic provides ability to lock out electric strips down to
balance point and bring on in stages.
913852