TROUBLESHOOTING
For proper operation, the Sensor Switch has to consume power from hot and
Ground
. Therefore, a Secured Ground Wiring
is required.
Initial run
The Sensor Switch needs
initial run within three minutes
. During the initial run, the load might be turned On and Off
several times. The Time Delay knob is default set on 15 seconds, do not adjust it until initial run is finished and proper
operation function confirmed.
The Load is out of control (frequently flashing)
1. It can take up to three minutes for initial run.
2. Check the wiring connections, especially the
Ground Wiring
.
The Load does not turn On without LED flashing or LED flashing regardless of motion
1. Push Manual On/Off Button, if the load turns On; verify that Sensitivity Range is on high. If the Load does not turn
On, check the wiring connections.
The Load does not turn On while LED flashing with motion detected
1. Check to see if Ambient Light Level is enable by covering the lens by hand.
2. Push Manual On/Off Button, if the load turns On; verify that Sensitivity Range is on high. If the Load does not turn
On, check the wiring connections, especially Hot Line and Ground wiring.
The Load does not turn Off
1. There can be up to a 30 minutes time delay after the last motion detected. To verify proper operation, turn the Time
Delay Knob to 15s (Test Mode), make sure there is no motion (no LED flashing), the Load should turn Off in 15
seconds.
2. Check if there is any significant heat source mounted within six feet (two meters) that may cause false detection
such as high wattage light bulb, portable heater and HAVC device.
3. Check the wiring connections, especially the Ground wiring to the sensor switch.
The Load turns On when not desired
1.
Mask the Sensor Switch’s lens to eliminate unwanted coverage area.
2. Turn the Sensitivity Level knob toward left to avoid false alert in smaller room and near the door way.
3. Set the Band Switch to the VAC positon.