background image

Programmable controller HMI SINGLE 

User Guide 

 

Welcome 

Thank you for buying the product! Your new controller will 
provide  years  of  reliable  service.  Using  this  digital  device 
will provide more uniform comfort in your home through 
the  seasons.  Please  read  this  manual  for complete 
instructions on installing and operating your device. If you 
require  further  assistance,  please  feel  free  to  contact 
directly with Reventon Group Sp. z o.o. 

In the box you will find 

- programmable controller HMI SINGLE 
- user guide 
- external sensor NTC 
- screws (2 pieces) 

Service 

We offer the warranty of 24 months from the sales day.

 

Technical data 

Sensor: NTC 10k   

 

        Accuracy: 

±

 0.5

°

Timing error: <1% 

   Power consumption: < 1.5 W 

Set temp. range (thermostatic mode): 0 - 50

°

Set temp. difference range (temp. difference mode): 0 - 20

°

Power supply: 95 ~ 240 VAC, 50 ~ 60 Hz 
Maximal current load:  

 

fan: 5 A (inductive) 

 

valve actuator: 3 A 

Shell material: PC (fireproof) 
Dimensions: 86 x 86 x 13,3 mm 
Installation box: 86 x 86 mm lub 

Ø

 60 mm 

Ambient temperature: t = 0 - 

45°C, ϕ

  = 5-95% 

Storage temperature: -5 - 55

°

RS485/Modbus RTU communication 
Degree of protection (housing): IP 20 
Degree of protection (external sensor): IP 68 

About device 

Programmable controller HMI SINGLE is designed to on/off 
control  the  single  stage  fans  and  valves  in  fan, 
destratification  fan  and  fan  coil  unit  applications.  It  can 
operate in thermostatic or temperature difference mode. 
In the first one it control the work of device by  comparison 
of  the  room  temperature  and  setting  temperature. 
In temperature  difference  mode  it  turn  on/off  device 
depending  on  the  temperature  difference  between  value 
measured by external sensor and one measured by internal 
sensor. It can work in heating, cooling or ventilation mode. 
The item is microprocessor based device with LCD display.  

Features of the controller 

 

Modern design similar as a cell phone 

 

Beautiful Frame CHROME creates elegant life 

 

Acrylic lenses to avoid the finger scratch 

 

Touch Button makes simple operation 

 

Large  screen  display  with  backlight  is  easy  to  read  - 
even in the dark 

 

Six periods program schedules 

 

One-touch temp control overrides program schedule  

 

Precise  comfort  control  keeps  temperature  within 

0.5°C of 

the level you set 

 

Data memory when device is off 

 

Easy installation 

 

86 x 86 mm hidden box and european 60 mm round box 
is available 

Home screen quick reference

 

 

Operation 

1.

 

Setting the temperature 

a.

 

In  the  mode  of  programmable  set  temperature  could 

not be  adjusted.  If  the  user  want  to  change,  please 
reprogram. 
b.

 

In  the  mode  of  manual,  press 

  or 

  to  set 

temperature. Manual mode is signalised by icon 

2.

 

Setting lock 

Press  and  hold   

  and 

  for  5  sec.  to lock  the  screen. 

The icon 

 will display on the screen. 

Press  and  hold 

 and 

  again  for  5  sec.  to  unlock 

the screen. 

3.

 

Setting the system mode 

Press 

 to change the system mode COOLING, HEATING and 

VENTILATION. In VENTILATION, the valve is off but the fan runs. 

4.

 

Checking  temperature  of  external  sensor  (available 

only in temperature difference mode)

 

To check the external sensor temperature in temperature 
difference  mode  press  and  hold 

.  If  external 

temperature sensor is displayed, the icon 

 appears. 

Отзывы: