Programmable controller HMI SINGLE
User Guide
Welcome
Thank you for buying the product! Your new controller will
provide years of reliable service. Using this digital device
will provide more uniform comfort in your home through
the seasons. Please read this manual for complete
instructions on installing and operating your device. If you
require further assistance, please feel free to contact
directly with Reventon Group Sp. z o.o.
In the box you will find
- programmable controller HMI SINGLE
- user guide
- external sensor NTC
- screws (2 pieces)
Service
We offer the warranty of 24 months from the sales day.
Technical data
Sensor: NTC 10k
Accuracy:
±
0.5
°
C
Timing error: <1%
Power consumption: < 1.5 W
Set temp. range (thermostatic mode): 0 - 50
°
C
Set temp. difference range (temp. difference mode): 0 - 20
°
C
Power supply: 95 ~ 240 VAC, 50 ~ 60 Hz
Maximal current load:
•
fan: 5 A (inductive)
•
valve actuator: 3 A
Shell material: PC (fireproof)
Dimensions: 86 x 86 x 13,3 mm
Installation box: 86 x 86 mm lub
Ø
60 mm
Ambient temperature: t = 0 -
45°C, ϕ
= 5-95%
Storage temperature: -5 - 55
°
C
RS485/Modbus RTU communication
Degree of protection (housing): IP 20
Degree of protection (external sensor): IP 68
About device
Programmable controller HMI SINGLE is designed to on/off
control the single stage fans and valves in fan,
destratification fan and fan coil unit applications. It can
operate in thermostatic or temperature difference mode.
In the first one it control the work of device by comparison
of the room temperature and setting temperature.
In temperature difference mode it turn on/off device
depending on the temperature difference between value
measured by external sensor and one measured by internal
sensor. It can work in heating, cooling or ventilation mode.
The item is microprocessor based device with LCD display.
Features of the controller
•
Modern design similar as a cell phone
•
Beautiful Frame CHROME creates elegant life
•
Acrylic lenses to avoid the finger scratch
•
Touch Button makes simple operation
•
Large screen display with backlight is easy to read -
even in the dark
•
Six periods program schedules
•
One-touch temp control overrides program schedule
•
Precise comfort control keeps temperature within
0.5°C of
the level you set
•
Data memory when device is off
•
Easy installation
•
86 x 86 mm hidden box and european 60 mm round box
is available
Home screen quick reference
Operation
1.
Setting the temperature
a.
In the mode of programmable set temperature could
not be adjusted. If the user want to change, please
reprogram.
b.
In the mode of manual, press
or
to set
temperature. Manual mode is signalised by icon
.
2.
Setting lock
Press and hold
and
for 5 sec. to lock the screen.
The icon
will display on the screen.
Press and hold
and
again for 5 sec. to unlock
the screen.
3.
Setting the system mode
Press
to change the system mode COOLING, HEATING and
VENTILATION. In VENTILATION, the valve is off but the fan runs.
4.
Checking temperature of external sensor (available
only in temperature difference mode)
To check the external sensor temperature in temperature
difference mode press and hold
. If external
temperature sensor is displayed, the icon
appears.