20
ENGLISH
GB
7.1. Faults Display
Problem
Causes
Solutions
Pr1
"
Pr1
" flashes on the display
and the buzzer emits an
intermittent noise
(compartment probe error)
The type of probe is
incorrect.
The probe is faulty.
The probe – circuit board
connection is incorrect.
The temperature detected
by the probe is out of the
limits accepted by the
compartment probe in use
Contact the after-
sales centre.
Check that the
compartment probe is
the PTC type.
Check the integrity of the
compartment probe.
Check correctness of the
instrument - probe
connection.
Check that the
temperature in proximity
of the compartment
probe is not out of the
accepted limits
Pr3
"
Pr3
" flashes on the display
and the buzzer emits an
intermittent noise
(evaporator probe error)
Pr2
"
Pr2
" flashes on the display
and the buzzer emits an
intermittent noise
(needle probe error)
rtc
“
rtc
” flashes on the
display
Clock error
Set date and correct time
again.
Pf
“
Pf
" flashes on the display and
the buzzer emits an
intermittent noise
(
electrical power supply
failure alarm
)
There has been a power failure.
Check the electrical
system.
Contact the after-sales
service if the problem
persists.
HP
"
HP
" flashes on the display
and the buzzer emits an
intermittent noise
high
pressure
Compressor
Circuit
Breaker alarm
evaporator fan deflector
The pressure detected by
the maximum pressure
switch is higher than the
limit value.
The evaporator fan deflector
has been opened.
The absorption of the
compressor has exceeded
the envisioned maximum
limit.
Air the environment.
Clean the condenser
Close the evaporator fan
deflector.
Check that the fans
function correctly.
If the problem
persists, contact the after-
sales centre