Revision 2.1D 

 

Page 10 of 14 

 

 

www.resourcedm.com 

Mercury Switch User Guide

 

 

Warning 

 
 
 
 
 
 

Please Note 

The specifications of the product detailed on this 
Set-Up  Guide  may change without notice. RDM 
Ltd. shall not be liable for errors or for incidental 
or consequential damages, directly and indirectly, 
in connection with the furnishing, performance or 
misuse of this product or document.

 

Ensure that all power is 
switched off before   
installing or maintaining 
this product 

Input/Output table 

 

Number 

IO 

Range 

Bar (Psi) 

Units 

I-01 

Evap Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-02 

Evap 1 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-03 

Evap 2 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-04 

Evap 3 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-05 

Evap 4 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-06 

Evap 5 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-07 

Evap 6 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-08 

Evap 7 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-09 

Evap 8 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-10 

Evap 9 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-11 

Evap 10 Press 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-12 

Humidity 

 0 to 100  

rH  

I-13 

Sensor Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

I-14 

Remote 1 Pressure 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-15 

Remote 1 Pressure 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

I-16 

Remote 1 Pressure 

-3.4 to 180.0 (-49.3 to 2610) 

Bar (Psi) 

O-01 

Evap Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-02 

Evap 1 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-03 

Evap 2 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-04 

Evap 3 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-05 

Evap 4 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-06 

Evap 5 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-07 

Evap 6 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-08 

Evap 7 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-09 

Evap 8 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-10 

Evap 9 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-11 

Evap 10 Temp 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-21 

MOP 

Off ( 0 ) or On (1)      

 

O-31 

Trim Level 

0 to 100 % 

O-32 

Remote Trim 

Off ( 0 ) or On (1)      

 

O-33 

Remote 1 Temperature 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-34 

Remote 2 Temperature 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

O-35 

Remote 3 Temperature 

-49.0 to 60 (-56.2 to 140.0) 

C (

F) 

 
 

EEV Control Operation 

 
Product PR0018-PHI is intended for EEV control on an Island by island basis and can be implemented in two ways. 
 

1. 

Using the on board 4-20mA Input to measure the suction pressure going to the island. 

2. 

Using a remote suction pressure sent from Mercury Plant Controller (PR0600-PACK) on the same IP network. Note this remote 
pressure can be shared by more than one Mercury Switch. 

 

On board 4-20mA Suction Pressure Input Control Application 

 

 

Ensure parameter P-57 is set to 

“Local”. 

 

Configure the remaining parameters. 

 

Connect the suction pressure transducer for the Island to the 4-20mA input on the Mercury Switch.  

 

Ensure the transducer is correctly connected and the mA input selector jumper is in the Pressure position. 

 

Ensure each Mercury case controller has been configured to accept the calculated remote evaporator temperature. See 
Mercury user guide for further details. 

 

Remote Suction Pressure Application 

 

 

Ensure parameter P-57, Evaporator Type, is set to Remote 1 or Remote 2 or Remote 3. 

 

Set parameter P-56, Broadcast ID, to match the ID of the desired Plant Pack Controller. 

 

Configure the remaining parameters. 

 

Configure the desired Plant Pack controller to broadcast the Suction pressure. See RDM Plant Controller PR0600 for further 
information on how to broadcast pressure. 

 
Note 
 

If the Plant Controller being read from is set to Bar then the Mercury Switch has to be set for Bar (Type 1 or 3) 
If the Controller being read from is set to PSI then the Mercury Switch has to be set for PSI (Type 2 or 4). 
 

To disable local transducer 

 
To disable the local pressure input if it is not being used and stop it alarming transducer fault. 
Set P-02 (Span) = 0. This only applies to software version 2.1 or higher. 

 

Содержание Mercury PR0018

Страница 1: ...ercury Switch User Guide Resource Data Management Ltd 80 Johnstone Avenue Hillington Industrial Estate Glasgow Scotland G52 4NZ UK 44 0 141 810 2828 Switchboard support resourcedm com Technical Suppor...

Страница 2: ...Setup via Display 5 Recommended set up method 6 Set View Type 6 Set View Parameters This can also be achieved at the network front end 6 ID 6 Network Configuration 6 IP L Local IP Address 7 IP r IP Ad...

Страница 3: ...s As well as the Switch function there is the option for Island EEV control This control can be achieved by using a transducer connected to the Mercury Switch 4 20mA input or from a remote Suction pre...

Страница 4: ...elf configuring Connection to a Data Manager Director Use a standard CAT5 patch lead and connect the Data Manager or Data Director to one of the 3 10 Base T ports 10 100 Base T connectors The three 10...

Страница 5: ...splay The display fits a standard UK single socket pattress Enter Button Button used to enter confirm values after a change Up Button When in the software menu the up button is used to scroll up throu...

Страница 6: ...press Enter again to save the value The parameter list number will be displayed again Two other options are present in the parameter menu dFLt and ESC Selecting ESC will exit setup mode Selecting dFLt...

Страница 7: ...ed by the DHCP server To configure the Mercury Switch for IP r set the two rotary switches to give each controller a unique identifier The controller should then be connected to the network 2 nEt From...

Страница 8: ...5 0 to 7 2 0 1 Bar Psi 0 1 P 17 Evap 7 offset 0 0 to 0 5 0 to 7 2 0 1 Bar Psi 0 1 P 18 Evap 8 offset 0 0 to 0 5 0 to 7 2 0 1 Bar Psi 0 1 P 19 Evap 9 offset 0 0 to 0 5 0 to 7 2 0 1 Bar Psi 0 1 P 20 Ev...

Страница 9: ...educed to a predetermined percentage A MOP alarm is also created See MOP P 41 MOP Diff When the pressure reduces below this value valves on controllers connected to the Switch will recover to their no...

Страница 10: ...te 1 Temperature 49 0 to 60 56 2 to 140 0 o C o F O 34 Remote 2 Temperature 49 0 to 60 56 2 to 140 0 o C o F O 35 Remote 3 Temperature 49 0 to 60 56 2 to 140 0 o C o F EEV Control Operation Product PR...

Страница 11: ...ury Switch Or the remote Mercury Plant Controller The Mercury Case controllers require to have P17 Evaporator control set to 1 Remote for this feature to function Mercury Switch Type There are 4 types...

Страница 12: ...et to Remote and the Data Manager GP timer channel directed to the Mercury Switch is in the on period the humidity control will operate as described above During the Data Manager GP timer channel off...

Страница 13: ...to the Mercury Switch WebPages This can be achieved by using the Controller Info page in the Data Manager Data Director Find the IP address assigned to the Mercury Switch in question from the list No...

Страница 14: ...in the UK manufactured in Taiwan Ventilation There is no requirement for forced cooling ventilation Class 2 Insulation No protective Earth is required and none should be fitted The host equipment must...