6

en

3.4 

Emptying the solar thermal system

WARNING!

Risk of injury. The discharged fluid 
can have very high temperatures. 
Place the collection container so 
that people standing near by are 
not endangered when the solar 
thermal system is being emptied.

• 

Open the non-return valves in the ball valves in 
flow and return by turning the ball valves to a 45° 
position with an open-ended spanner.

• 

Place a temperature-resistant collection container 
under the drain ball valve at the lowest point of 
the solar thermal system.

• 

Open the drain ball valve at the lowest point of the 
solar thermal system.

• 

Open the bleeding devices at the highest point of 
the solar thermal system, where available.

• 

Dispose of the solar fluid in observance of local 
regulations.

Flowmeter

The Flowmeter is for measurement and display of the 
flow rate of 1-20 l/min. In order to guarantee the flaw-
less function of the measuring device the system must 
be flushed and free from foreign substances.

Left scale:
Upper edge of 
the propeller

Right scale:
Lower edge of 
the propeller 

Air separator

The air separator (manual bled valve) is for bleeding 
the solar fluid in the solar thermal system. The air 
precipitated from the solar fluid gathers in the upper 
area of the manual bleed valve (see diagram) and can, 
if required, be discharged at the bleeding valve. To gu-
arantee faultless bleeding of the collector circuit the 
flow rate in the flow must be at least 0.3 m/s.
Check the system pressure after bleeding and if ne-
cessary increase it to the specified operating pressure.

WARNING!

Risk of injury caused by very high 
temperatures. During bleeding the 
escaping air and solar fluid can re-
ach temperatures of over 100 °C.

Bleeding the solar thermal system directly 

after commissioning.

At  first  you  should  bleed  the  solar  thermal  system 

daily and then weekly or monthly, depending on the 
volume of discharged air, in order to achieve optimal 
efficiency.

Note

Bleed  the  solar  thermal  system  half-yearly 

with the manual bleed valve to achieve op-
timal efficiency.

Connection

WARNING!

Always disconnect the control-
ler from power supply before 
opening the housing!

The controller is already integrated in the station and 
ready to plug in. In the case of maintenance or service 
work, the controller is to be taken out from the stati-
on. Please pay attention to the followong steps:

• 

switch off the system, disconnect plug from the 
mains

• 

remove the front half of the insulation

• 

unscrew the cross-recessed screw off the front 
cover and remove it by pulling it upwards

• 

unscrew the lower cross-recessed screw, push the 
controller upwards and remove it

Mounting of the controller has to be carried out in 
reverse order.

Accessories for the station

For installation screw connections are required, which 
are not included in the scope of delivery. Self-sealing 
double nipples, solder nipples or clamp-ring connec-
tions can be used. For further information, please see 
product catalogue.

Содержание FlowSol C

Страница 1: ...on Operation Commissioning Manual for the specialised craftsman Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit Please keep this ma...

Страница 2: ...rks Initial installation must be effected by qualified per sonnel named by the manufacturer Description of symbols WARNING Warnings are indicated with a warn ing triangle They contain information on h...

Страница 3: ...ressure Safety valve to prevent inadmissible overpressure Flushing and filling unit optional for flushing filling and emptying the solar thermal system 1 Overview Integrated controller DeltaSol C Outs...

Страница 4: ...lushing and filling the solar thermal system Attention Risk of scalding To prevent the solar fluid boiling in the collectors the system should not be flushed or filled during periods of strong sunshin...

Страница 5: ...al times at the Air separator until the dischar ged solar fluid is free of air bubbles Close the drain ball valve 3 of the flushing and fil ling unit with the filling pump running and increase the sys...

Страница 6: ...ector circuit the flow rate in the flow must be at least 0 3 m s Check the system pressure after bleeding and if ne cessary increase it to the specified operating pressure WARNING Risk of injury cause...

Страница 7: ...7 en Notes...

Страница 8: ...e completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false information a...

Отзывы: