Installation
Commissioning
Settings
Tr
oubleshooting
Data comm
unication
Heating / Heating circuit
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Interval
Valve control runtime
1 … 20 s
4 s
Heat. sys.
Heating system selection
Curve, Constant
PWM characteristic curve
Heating curve Heating curve
0.3 … 3.0
1.0
Set temp.
Set temperature
10 … 100 °C
25 °C
Centr. outd.
sen.
Central outdoor sensor unit
option
Yes, No
No
Room influence Room influence option
Yes, No
No
Room factor
Room influence factor
1 … 10
5
Room therm.
Room thermostats sub-menu -
-
Room therm.
Room thermostat option
Yes, No
No
Type
Room thermostat type
selection
Sensor, Switch
Sensor
TambSet
Room temperature
10 … 30 °C
18 °C
Hysteresis
RTH hysteresis
0.5 … 20.0 K
0.5 K
Timer
RTH timer
Yes, No
No
Correction
Correction
1 … 20 K
3 K
RTH
Room thermostat
Activated, Deactivated Activated
HC off
Heating circuit off option
Yes, No
No
Tflowmin
Minimum flow temperature
20 … 89 °C
20 °C
Tflowmax
Maximum flow temperature 21 … 90 °C
50 °C
Pump off
Deactivation of the heating
circuit pump when Tflowmax
is exceeded
Yes, No
No
Ret. limit value Return limit value option
Yes, No
No
T-ret.
Return limit value
20 … 60 °C
30 °C
Factor
Flow correction factor
0.1 … 1.0
0.1
Day correction Day correction
-5 … +45 K
0 K
Night corr.
Night correction
-20 … +30 K
-5 K
Timer
Timer option
Yes, No
No
Mode
Correction mode selection
Day / night, Day / Off,
Outdoor /Off
Day / night
TLimit
Limit temperature
-20 … +30 °C
16 °C / 0 °C
Timer HC
Heating circuit timer
Yes, No
No
TSummer
Summer temperature day
0 … 40 °C
20 °C
Daytime on
Daytime on
00:00 … 23:45
00:00
Daytime off
Daytime off
00:00 … 23:45
00:00
TNight
Summer temperature night
0 … 40 °C
14 °C
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Remote access Remote access option
Yes, No
No
Type
Remote access type selection RTA, BAS
RTA
Sen. Frost
Antifreeze sensor
Flow, Outdoor
Flow
TFrost
Antifreeze temperature
+4 … +10 °C /
-20 … +10 °C
+5 °C / 0 °C
Chimney
sweeper
Chimney sweeper option
Yes, No
Yes
6.1
Screed drying
This function is used for time- and temperature-controlled screed drying for the
heating circuit.
Note:
The screed drying function is blocked against the chimney sweeper func-
tion. In order to activate the screed drying function, the chimney sweeper
function must be deactivated.
In the Heating / Screed drying menu the function can be set to standby by using
the Activated item.
If the microbutton
♦
is pressed and held down for at least 3 s, the screed drying
programme will start.
The message Screed drying will be indicated on the display and the remaining
time will be indicated as a countdown (dd:hh). During this process, the Lightwheel
®
will be flashing red.