System 17: 2-store solar system with pump logic and heat exchange control
The controller compares the temperature at sensor S1 to the temperatures at
sensors S2 and S4. If the measured temperature differences are higher than the ad-
justed switch-on temperature differences, the pump (R1 and/or R2) will be activat-
ed and the corresponding store will be loaded up to the adjusted store maximum
or set temperature respectively at most. The priority logic effects prior loading of
store 1.
Heat exchange control to an existent store via an additional pump (R3) can be
carried out with another temperature differential function (S3 heat source / S4
heat sink).
Sensors
S1
Temperature collector
1 / GND
S2
Temperature store 1
base
2 / GND
S3
Temperature heat
exchange source
3 / GND
S4
Temperature store
2 base and heat
exchange sink
4 / GND
S5
Free
5 / GND
Relay
R1
Solar pump store 1
R1 / N / PE
R2
Solar pump store 2
R2 / N / PE
R3
Store loading pump
R3 / N / PE
R4
Free
R4 /R4
R3
R1
R2
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PW
M
2
N
R4
V40
VBus GN
D
L'
VFS
RPS