Overview

•  Adjustable temperature difference 2 … 16 K, hysteresis 1.6 K
•  1 PWM output for speed control of a high-efficiency pump
•  Antifreeze function adjustable by DIP switch
•  Maximum or minimum temperature limitations adjustable 

by DIP switch

•  Protection against dripping water

Technical data 
Inputs: 
2 Pt1000 temperature sensors
Outputs: 1 electromechanical relay (changeover), 1 PWM output
PWM frequency: 1000 Hz
PWM voltage: 11.0 V
Switching capacity: 4 (1) A 240 V~ (electromechanical relay)
Total switching capacity: 4 A 240 V~
Power supply:  100 … 240 V~  (50 … 60  Hz)
Supply connection: type Y attachment
Standby:  0.39 W
Mode of operation: Type  1.B
Rated impulse voltage: 2.5 kV
Functions: antifreeze function, maximum or minimum temperature limitation
Housing: plastic, PC-ABS and PMMA
Mounting: wall mounting
Indication / Display:  1 operating control LED
Operation: 3 potentiometres, 4 DIP switches, 1 jumper
Protection type: IP 20 / DIN EN 60529
(with seal IP 22)
Protection class: II
Ambient temperature:  0 … 40 °C
Degree of pollution: 2
Dimensions: Ø 139 mm, depth 45 mm

Installation

2.1 

Mounting

WARNING!

Electric shock!
Upon opening the housing, live parts are exposed!

 

Î

Always disconnect the controller from power supply 
before opening the housing!

Note
Strong electromagnetic fields can impair the function of the device.

 

Î

Make sure the device as well as the system are not exposed to strong 
electromagnetic fields.

The unit must only be located in dry interior rooms. 
The controller must additionally be supplied from a double pole switch with contact 
gap of at least 3 mm.
Please pay attention to separate routing of sensor cables and mains cables.

Содержание DeltaSol AX HE

Страница 1: ...d this manual carefully to get the best performance from this unit Please keep this manual safe DeltaSol AX HE www resol com Manual en Differential temperature controller Manual for the specialised cr...

Страница 2: ...exclusively addressed to authorised skilled personnel Only qualified electricians should carry out electrical works Initial installation must be effected by the system owner or qualified personnel nam...

Страница 3: ...ntees a protection against dripping water 1 Overview 4 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 6 3 Operation and function 6 3 1 Flashing codes 6 3 2 DIP switches and potentiometres 6...

Страница 4: ...m temperature limitation Housing plastic PC ABS and PMMA Mounting wall mounting Indication Display 1 operating control LED Operation 3 potentiometres 4 DIP switches 1 jumper Protection type IP 20 DIN...

Страница 5: ...2 2 1 112mm 2 5 6 7 3 8 4 T4A fuse Mains connection Relay load Grounding terminal common terminal block Sensor 1 2 PWM output DIP switches Switch on temperature difference potentiometre Temperature li...

Страница 6: ...normally closed contact 9 neutral conductor N Grounding terminal common terminal block Speed control of a HE pump is possible via a PWM signal The pump has to be connected to the relay power supply as...

Страница 7: ...the manual mode is active the operating control lamp flashes red and green 3 4 Manual mode 3 5 Maximum temperature limitation With DIP switch 2 the temperature limitation can be activated as a maximum...

Страница 8: ...eresis below the adjusted temperature difference the pump will be switched off S1 Collector sensor S2 Store sensor RO Solar pump ON OFF 1 2 3 4 C Deactivated by default DIP switch in OFF position de f...

Страница 9: ...cuit return preheating Use grounding terminals The controller calculates the temperature difference between collector sensor S1 and store sensor S2 If the difference is larger than or identical to the...

Страница 10: ...nce falls by 1 6K non adjust able hysteresis below the adjusted temperature differ ence the pump will be switched off S1 Solid fuel boiler sensor S2 Store sensor RO Circulating pump 5 Accessories SP10...

Страница 11: ...nnected temperature sensors can be checked with an ohmmeter Please check if the resistance values correspond with the table C F Pt1000 C F Pt1000 10 14 961 55 131 1213 5 23 980 60 140 1232 0 32 1000 6...

Страница 12: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: