V404, V504, V524, V804, AND VS824 AUTOMATIC VALVE OPERATORS

7

95-6999-08

CALIBRATE OPERATOR AND INSTALL SETTING KNOB

Calibration is necessary whenever the V504, V524. operator or the bulb and bellows assembly is replaced. During 

calibration, refer to Table 3 to correlate room temperature with the numbers on the setting dial.  

V504/V524 WITH DIAL ON OPERATOR 

1.

Light pilot as described under Pilot Lighting Proce-

dure. Place a reliable thermometer near the tem-

perature sensing bulb to measure room 

temperature. Wait 5-10 minutes. 

2.

If the main burner is on, turn the calibration knob 

clockwise just until the burner goes off. If the main 

burner is off, turn the calibration knob counter-

clockwise just until the burner goes on. 

3.

Choose one of the red setting dials. Use Part No. 

394018 when the knob can be reached and turned 

directly; use Part No. 394138 when a rod and han-

dle will be installed on the dial. 

4.

Slide the dial over the knob, so that the dial number 

corresponding to the room temperature aligns with 

the indicator on the valve body. See Table 3 and 

Fig. 12. 

5.

Insert the screw supplied with the dial and tighten 

firmly while holding the dial in place. 

6.

If using 394138 Dial, insert 1/4 in. rod (obtain 

locally) into end of dial. Align hole in end with hole 

in dial sleeve. Fasten with cotter pin. 

7.

Turn dial to desired setting, making sure the cali-

bration knob is turning with the dial. If not, repeat 

steps 2-5. 

Fig. 12. Calibrating V504/V524 with dial on operator.

V504/V524 WITH DIAL MOUNTED ON CABINET. 

1.

Light pilot as described under Pilot Lighting Proce-

dure. Place a reliable thermometer near the tem-

perature sensing bulb to measure room 

temperature. Wait 5-10 minutes.

2.

Set the remote dial to the number corresponding 

with the bulb temperature. See Table 3 and Fig. 13.

Fig. 13. Calibrating V504/V524 with dial mounted on 

cabinet.

3.

If the main burner is on, turn the calibration knob 

slowly clockwise until the burner goes off. If the 

main burner is off, turn the calibration knob slowly 

counterclockwise until the burner goes on. 

4.

Slide the black locking knob over the calibration 

knob with the setting indicator in the notch. See 

Fig. 13. lnsert the screw supplied with the dial and 

tighten firmly. 

5.

Set remote dial to desired setting. 

Table 3. Temperature Dial Setting Correlation.

Setting  Dial  Number

1

2

3

4

5

6

7

8

9

Approximate Temperature

35 F-75 F [2 C-24 C]-Range

35

[2]

40

[4]

45

[7]

50

[10]

55

[13]

60

[16]

65

[18]

70

[21]

75

[24]

50 F-90 F [10 C-32 C] Range

50

[10]

55

[13]

60

[16]

65

[18]

70

[21]

75

[24]

80

[27]

85

[29]

90

[32]

Содержание V404

Страница 1: ...ng the valve V504 provides modulating control V524 provides on off control The V504 V524 replacement operator package includes Operator Operator Gasket 394018 Red Knob and Setscrew 394138 Red Knob and Setscrew 394075 Black Knob and Setscrew 388589BF Mounting Screws for Standard Capacity Valves The bulb and bellows assembly must be ordered separately see Table 2 Longer screws are required to mount ...

Страница 2: ...ivoltage system the entire system is powered by the millivoltage generated by the Powerpile generator It is important to clean and scrape all wires before connecting Solder and tape all necessary splices using rosin flux to prevent corrosion Tighten terminal screws firmly Total control circuit wiring must not exceed 30 ft 9 m of 2 wire 18 gauge cable or 50 ft 15 m of 2 wire 16 gauge cable V524A 3 ...

Страница 3: ...regulator gasket 3 Remove old operator from valve body Discard old operator and gasket REMOVING ADAPTER CASTING FROM MANUAL VALVE 1 Remove pressure regulator or blank cover plate Save regulator or cover plate for reassembly to operator Save gasket for blank cover plate discard pressure regulator gasket 2 Remove adapter casting from valve body See Figs 1 and 2 Discard casting and gasket INSTALLING ...

Страница 4: ...s hole See Fig 4 5 If control has pressure regulator choose the cor rect new pressure regulator gasket see Fig 3 Press gasket into circle on operator casting align ing tab with recess in casting See Fig 4 Position regulator over gasket and fasten with two screws used originally For V5307 put the longer screw provided with the regulator in the outside corner hole Tighten screws evenly and securely ...

Страница 5: ...splices using rosin flux to prevent corrosion Tighten terminal screws firmly Total control circuit wiring must not exceed 30 ft 9 m of 2 wire 18 gauge cable or 50 ft 15 m of 2 wire 16 gauge cable 1 Install millivoltage thermostat limit controller if required and Powerpile generator according to manufacturer s installation instructions 2 After Powerpile generator is installed route gener ator lead ...

Страница 6: ... 32 UNC 2 3 8 in long screws obtain locally for high capacity valves 10 If the bulb and bellows assembly is new follow the instructions provided with the assembly to install the bulb and the remote dial assembly if used Fig 9 Form capillary smoothly and without crimping to fit in hole in operator Fig 10 Mounting the V504 and V524 operator on a standard capacity valve Cabinet mounted dial shown Fig...

Страница 7: ... place 6 If using 394138 Dial insert 1 4 in rod obtain locally into end of dial Align hole in end with hole in dial sleeve Fasten with cotter pin 7 Turn dial to desired setting making sure the cali bration knob is turning with the dial If not repeat steps 2 5 Fig 12 Calibrating V504 V524 with dial on operator V504 V524 WITH DIAL MOUNTED ON CABINET 1 Light pilot as described under Pilot Lighting Pr...

Страница 8: ...naturally Do not light pilot or operate electric switches lights or appliances until you are sure work area is free of gas Failure to follow these instructions may result in an explosion 2 Turn the Lite Rite knob to PILOT depress it com pletely and light the pilot burner while holding it down Hold the knob down about one minute If the pilot goes out when the knob is released repeat steps 1 and 2 3...

Отзывы: