R8845U UNIVERSAL SWITCHING RELAY

3

68-0215—02

Fig. 1. R8845U dimensions in in. (mm).

INSTALLATION

When Installing this Product . . .

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

5.

Follow local codes for installation and application.

WARNING

Electrical Shock Hazard.

Can cause severe injury or death.

The transformer core is not bonded. Disconnect 

power supply before wiring.

Mounting

In replacement applications, mount the new relay in the same 

location as the old relay. For new installations, locate the 

relay vertically on a solid wall or partition as close as 

possible to the device to be controlled. Select a location that 

is easily accessible for installation and service.

NOTE:

To reduce the possible transformer hum and relay 

noise that is sometimes amplified by mounting sur-

faces such as sheet metal, plasterboard, and similar 

materials, place rubber or felt washers between the 

case and the mounting surface.

1.

Position the relay and mark the mounting holes. See 

Fig. 1.

2.

Start a screw in the upper right corner for the keyhole 

type mounting hole. Screw it down within about 1/8 in. 

(3 mm) of the surface.

3.

Hang the relay on the screw, position the case, and 

start the bottom screw.

4.

Tighten both screws.

WIRING

WARNING

Electrical Shock or Personal Injury Hazard.

Can cause severe injury or death.

Use only NEC Class 1 wire for all line voltage wiring 

connections. Class 1 wires must be rated for at least 

167°F (75°C).

All wiring must comply with all applicable electrical codes, 

ordinances, and regulations. Follow all instructions furnished 

with the controlled equipment.

IMPORTANT

The switching relay terminals are approved only for 

use with copper wires.

When two or more line-voltage load devices are to be 

controlled in parallel, the total current must not exceed the 

rating for the relay load outputs. Never connect load 

terminals to a load that uses more current than the amount 

listed in the electrical ratings on the relay. See Table 2 for 

maximum lowvoltage wiring length specifications. See the 

schematic and typical hookups in Fig. 2 through 9.

7/32 (6) 

DIAMETER 

MOUNTING 

HOLE

KNOCKOUT 

FOR 1/2 (13) 

CONDUIT (3)

1-1/16

(27)

1-1/4 (32)

2-3/16

(56)

3-1/2

(89)

3-11/16 (94)

5/16

(8)

5/16 (8)

6-1/4

(159)

5-3/8

(137)

1-3/8 (35)

4-7/16 (118)

2-1/8

(54)

3/16 (5) DIAMETER
3/8 (10) DIAMETER

7/8(22) 

DIAMETER

KEYHOLE 

TYPE

MOUNTING 

HOLE

M17512

Table 2. Low Voltage Maximum Wire Lengths.

Wire Size 

(AWG)

Total Wire Length

Wire Length of Run to 

Thermostat

Feet

Meters

Feet

Meters

22

120

38.0

60

18.0

20

200

61.0

100

30.5

18

300

91.5

150

45.5

16

500

152.5

250

76.0

14

800

244.0

400

122.0

Содержание R8845U

Страница 1: ...s unit may not exactly match the listed spec ifications Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if thos...

Страница 2: ...onnections R8845U has lower output load rating Check load requirements use RA889A if normally closed contacts are required R182B 1 3 6 8 R182C 1 2 6 8 3 5 R182J L1 L2 4 7 If used to replace an R182J i...

Страница 3: ...er right corner for the keyhole type mounting hole Screw it down within about 1 8 in 3 mm of the surface 3 Hang the relay on the screw position the case and start the bottom screw 4 Tighten both screw...

Страница 4: ...PROTECTION AND DISCONNECT MEANS AS REQUIRED IF CONTROLLING TWO LOADS USE N O AND COM FOR LINE VOLTAGE LOAD A AND B FOR LINE OR LOW VOLTAGE LOAD IF USING LOW VOLTAGE USE A SEPARATE TRANSFORMER M14296 T...

Страница 5: ...OL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED B1 IS 1 4 IN TAB TERMINAL 1 2 L7148A L8148A 2 1 M14300 3 3 X2 X1 N O COM L2 L1 W T R T X2 X1 N O COM L2 L1 W T R T X2 X1 N O COM...

Страница 6: ...CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED 1 1 20 VA M13315 R8888 1 G R8845U R T W T TO APPROPRIATE CONNECTIONS AS REQUIRED BY THE SYSTEM H1 H2 TYPICALLY CONNECTED TO T T OF...

Страница 7: ...ake certain the relay controls the equipment as intended TROUBLESHOOTING Test Button This connection is the same as a call for heat connection between the R T and W T terminals Heat Call LED The LED s...

Отзывы: