INSTALLATION INSTRUCTIONS

69-0617EF-01

R8184G PROTECTORELAY 
OIL PRIMARY

APPLICATION

The intermittent ignition oil primary control operates the 

oil burner, oil valve (if desired) and the ignition 

transformer in response to a call for heat from the 

thermostat. Through a C554 Cad Cell Flame Sensor, the 

R8184 monitors the burner flame and shuts down the 

system on ignition failure or on flame failure during the 

run cycle. A light emitting diode (LED) on the terminal 

strip lights when the safety switch opens to provide 

safety shutdown indication. A manual reset button is 

provided to reset the safety switch after lockout.

For convenience in system maintenance, the safety 

switch can be manually opened using a lever on the 

front of the control. Clock thermostats that power the 

clock through the primary control transformer will lose 

time during lockout unless backup batteries are 

installed.

R8184G is component recognized by Underwriters 

Laboratories Inc. and meets their flammability test 

requirements for a final enclosure.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a 

hazardous condition.

2.

Check the ratings given in the instructions and on 

the product to make sure the product is suitable 

for your application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Electrical shock hazard.

Disconnect power before beginning installation 

to prevent electrical shock or equipment 

damage. Make sure combustion chamber is free 

of oil or vapor before starting system.

Choose Location

This unit can be mounted on a 4 x 4 in. junction box, 

directly on the burner housing or inside the appliance 

cabinet. In a replacement application, mount in the 

same location as the old control. Line voltage 

connections must be in a wiring enclosure, such as a 

junction box or the appliance wiring compartment.

Make sure operating temperatures at the selected 

location will be within the range of -40° C to +54° C 

(-40° F to +130° F).

Make Wiring Connections and 
Mount Control

Wiring must comply with all local codes and ordinances.

Before mounting the control, make line voltage 

connections as shown in Fig. 3. Splice leads with 

solderless connectors. Do not exceed load ratings 

shown on the device label.

If cad cell leads are run with line voltage wires, breakout 

knockout at the bottom of the low voltage terminal strip 

and thread can cell leads through the hole.

If necessary use control as a template to mark and drill 

new mounting holes. Mount using No. 6 screws (obtain 

locally).

After mounting, make low voltage connections to the 

screw terminals. Strip leads 3/8 in. [10 mm] and insert 

under terminal screw. See Fig. 3. Connect cad cell leads 

to F-F terminals and thermostat leads to T-T terminals. 

See Fig. 1.

Содержание R8184G

Страница 1: ...experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical shock hazard Disconnect power before beginning installation to prevent electrical shock or equipment damage Make sure combustion chamber is free of oil or vapor before starting system Choose Location This unit can be mounted on a 4 x 4 in junction box dir...

Страница 2: ...CTION AS REQUIRED 1 F F COOLING CONTROL 2 LINE VOLTAGE THERMOSTAT 2 1 TO USE R8184 WITH LINE VOLTAGE CONTROLLER JUMPER T T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER 3 T W T R LOCKOUT INDICATOR LED SAFETY SWITCH R G Y W X C RH FAN RELAY L1 HOT L2 1 2 3 REMOVE PLUG AND ROUTE VIOLET LEADWIRE THROUGH HOLE IN BASE OF R8184 T87F Q539A COOLING TRANSFORMER VIOLET JUNCTI...

Страница 3: ...Do not attempt to take it apart Replace entire control if operation is not as described Preliminary Steps 1 Check wiring connections and power supply Make sure power is on to the controls burner motor and ignition transformer 2 Make sure limit control is closed Check Oil Primary Relay NOTE You ll need an insulated jumper wire with both ends stripped 1 Disconnect cad cell leads from F F terminals 2...

Страница 4: ...gies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 0617EF 01 M S 09 20 Printed in United States Fig 4 Move lever down to trip safety switch PUSH LEVER DOWN TO TRIP SAFETY SWITCH WHEN SAFETY SWITCH TRIPS RESET BUTTON POPS OUT INDICATOR LIGHT COMES ON ...

Страница 5: ...te 4 Une fois l installation terminée vérifier le fonctionnement du produit comme indiqué aux présentes instructions MISE EN GARDE Danger de décharge électrique Couper l alimentation avant l installation afin d éviter tout choc électrique ou tout dommage à l équipement S assurer que la chambre de combustion est exempte de mazout ou de vapeur avant de mettre le système en marche Emplacement L appar...

Страница 6: ...EUR 2 1 POUR COMBINER LE R8184 À UN RÉGULATEUR TENSION SECTEUR RACCORDER PAR CAVALIER LES BORNES T T ET BRANCHER LE THERMOSTAT TENSION SECTEUR EN SÉRIE AVEC LE LIMITEUR 3 T W T R VOYANT DE L INDICATEUR DE VERROUILLAGE SS R G Y W X C RH RELAIS DU VENTILATEUR L1 SOUS TENSION L1 SOUS TENSION L2 1 2 3 RETIRER LE BOUCHON ET ACHEMINER LE FIL VIOLET DANS LE TROU SITUÉ À L INTÉRIEUR DE LA BASE DU R8184 T8...

Страница 7: ...une panne de courant 1 Suivre les instructions pour la mise en marche du brûleur 2 Pendant que le brûleur fonctionne déclencher le disjoncteur ou retirer le fusible pour mettre le système hors tension 3 Le brûleur devrait s arrêter 4 Rétablir l alimentation Le brûleur devrait se remettre en marche Si le système ne fonctionne pas comme il est décrit procéder à la vérification VÉRIFICATION ET MAINTE...

Страница 8: ...nder la pièce no 130367 Déclencher l Interrupteur de Sécurité Avant d Effectuer la Maintenance du Brûleur MISE EN GARDE Le déclenchement de l interrupteur de sécurité provoque la fermeture du brûleur sans couper l alimentation Couper l alimentation à l interrupteur du système ou au disjoncteur avant d assurer la maintenance du système du moteur du brûleur de la vanne à mazout ou de l allumage pour...

Отзывы: