5.2 Maintenance

Do not use any cleansers that contain solvents and/or 
alcohol for cleaning the plastic parts, because this can 
cause damage to the plastic components - water 
damage could result.
Detergents must not be allowed to enter the 
environment or the sewerage system!

Interval: every 12 months
See chapter 10 Maintenance Report

Test set-up

Mount the backflow preventer in the testing equipment. Open 
all the valves, to bleed the system. Close valve 3. Check that 
the backflow preventer is sealed.

5.2.1 Inspection of check valve on input 

side 

1.

Close valve 2

2.

Wait 10 seconds and observe the differential 
pressure. If it is constant, the check valve is airtight. 
Make a note of the differential pressure 

If the differential pressure = 0, the seal on the input side is 
damaged or soiled. Follow the instructions in chapter 5.2.3 
Maintenance. 

5.2.2 Inspection of discharge valve 

1.

Close valve 2

2.

Close valve 1

3.

Slowly open valve 3 and observe the differential 
pressure. The discharge valve must respond (begin to 
drop) before the differential pressure exceeds 0.14 
bar. Make a note of the differential pressure at which 
the discharge valve responds (drops). 

If the differential pressure is <0.14 bar at the response 
moment, follow the instructions in chapter 5.2.3 Maintenance. 

5.2.3 Maintenance

Note:

For exploded drawing see chapter 11 

1.

Fix the backflow preventer on the key area of the 
housing and open the cover on the output side with 
the help of a tape puller

2.

Remove the springs and piston 

3.

Clean all interior parts and the running surface with 
clear water and check that they are in good condition. 

4.

If necessary, exchange all seals and pistons. When 
dismantling, ensure that the sealing faces in the base 
of the groove are not damaged. 

5.

Lightly grease the seals. 

6.

Reassemble in reverse order. 

7.

Carry out points in chapter 5.2.1 Inspection of check 
valve on input side and chapter 5.2.2 Inspection of 
discharge valve for inspection. 

6

Disposal

Observe the local requirements regarding correct waste 
recycling/disposal!

7

Troubleshooting

8

Spare Parts

For Spare Parts visit homecomfort.resideo.com/europe

9

Accessories

For Accessories visit homecomfort.resideo.com/europe

Problem

Cause

Remedy

Discharge valve opens for no apparent 
reason

Fluctuating inlet pressure

-

Pressure surge on the secondary side

-

Inlet check valve seal or discharge valve 
seal soiled or defective

Remove and clean piston

Discharge valve does not close

Seal damaged

Remove piston and replace seal

Running surface is soiled

Remove and clean piston

Содержание Braukmann BFW112

Страница 1: ...7378 001 Rev A Braukmann BFW112 Operating and maintenance manual Bedienungs und Instandhaltungsanleitung Mobile Backflow Preventer B FW in accordance with DIN 14346 Mobiler Systemtrenner B FW nach DIN 14346 ...

Страница 2: ...2 MU0H 1264GE23 R0520 5 2 11 1 3 2 ...

Страница 3: ...5 Maintenance 4 6 Disposal 5 7 Troubleshooting 5 8 Spare Parts 5 9 Accessories 5 10 Maintenance Report 6 D 1 Sicherheitshinweise 7 2 Technische Daten 7 3 Produktvarianten 7 4 Montage 7 5 Instandhaltung 7 6 Entsorgung 8 7 Fehlersuche 8 8 Ersatzteile 8 9 Zubehör 8 10 Instandhaltungsprotokoll 9 ...

Страница 4: ... parts are free of dirt Store in a clean and dry place These armatures need to be maintained regularly 4 2 Assembly instructions 1 Thoroughly flush hydrant standpipe 2 Check that backflow preventer connections are clean 3 Assemble backflow preventer Position backflow preventer and using both handles rotate it and the counter coupling on the hydrant standpipe to connect Note flow direction indicate...

Страница 5: ...ps If the differential pressure is 0 14 bar at the response moment follow the instructions in chapter 5 2 3 Maintenance 5 2 3Maintenance Note For exploded drawing see chapter 11 1 Fix the backflow preventer on the key area of the housing and open the cover on the output side with the help of a tape puller 2 Remove the springs and piston 3 Clean all interior parts and the running surface with clear...

Страница 6: ...ding to 8 2 1 Check discharge valve according to 8 2 2 Maintenance performed Signature Okay Not okay Defects Okay Okay Okay Not okay Not okay Not okay Maintenance performed according to 8 2 3 Yes No Yes Maintenance performed according to 8 2 3 No Maintenance performed according to 8 2 3 Yes No Device cleaned Seals greased Seals replaced Others P P at opening ...

Страница 7: ... Sauberkeit achten Sauber und trocken lagern Diese Armaturen müssen regelmäßig instandgehalten werden 4 2 Montageanleitung 1 Standrohr Hydrant gut durchspülen 2 Anschlüsse am Systemtrenner auf Sauberkeit prüfen 3 Systemtrenner montieren Systemtrenner ansetzen und mit beiden Griffen durch drehen mit Gegenkupplung am Hydrant Standrohr verbinden Durchflussrichtung beachten Pfeilrichtung 5 Instandhalt...

Страница 8: ...cht tropft Ist der Differenzdruck im Moment des Ansprechens 0 14 bar folgen Sie den Anweisungen in 5 2 3 Instandsetzung 5 2 3Instandsetzung Hinweis Explosionszeichnung siehe Kapitel 11 1 Fixieren Sie den Systemtrenner an der Schlüsselfläche des Gehäuses und öffnen den ausgangsseitigen Deckel mit Hilfe eines Bandabziehers 2 Entnehmen Sie Feder und Kolben 3 Reinigen Sie alle Innenteile und die Lauff...

Страница 9: ... Ablassventil nach 8 2 1 Durchgeführte Instandsetzungen Unterschrift in Ordnung nicht in Ordnung Mängel in Ordnung in Ordnung in Ordnung nicht in Ordnung nicht in Ordnung nicht in Ordnung Wartung gem 8 2 3 durchgeführt ja nein ja Wartung gem 8 2 3 durchgeführt nein Wartung gem 8 2 3 durchgeführt ja nein Gerät gereinigt Dichtungen gefettet Dichtungen ersetzt Sonstiges P P bei Öffnung ...

Страница 10: ...Pièce 4 1180 Rolle Switzerland 2020 Resideo Technologies Inc All rights reserved For more information homecomfort resideo com europe Ademco 1 GmbH Hardhofweg 40 74821 MOSBACH GERMANY Phone 49 6261 810 Fax 49 6261 81309 Subject to change MU1H 1264GE23 R0520 ...

Отзывы: