Operating Instructions 

REOVIB 514

 

ID No. 51401

 

 

 

REO ELEKTRONIK AG 

                                            

 

 

 

Technical Safety Information for the User

 

 
This description contains the necessary information for the correct application of the product described below. It is intended for 
use by technically qualified personal. 
 
Qualified  personnel  are  persons  who,  because  of  their  training,  experience  and  position  as  well  as  their  knowledge  of 
appropriate standards, regulations, health and safety requirements and working conditions, are authorised to be responsible for 
the  safety  of  the  equipment,  at  all  times,  whilst  carrying  out  their  normal  duties  and  are  therefore  aware  of,  and  can  report, 
possible hazards (Definition of qualified employees according to IEC 364) 
 
Safety Instructions 
 
The following instructions are provided for the personal safety of operators and also for the protection of the described product 
and connected equipment. 
 

Warning! 

Hazardous Voltage

 

Failure to observe can kill, cause damage or serious injury

 

 

 

Isolate from mains before installation or dismantling work, as well as for fuse changes or post installation modifications. 

 

Observe the prescribed accident prevention and safety rules for the specific application. 

 

Before putting into operation check if the rated voltage for the unit conforms with the local supply voltage. 

 

Emergency  stop  devices  must  be  provided  for  all  applications.  Operation  of  the  emergency  stop  must  inhibit  any  further 
uncontrolled operation. 

 

The electric connections must be covered! 

 

Earth connection must be checked for safe function after assembly! 

 
Specified Use 
 
The units described herein are electrical controllers for installation in industrial plant. They are not suitable for domestic use. 
Units with exposed electrical contacts are only suitable for installation in control panels. 
 
These units conform with the standard 2004/108/EC 

 

EMC Standard

 

 

 

!

 

 

230V, 50/60Hz

L
N
PE

Magnet

Set point

+

-

+

-

12...24 V, DC

0

10 20 30 40 50 60 70 80 90 100 [%]

10

20

30

40

50

60

70

80

90

100

[%]

o

u

tp

u

v

o

lt

a

g

e

Set point

U

m

in

U

m

a

x

.

0...20 mA
0...10 V, DC

Connection for external track control
e.g. REOVIB 513, if not useing make a link

A   S   E

U
E
E

1

2

Umax

Umin

REOVIB 514

link

Adjustment:
Connect controller according to diagram.
Adjust setpoint to minimum and inhibit unit.
Switch on mains supply and enable unit.
Slow increase the setpoint to maximum and monitor
the load condition (if possible measure the current).
On reaching maximum, limit the output with trimmer
Umax and then set the minimum set point
value with trimmer Umin.

O

p

e

ra

ti

n

g

 r

a

n

g

e

Effects of Umin and Umax trimmers

Connection Drawing

Setpoint source voltage signal
0...10 V, DC or current 0...20 mA
Enable signal voltage 12...24 V, DC
Control cables should be screened
Bond screen to earth on unit

Setpoint and enable control terminals are mains 
potential free

Enable using

Signal  Voltage

Close contacts to

enable

Setpoint source using
10 kOhm Potentiometer

Selection for 

3000 / 6000 cycles / min

Fit link for

6000 cycles / min

Fit link for

0...20mA Setpoint source

To prevent noise the earth must be 
bonded if possible to a flat mounting 
surface eg mounting plate.

Only use type FF 10 A  fuses
(very fast acting characteristic)