97
DB9 Female
TX- (RS422/RS485)
1
5
9
+5VDC*
*(DO NOT USE)
G N D
RX+ (RS422/
RXD (RS232C/CMOS)
TXD (RS232C)
TX+ (RS422/RS485)
TXD (CMOS)
RX- (RS422/RS485)
6
8
9
7
2
4
5
3
1
6
PLC 1 PORT OF GWY-S7
PLC1 port of GWY-S7 has a DB9 female type connector and is compatible with RS232C, RS422, RS485
and CMOS signal levels. Pin outs of this port are as given below:
RS485 port:
RS485 port of Gateway can have any of the following two pin outs, depending on the model number. User
can configure this port either as 4 wire + Signal Ground or 2 wire + Signal Ground.
PLC2 port of GWY-02, GWY-04, GWY-06 and GWY-08 models
This port has a 6x1 pin PCB Terminal Block type connector with following pins:
1. TX+
2. TX-
3. RX+
4. RX-
5.Termination
6. SG
Termination should be shorted with RX- for first and last node in a RS485 network.
PLC1 port of GWY-04 and GWY-08 models
This port has a 4x2 pin PCB Terminal Block type connector with following pins:
1. TX+
2. RX+
3.Termination
4. GND
5. TX-
6. RX-
7. +5 VDC (GWY-04) / +24VDC (GWY-08)
8. PLC Attach
Termination should be shorted with RX- for first and last node in a RS485 network. PLC attach line should be
connected to ground when PLC is attached on this port, else when Gateway has to be configured, leave PLC
Attach line open.
Pin
Name
Signal Level
Description
1.
TX+
RS422 / RS485
Differential Tr, also referred as TXA
2.
TXD
RS232
Transmit
3.
RXD
RS232 / CMOS
Receive
4.
RX+
RS422 / RS485
Differential R, also referred as RXA
5.
RX-
RS422 / RS485
Differential Receive -, also referred as RXB
6.
+5VDC
-
DO NOT USE
7.
TXD
CMOS
Transmit
8.
TX-
RS422 / RS485
Differential Transmit -, also referred as TXB
9.
GND
-
Signal Ground common to all signals.
Содержание GWY-00
Страница 1: ...GATEWAY USER S MANUAL ...
Страница 10: ...10 HARDWARE In this chapter Dimensional Details and Mounting Instructions Power Requirements Communications ...
Страница 15: ...15 GETTING STARTED In this chapter Introduction Gateway Operation Configuration and Communication ...
Страница 25: ...25 TYPICAL PROJECTS In this chapter Project Setup Example 1 Example 2 Example 3 ...
Страница 30: ...30 CONFIGURATION SOFTWARE In this chapter System Requirements Installation Instructions ...
Страница 32: ...32 CABLE DIAGRAMS In this chapter Wiring Diagrams Communication Cable ...
Страница 34: ...34 COMMUNICATION CABLES FOR GWY 00 ...
Страница 69: ...69 COMMUNICATION CABLES FOR GWY S7 ...
Страница 83: ...83 COMMUNICATION CABLES FOR GWY S8 ...
Страница 85: ...85 IBM CABLES ...
Страница 88: ...88 TROUBLESHOOTING GUIDE ...
Страница 104: ...CIV INDEX ...