Step 2: 

Follow below chart to connect battery pack. 

 

 

Step 3:

 Insert two battery packs inside of cabinet. Assemble top case to original position. 

 

 

5. Operation 

Power On/Off 

Once the inverter has been properly installed, press the power switch to turn on the unit. The unit will work 
automatically in line mode or inverter mode according to input utility power's status. When press the power 
switch again, the unit will be turned off. 
 

LED Indicators, Function Keys & Audible Alarms 

There are three indicators in the front panel of the unit. 

LED Indicator 

Messages 

 

Green 

Solid On 

Output is available in bypass mode 

Flashing 

Output is powered by battery in inverter mode 

 

Green 

Solid On 

Battery is not charging. 

Flashing 

Battery is charging. 

 

Red 

Solid On 

Fault mode 

Flashing 

battery low or overload warning 

Function Keys 

Function Key 

Description 

ESC 

To exit setting mode 

SELECT 

To go to next selection 

ENTER 

To confirm the selection in setting mode or enter setting mode 

 

Содержание Jaguar 1.2K

Страница 1: ...USER MANUAL J A G U A R B AT T E RY B O X 1 2kVA 900W 2 4kVA 1600W s a l e s p o w e r p r o v i d e r c o z a w w w p o w e r p r o v i d e r c o z a ...

Страница 2: ...Table of Contents 1 Introduction 1 2 Important Safety Warning SAVE THESE INSTRUCTIONS 1 3 Product Overview 3 4 Installation 3 5 Operation 5 6 Trouble Shooting 10 7 Specifications 11 ...

Страница 3: ... cover or obstruct the cooling fan CAUTION Do not operate the inverter if it has received a sharp blow been dropped or otherwise damaged in any way If the inverter is damaged called for an RMA Return Material Authorization WARNING There are no user replaceable parts inside of the inverter Do not attempt to service the unit yourself WARNING It s very important for system safety and efficient operat...

Страница 4: ...ke or allow a spark or flame in vicinity of a battery CAUTION If a remote or automatic generator start system is used disable the automatic starting circuit or disconnect the generator to prevent accident during servicing ...

Страница 5: ...automatically charge the internal battery even though the unit is off Connect to Battery Pack 1 2k Model Follow below steps to connect battery pack Step 1 Take out top case by removing screws as shown below chart 1 Power switch 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons Please see the Operation section for the details 6 LCD display 7 AC input 8 AC output receptacl...

Страница 6: ...t to connect battery pack Step 3 Insert battery pack inside of cabinet Assemble top case to original position 2 4k Model Follow below steps to connect battery pack Step 1 Take out top case by removing screws as shown below chart ...

Страница 7: ...e power switch again the unit will be turned off LED Indicators Function Keys Audible Alarms There are three indicators in the front panel of the unit LED Indicator Messages Green Solid On Output is available in bypass mode Flashing Output is powered by battery in inverter mode Green Solid On Battery is not charging Flashing Battery is charging Red Solid On Fault mode Flashing battery low or overl...

Страница 8: ...mation Indicates the Battery level by 0 24 25 49 50 74 and 75 100 in battery mode charging status in line mode In AC mode it will present battery charging status Status Battery voltage LCD Display Constant Current mode Constant Voltage mode 11Vdc pcs 4 bars will flash in turns 11Vdc 11 5Vdc pcs Bottom bar will be on and the other three bars will flash in turns 11 5Vdc 12 5Vdc pcs Bottom two bars w...

Страница 9: ...mode Escape 01 AC input voltage range Wide default If selected acceptable AC input voltage range will be within 90 280VAC Narrow If selected acceptable AC input voltage range will be within 170 280VAC 02 Battery type AGM Default Flooded User defined 03 Max AC charging current 20A default 10A 04 Bulk charging C V voltage voltage 12V model default setting 14 1V 24V model default setting 28 2V If sel...

Страница 10: ...ill be fixed to setting value no matter what percentage of load is connected Display Setting The LCD display information will be switched in turns by pressing SCROLL key The selectable information is switched as below order input voltage battery voltage output voltage load percentage load in Watt and main CPU Version Selectable information LCD display Selectable information LCD display Input volta...

Страница 11: ...e Mode The unit will provide output power from the mains It will also charge the battery at line mode Charging by utility Battery Mode The unit will provide output power from battery Power from battery only Fault Reference Code Fault Code Fault Event Icon on Fault Code Fault Event Icon on 00 Output short circuit 05 Fan locked 01 Over load time out 06 Over temperature 03 Output voltage too high 08 ...

Страница 12: ...on the front panel when the utility power is normal No LED display Battery is not connected well Check the external battery cable and terminal Make sure all the battery connections to the unit are all correct Battery defect Replace the batteries Buzzer beeps continuously and red LED is on Fault code 00 Output short circuited Check if wiring is connected well and remove abnormal load Fault code 01 ...

Страница 13: ... 10A 13A Maximum Output Fault Current 6 9A 13 6A Transfer Time 20 ms typical Waveform Simulated Sine Wave BATTERY Battery Type and Numbers 12 V 100Ah x 1 12 V 100Ah x 2 Maximum Battery Discharging Current 76A 76A Floating Charge Voltage 13 7 VDC 0 5 VDC 27 4 VDC 1 VDC Maximum AC Charging Current 10 A or 20 A 10 A or 20 A PHYSICAL Dimension DxWxH mm 393 250 459 345 400 450 Net Weight kgs 40 5 75 8 ...