MMU2-1600GE series Operations Manual Rev Apr 2020                Page 

33

 of 51 

4.6.2.1.5

 

TESTING DEFAULTS 

The Testing Defaults function can be used to quickly configure the monitor with the factory recommended settings 
for the purpose of automated testing.  The testing defaults are all Dual Enables turned on, all other features turned 
off, the currently installed program card is used, and Daylight Saving and Buzzer Disable are not changed from 
their current settings. 

Use the arrow pushbuttons to select 

YES

  and press the 

ENTER

  pushbutton  to configure the monitor with the 

factory recommended settings for testing and lock the monitor. 

NOTE:  The monitor will provide an audible confirmation of implementation of the factory recommended 
configuration by sounding the buzzer (five chirps). 

4.6.2.1.6

 

CONFIGURATION CRC 

The monitor is capable of calculating a CRC (Cyclic Redundancy Check) value for every recorded configuration.  
This screen displays the last ten configurations and the CRC value for each configuration.  This screen is view 
only. 

4.6.2.1.7

 

CONFIG SETTINGS MENU 

If the monitor has an editing session open, the menu items will be inversed if any setting accessed through that 
menu item has been changed.  If the monitor has an editing session open, the display screens accessed through this 
menu will have a flashing cursor for any display that contains editable settings.  If the monitor is locked (no editing 
session open), all of the display screens will be read-only and will not have a cursor displayed.  The monitor will 
always indicate any pending setting changes by displaying the pending settings in inverse.  This pending status is 
updated in real-time so that if changes were made to a monitor through the COM port or the Ethernet port while 
someone was viewing the display for that setting, the pending change would be immediately visible. 

MENU TEXT 

MENU FUNCTION 

PROGRAM CARD 

Access the menu for viewing the program card settings. 

DUAL IND / FC 

View and/or modify the Dual Indication / Field Check settings. 

RED ENABLES 

View and/or modify the Per Channel Red Enables settings. 

PED MONITORING 

View and/or modify the pedestrian monitoring settings. 

FYA LEFT TURNS 

View and/or modify the Flashing Yellow Arrow Left Turn settings. 

CO-CHANNELS 

View and/or modify the Co-Channel settings. 

THRESHOLDS 

View and/or modify threshold settings. 

LOGGING 

View and/or modify the logging settings. 

OTHERS 

View and/or modify other miscellaneous settings. 

4.6.2.1.7.1

 

PROGRAMMING CARD MENU 

MENU TEXT 

MENU FUNCTION 

PER CHANNEL PERMISSIVES 

View the permissive jumpers on the program card. 

MYCD / LATCHES / MIN FLASH 

View Minimum Yellow Change Disable, CVM Latch, 24V Latch, and 
Minimum Flash jumpers on the program card. 

4.6.2.1.7.1.1

 

PER CHANNEL PERMISSIVES 

Programming card permissive settings are displayed on a per channel basis.  A jumper symbol (

) indicates that a 

channel (the row) is jumpered as permissive with another channel (the column).  A dash (

) indicates a non-

permissive channel combination.  This display is view only.  Use the up (

▲) or down (▼) pushbutton to scroll the 

viewing window to the other channels.  This display is view only.  Press the 

ENTER

 pushbutton or the 

ESCAPE

 

pushbutton to exit. 

4.6.2.1.7.1.2

 

MINIMUM YELLOW CHANGE DISABLE / LATCHES / MINIMUM FLASH 

This display is view only.  Press the 

ENTER

 pushbutton or the 

ESCAPE

 pushbutton to exit. 

MYCD – Programming card Minimum Yellow Change Disable settings are displayed on a per channel basis.  A 
jumper symbol (

) indicates that the Minimum Yellow Change is disabled for that channel.  A dash (

) indicates 

the Minimum Yellow Change is not disabled.  MYCD jumpers are usually not needed for monitors operating in the 
Type 12 mode.  In Type 16 mode, MYCD jumpers are usually required for all pedestrian channels. 

LATCHES

 

– CVM Latch determines if the monitor latches a CVM fault and requires a front panel or external reset 

in order to return to normal signal operation.  If set to NO, after a CVM fault has occurred, the monitor will return 
to normal signal operation once the CVM input returns to the valid (low) state and the Minimum Flash time has 
expired. 

24V Latch determines if the monitor latches a +24V Monitor I or +24V Monitor II fault and requires a front panel 
or external reset in order to return to normal signal operation.  If set to NO, after a +24V Monitor fault has 
occurred, the monitor will return to normal signal operation once both of the +24V Monitor inputs return to the 
valid (> +22VDC) state and the Minimum Flash time has expired. 

MINIMUM FLASH – The Minimum Flash time displayed is the time setting that is jumpered on the program card.  
According to the NEMA specification, the monitor will add one second to the jumpered time to get the actual 
Minimum Flash time used and that the jumpered value cannot be less than five seconds.  If the jumpered value is 
less than five seconds, it will be displayed as five seconds as this will be the value used.

 

Содержание MMU2-1600GE

Страница 1: ...GE series Malfunction Management Unit pn 889 3819 00 Revision April 2020 MMU2 1600GE Malfunction Management Unit Firmware Version 02 00 05 Operations Manual NEMA TS 2 Amendment 4 2012 Malfunction Mana...

Страница 2: ......

Страница 3: ......

Страница 4: ...BLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING ALL REGISTERED TRADEMARKS OF EBERLE DESIGN INC ARE UNDER COPYRIGHT MAINTENANCE NOTE IT IS AN E...

Страница 5: ......

Страница 6: ...bility 6 2 3 2 Minimum Flash 6 2 3 3 Minimum Yellow Change Channel Disable 6 2 3 4 Voltage Monitor Latch 6 2 3 5 Serial EEPROM 6 2 4 FEATURES 6 2 4 1 Monitor Power Failure 6 2 4 2 Minimum Flashing Ind...

Страница 7: ...g Field Changes 20 2 7 7 2 Log Local Flash Events 20 2 7 7 3 Log CVM Events 20 2 8 Diagnostics 20 2 8 1 Memory 21 2 8 2 Microprocessor Monitor 21 2 8 3 Internal Voltage Monitors 21 2 8 4 Diagnostic Co...

Страница 8: ...4 Other AC and Miscellaneous Inputs 46 4 6 5 5 DC Inputs 46 4 6 6 Diagnostic Info 46 4 6 6 1 LED Test Settings 46 4 6 6 2 Screen Test 46 4 6 6 3 Fault Codes 46 4 6 6 4 Diagnostic SDLC Frames Menu 46 4...

Страница 9: ......

Страница 10: ...ovide downward compatibility with a 12 channel conflict monitor unit CMU conforming to TS 1 1989 The signal monitor portion of the monitor is capable of checking for the presence of voltage on conflic...

Страница 11: ...Series is comprised of the following monitors Model MMU2 1600G Reno USA For applications calling for a NEMA TS 2 2003 compliant Malfunction Management Unit with integral graphics display Model MMU2 16...

Страница 12: ...The LED thresholds are more restrictive than the standard thresholds Therefore you will not miss a fault using the LED thresholds that would have been detected using the standard thresholds In the Sta...

Страница 13: ...troller Voltage Monitor input Connector A Pin V is a logic level input This input must stay in a low state nominal 0 volts for normal signal operation When high or floating the monitor will be in the...

Страница 14: ...9 Frame to 1 At all other times the Start Up Flash Call bit of the Type 129 Frame is set to 0 Typical Connection One set of contacts is used to control the flash transfer relays the other is usually u...

Страница 15: ...tored in the serial EEPROM is used 2 4 FEATURES 2 4 1 MONITOR POWER FAILURE The monitor responds to a Power Failure by entering a non latching flash state The monitor responds to a Power Failure wheth...

Страница 16: ...ort does not support handshaking signals Both the COM port and the optional Ethernet port can be used at the same time See Section 3 4 for connector pin assignments 2 4 6 ETHERNET PORT The monitor has...

Страница 17: ...ng configuration settings are monitored Programming Card jumpers Type Select input Factory Options Dual Indication Field Check Per Channel Red Enables Flashing Don t Walk Monitoring Flashing Yellow Ar...

Страница 18: ...ram card settings of the parent channel If ALLOW CONCURRENT YEL is YES then the yellow following a FYA will not conflict with the opposing thru yellow If IGNORE YEL TRAP is YES then the Yellow of the...

Страница 19: ...d for Yellow Red Green Red Green Yellow and Walk Yellow When operating in the Type 16 mode the following dual indications are checked for Yellow Red Green Red and Green Yellow When a channel has multi...

Страница 20: ...nds or more the monitor will latch a dual indication fault If the single indication timer reaches 1000 milliseconds the dual indication timer the single indication timer and the no indication timer ar...

Страница 21: ...RT CLEARANCE MONITORING Configuration All channels will be monitored for a short clearance fault Test Preformed When a channel has a Green or Walk that turns off a conflict channel cannot display a Gr...

Страница 22: ...Co Channel Per Channel Red Enables are enabled only channels that have been programmed with a Per Channel Red Enable setting of Y will be included in the channels checked for a field check fault Flas...

Страница 23: ...ed A voltage greater than 22VDC applied to the 24 Volt Monitor II input is recognized as adequate for proper operation A voltage of less than 18VDC is recognized as inadequate for proper operation Whe...

Страница 24: ...s to the fault condition continuity between the Normally Open and Common contacts illuminates the LOC FLASH indicator on the front panel and sets the Local Flash bit bit 79 of the Type 129 Frame to 1...

Страница 25: ...a flashing Red input is never checked for conflicts 2 6 2 PPLT5 MONITORING Configuration The setting of Co Channel Per Channel Red Enables determines if this feature is active All channels with a set...

Страница 26: ...yellow If IGNORE YEL TRAP is YES then the Yellow of the FYA channel can be on with the opposing thru green indication following a flashing yellow arrow If GREEN SOLO is selected and IGNORE UNUSED CHA...

Страница 27: ...RED ENABLE input is not active The testing defaults for this feature are all Per Channel Red Enables enabled and Co Channel Per Channel Red Enables set to no Tests Modified Red Fail Normal red fail te...

Страница 28: ...is changed from 800 milliseconds to 1 5 seconds Red Fail Reset time is changed from 300 milliseconds to 200 milliseconds Dual Indication Green Yellow Dual Indication Reset time is changed from 300 mi...

Страница 29: ...and Walks RMS Voltages of all Greens Yellows Reds and Walks Status of all DC inputs Status of Red Enable AC Line Voltage Red Enable Voltage and DC Input Voltages Time Mode The Signal Sequence Log reco...

Страница 30: ...aults will not be logged by the monitor as any one of these voltages being invalid will immediately place the monitor in a diagnostic failure mode with the microprocessor held in reset This prevents a...

Страница 31: ...nominal AC VOLTAGE INPUTS NORMAL THRESHOLDS Green Signal Inputs OFF 15 VRMS ON 25 VRMS Walk Signal Inputs OFF 15 VRMS ON 25 VRMS Yellow Signal Inputs OFF 15 VRMS ON 25 VRMS Red Signal Inputs OFF 50 V...

Страница 32: ...c Detect 1000 msec Typical 800 msec CVM FAULT No Fault 125 msec Detect 175 msec Typical 150 msec 24 VDC MONITOR No Fault 125 msec Detect 175 msec Typical 150 msec CLEARANCE FAIL No Fault 2 8 sec Detec...

Страница 33: ...12 Only I Channel 10 Walk I b Channel 10 Yellow I Channel 10 Yellow I c Channel 9 Yellow I Channel 9 Yellow I d Channel 8 Yellow I Channel 8 Yellow I e Channel 7 Yellow I Channel 7 Yellow I f Channel...

Страница 34: ...Type 16 Only I U Start Delay Relay N C Open During Start Delay O Start Delay Relay N C Open During Start Delay O V Channel 10 Red I Channel 10 Red I W Channel 14 Red I Channel 14 Red Type 16 Only I X...

Страница 35: ...erved 20 5 9 5 10 5 11 20 Reserved Reserved Reserved 21 5 12 5 13 5 14 21 Minimum Flash b8 Minimum Flash b4 Minimum Flash b2 22 5 15 5 16 6 7 22 Minimum Flash b1 24V Latch Enable CVM Latch Enable 23 6...

Страница 36: ...EDs ON Fault Blip Fault Disabled Fuse 1 4 Amp Slo Blo Connector B Channel Red Inputs Red Enable Start Delay Relay Local Flash 24V Monitor II Connector A Channel Green Yellow and Walk Inputs Output Rel...

Страница 37: ...rrent To Pending Compare Config To Current Compare Config To Prior Date Time Functions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log C...

Страница 38: ...is button will display the Configuration Shortcuts menu Right Pushbutton The pushbutton labeled is used to navigate through menu selections or settings being viewed If the setting being viewed can be...

Страница 39: ...r five seconds until the monitor gives five quick confirmation beeps or navigate to the Fault Monitoring Menu and select Save Changes 4 4 4 UPGRADE PENDING When new firmware has been downloaded in to...

Страница 40: ...ious display LOCATION This text field is 40 characters long The user can edit this field This field is typically used to store the intersection that the monitor is installed at example VIRGINIA AVE LO...

Страница 41: ...his monitor to the factory defaults WIZARD Access the configuration wizard that can be used to automatically configure most settings in the monitor 4 6 2 1 1 START CONFIGURATION Before a change can be...

Страница 42: ...gs LOGGING View and or modify the logging settings OTHERS View and or modify other miscellaneous settings 4 6 2 1 7 1 PROGRAMMING CARD MENU MENU TEXT MENU FUNCTION PER CHANNEL PERMISSIVES View the per...

Страница 43: ...tor will only perform Red Fail and Field Check monitoring for channels that have been enabled for this feature when the Red Enable input is active Only the Red Fail and Field Check monitoring are affe...

Страница 44: ...Yellow and Red drivers of the Parent Channel are ignored for conflict dual indication short clearance and short yellow monitoring If No is selected the Yellow and Red signal indications are monitored...

Страница 45: ...tion 2 7 7 3 for more information The factory default for this feature is YES 4 6 2 1 7 9 OTHERS MISCELLANEOUS LOCATION SETTINGS Use the up or down pushbutton to navigate between the settings Use the...

Страница 46: ...T This left turn is a standard protected left turn movement This is the default left turn type MMU2 Allows the selection of sixteen FYA configurations types A thru P This includes the eight Flashing Y...

Страница 47: ...s This is important because the MMU2 has a limited number of channels Type A B C and D require 1 channel for each protected left turns 1 3 5 7 and 4 channels for the 4 FYAs The MMU2 uses 16 channels t...

Страница 48: ...and 16G Type G and H require 1 channel for each protected left turn 1 3 5 7 and the Ped Yellow for the FYA The Controller Unit must be able to use the Ped Yellow as a FYA FYA Type G has the Peds on c...

Страница 49: ...plays the opposing Ped Yellows on channels 13G 14G 15G and 16G Type K and L require 1 channel for each protected left turns 1 3 5 7 and 4 channels for the 4 FYAs Type K assigns the Green of channels 9...

Страница 50: ...LT4 This left turn uses a five section head with a Green arrow Green ball Yellow ball and a Red ball If this type is selected other setting will be displayed FYA allows the selection of the channels w...

Страница 51: ...98V to 135V in one volt increments The recovery voltage is automatically set to three volts lower than the alarm voltage The factory default for this setting is 130V LOW VOLTAGE The AC low voltage ala...

Страница 52: ...guration changes COMPARE CONFIG TO CURRENT View the differences between any previous configuration and the current configuration COMPARE CONFIG TO PRIOR View the differences between any previous confi...

Страница 53: ...e Red Enable Voltage and DC Input Voltages are recorded This display is view only The display consists of a voltage section two status sections and a single line footer showing the Fault Type and the...

Страница 54: ...ghlighted setting Press the ENTER pushbutton to accept and store the modified Daylight Saving Time Ahead settings Press the ESCAPE pushbutton to exit 4 6 4 4 VIEW UP TIME The MMU 1600G warranty covera...

Страница 55: ...NOTE In most instances once the LED Test has been completed the function should be turned OFF If the LED Test has been left ON repeat the procedure outlined above or press the RESET pushbutton to turn...

Страница 56: ...r of breaks received BREAKS number of parity errors received PARITY number of frames received with a checksum error CHKSUM number of start of frame errors SOF and number of end of frame errors EOF Thi...

Страница 57: ...C line voltage is above 98VRMS When the AC line voltage is below 89VRMS the indicator will flash at a 1 Hz rate to indicate low line voltage While the AC line voltage is low all field status indicator...

Страница 58: ...through the RaeComM software or via the front panel See Section 4 6 2 1 7 9 4 8 1 CRITICAL FAILURE When the monitor main microprocessor is held in the reset state due to a critical hardware failure th...

Страница 59: ...A E web site www renoae com 3 Connect the monitor to the computer through the COMM PORT or ETHERNET 10 100 port on the MMU 1600GE 4 Start the RaeComM program 5 Ensure that the RaeComM software can com...

Страница 60: ...ompare Config To Current Compare Config To Prior Date Time Functions Clear Logs Clear All Logs Logging Thresholds View Prior Faults Log View Signal Sequence Log Clear Date Time Log Clear AC Line Log C...

Отзывы: