Connection and installation

•  Remove the cover. Rotate the two clamping knobs to the left or right, the cover can then be raised to the 

rear and removed.

•  Carefully cut into the cable sheath of the network cable at approx. 50 mm. Do not damage the shielding 

and the inner conductor!

•  Pull off the cable sheath.
•  Pull the braided shielding backwards over the cable sheath and twist it. Remove the shielding of the wire 

pairs.

•  Loosen the metal bracket for the strain relief in the patch panel for the corresponding port, where you want 

to connect the cable.

•  For cabling use either the colour coding according to T568A or T568B (in Europe T568A is usually used). 

Do not mix the two colour codes on your network, or otherwise the network connections may not work.
Guide the shielding of the cable pairs of the CAT6 cable up to the insulation displacement terminals.

Pin

T568A

T568B

1

white/green

white/orange

2

green

orange

3

white/orange

white/green

4

blue

blue

5

white/blue

white/blue

6

orange

green

7

white/brown

white/brown

8

brown

brown

•  Connect the wires (starting from insulation displacement terminal 8) with a suitable LSA punch down tool. 

Pay attention to the correct colour coding.

•  Secure the network cable with the strain relief, so that the shielding braid is located under the strain relief 

and contact is achieved. 

  Do not use force; do not pinch the cable too tightly.

• 

Finally, the network cable is to be fixed at the rear end of the patch panel with a cable tie. Do as described 

above for other network cables.

•  When all the cables are connected, replace the cover. Secure the cover with the two clamping knobs.
•  Install the patch panel in your 254 mm (10”) network cabinet. Suitable installation material is enclosed 

for this purpose. 
Alternatively, you can hang the patch panel on a wall, thanks to the openings on the underside. Use 

suitable screws and, if necessary, dowels depending on the existing surface.

•  Attach the grounding cable of the patch panel to a grounding connection provided for this purpose.
•  Label the cables and network ports on the patch panel in a suitable manner, so that you can inspect the 

connections and cable connections more easily in the event of faults.

Care and cleaning

•  Never use aggressive detergents, rubbing alcohol or other chemical solutions, as these may damage the 

casing or cause the product to malfunction.

•  Use a dry, lint-free cloth to clean the product.

Disposal

  The product must not be disposed of with the household waste Always dispose of the product 

according to the relevant statutory regulations.

Technical data

Rated voltage ....................................... 125 V/AC RMS
Rated current ........................................ 1.5 A
Contact resistance ................................

max. 100 mΩ

Insulation resistance .............................

min. 1000 mΩ, 500 V/DC

Dielectric strength ................................. 750 V/AC RMS, 60 Hz, 1 min
Transmission rate ................................. 500 Mbps
Standards ............................................. ISO/IEC 11801:2002 Class E

ANSI/TIA/EIA-568 B.2-1

Connection service life ......................... min. 750 mating cycles (RJ45)

min. 200 mating cycles (insulation displacement terminals)

Operating conditions ............................. -10 to +60 °C, 10 – 85 % RH
Storage conditions ................................ -20 to +75 °C, 10 – 85 % RH
Dimensions ........................................... 238 x 108 x 44.5 mm

 Operating instructions

12 Port Patch Panel CAT6

Item no. 2266996

Intended use

The product is intended for cabling of rigid network lines in accordance with CAT6 standards. This then 

makes the connection of conventional patch cables to the RJ45 sockets possible.
For safety reasons, you must not rebuild and/or modify this product. Using the product for purposes other 

than those described above may damage the product. In addition, improper use can cause hazards such 

as a short circuit or fire. Read the instructions carefully and store them in a safe place. Make this product 

available to third parties only together with its operating instructions.
This product complies with statutory national and European regulations. All company and product names are 

trademarks of their respective owners. All rights reserved.

Delivery content

•  Patch panel
•  12x cable ties (75 x 1.9 mm)
•  4x M6 x 16 screw set
•  Operating Instructions

Up-to-date operating instructions      

Download the latest operating instructions at www.conrad.com/downloads or scan the QR code on this page. 

Follow the instructions on the website.

Explanation of symbols

  This symbol is used to highlight important information in these operating instructions. Always 

read this information carefully.

  This symbol indicates special information and advice on how to use the product.

Safety instructions

Read the operating instructions carefully and especially observe the safety information. 

If you do not follow the safety instructions and information on proper handling in this 

manual, we will assume no liability for any resulting personal injury or damage to 

property. Such cases will invalidate the warranty/guarantee.

•  The product is not a toy. Keep it out of the reach of children and pets.
•  Do not leave packaging material lying around carelessly. This may become dangerous 

playing material for children.
•  Protect the product from extreme temperatures, direct sunlight, strong jolts, high humidity, 

moisture, flammable gases, vapours and solvents.

•  Do not place the product under any mechanical stress.
•  If it is no longer possible to operate the product safely, stop using it and prevent unauthorized 

use. Safe operation can no longer be guaranteed if the product:

 -

is visibly damaged, 

 -

is no longer working properly, 

 -

has been stored for extended periods in poor ambient conditions or 

 -

has been subjected to any serious transport-related stresses.

•  Always handle the product carefully. Jolts, impacts or a fall even from a low height may 

damage the product.
•  Consult a technician if you are not sure how to use or connect the product.
• 

Maintenance, modifications and repairs are to be performed exclusively by an expert or at 

a qualified shop.

•  If you have questions which remain unanswered by these operating instructions, contact our 

technical support service or other technical personnel.

This is a publication by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau (www.conrad.com). 

All rights including translation reserved. Reproduction by any method (e.g. photocopying, microfilming, or the capture in 

electronic data processing systems) requires prior written approval from the editor. Reprinting, also in part, is prohibited. 

This publication represents the technical status at the time of printing.
Copyright 2020 by Conrad Electronic SE. 

  

*2266996_v1_1220_02_JC_m_en

Содержание T568A

Страница 1: ...nach CAT6 vorgesehen An den RJ45 Buchsen können dann herkömmliche Patchkabel angeschlossen werden Aus Sicherheitsgründen dürfen Sie das Produkt nicht umbauen und oder verändern Falls Sie das Produkt für andere Zwecke verwenden als zuvor beschrieben kann das Produkt beschädigt werden Außerdem kann eine unsachgemäße Verwendung Gefahren wie z B Kurzschluss Brand etc hervorrufen Lesen Sie sich die Bed...

Страница 2: ... Panel CAT6 Item no 2266996 Intended use The product is intended for cabling of rigid network lines in accordance with CAT6 standards This then makes the connection of conventional patch cables to the RJ45 sockets possible For safety reasons you must not rebuild and or modify this product Using the product for purposes other than those described above may damage the product In addition improper us...

Страница 3: ...ande 2266996 Utilisation prévue Le produit sert au câblage de lignes de réseau fixes prévues selon CAT6 Il est possible de raccorder un câble de brassage conventionnel à une douille RJ45 Pour des raisons de sécurité toute transformation et ou modification du produit est interdite Si vous utilisez le produit à d autres fins que celles décrites précédemment vous risquez de l endommager Par ailleurs ...

Страница 4: ...n conventionele patchkabels worden aangesloten Om veiligheidsredenen zijn er geen aanpassingen en of wijzigingen aan dit product toegestaan Indien het product voor andere doeleinden wordt gebruikt dan de hiervoor beschreven doeleinden kan het product worden beschadigd Bovendien kan bij verkeerd gebruik een gevaarlijke situatie ontstaan zoals bijv kortsluiting brand enz Lees de gebruiksaanwijzing z...

Отзывы: