Wind direction transmitter instruction manual (analog type)
Shandong Renke Control Technology Co., Ltd.
www.renkeer.com
8
disconnect the power supply. Water entering the transmitter can cause irreversible changes.
3. Prevent chemical reagent, oil, dust and other direct damage to the sensor, do not use it for a
long time in the environment of condensation, extreme temperature, and prevent cold and heat
shock.
4. Calculation method
4-20mA output comparison
table
0-10V output comparison table 0-5V output comparison table
output value
(
mA
)
Correspondin
g wind
direction
Output value
(V)
Correspondin
g wind
direction
Output value
(V)
Correspondin
g wind
direction
≈
4
North wind
≈
0
North wind
≈
0
North wind
≈
6.2857
Northeast
wind
≈
1.4286
Northeast
wind
≈
0.7143
Northeast
wind
≈
8.5714
Dongfeng
≈
2.8571
Dongfeng
≈
1.4286
Dongfeng
≈
10.8571
Southeast
wind
≈
4.2857
Southeast
wind
≈
2.1429
Southeast
wind
≈
13.1429
south wind
≈
5.7143
south wind
≈
2.8571
south wind
≈
15.4286
Southwest
wind
≈
7.1429
Southwest
wind
≈
3.5714
Southwest
wind
≈
17.7143
Westerly
≈
8.5714
Westerly
≈
4.2857
Westerly
≈
20
Northwest
wind
≈
10
Northwest
wind
≈
5
Northwest
wind
5. Common problems and solutions
Symptom: No output or output error
possible reason:
1) PLC calculation error caused by incorrect range measurement. Please refer to the technical
specifications in Part 1 for the measurement range.
2) The wiring method is incorrect or the wiring sequence is wrong.
3) The power supply voltage is incorrect (24V power supply for 0-10V models).
4) The distance between the transmitter and the collector is too long, causing signal disturbance.
5) The PLC acquisition port is damaged.
6) The equipment is damaged.