RenewAire RH-D Series Скачать руководство пользователя страница 21

RH-D AND RH-W ELECTRIC DUCT HEATERS

21

 

1.800.627.4499 

INSTALLATION, OPERATION AND MAINTENANCE MANUAL 

RENEWAIRE.COM 

MAINTENANCE

7.3 RH-D TROUBLE SHOOTING

7.1 RH-D ANNUAL MAINTENANCE

7.2 RH-W ANNUAL MAINTENANCE

7.0 MAINTENANCE

RISK OF BURNS

This device is an electric heater and produces very high temperatures, capable of causing severe 

burns. Use caution when working on the heater and wear appropriate Personal Protective Equipment 

(PPE) whenever working on the unit.

CAUTION

7.3.1 Testing AFS and S1 Sensors

7.3.2 Testing Control Modules D21-T and D22-T

Remove AFS and/or S1 sensor from D21-T/D22-T board and measure the ohms across the Thermistor:

The reading should be 10KΩ at 77 F. If the temperature is higher, the resistance will go down and if the 

temperature is lower, the resistance will go up. If the sensor reads OPEN LINE, replace sensor. 

A D22-T is essentially a D21-T with 2 power outputs instead of one. Here are the steps to follow to test 

and troubleshoot these 2 boards:

The first step in testing the D21-T/D22-T controllers is to confirm that there is 24 VAC powering the 

board. (Top left connections on the board). The airflow sensor is a device that protects the heater 

element section from overheating. If there is a lack of proper airflow, the controller and the airflow 

sensor will make the unit modulate proportionally with the airflow. This simply means that, if the 

element section is getting half of the needed airflow, the heater will work at half the capacity. This 

prevents overheating of the elements which would damage them. For testing purposes, remove the 

Airflow sensor (AFS) from the terminals A and A. When that airflow sensor is removed, the heater will 

still operate normally but without element protection (this is only for testing). Make sure you reconnect 

the airflow sensor after testing.

If there is a built-in duct temperature sensor connected to S and S, you can simply dial your set point 

on the blue potentiometer on the controller. If the red light never turns on, temporarily disconnect wires 

connected on S and S. The board can still operate but only in an ON/OFF mode. The heater/red light 

should turn ON, if the potentiometer is set anywhere between 0 and 18 and OFF anywhere else. Again, 

if the red light never turns on, the controller is defective and replacement is required. If the heater is 

controlled remotely with a room or duct thermostat, simply set the potentiometer to position “R” (R for 

Remote control). Note that these controllers have power outputs. It is possible after many switching 

cycles that the built-in triacs will stay stuck in a closed or open position. The control side of the board 

might still be good, but the power side will not operate. If the triacs are stuck closed, the thermal cut-

outs will cut power to the unit. If the triacs are stuck open, the unit will not put out any heat even if 

there is a demand.

There is no required annual maintenance for any RH-D heater.

RH-W heaters have a fault indicator LED. RenewAire suggests that the LED be checked annually for 

indication of detected problems. 

Содержание RH-D Series

Страница 1: ...ELECTRIC DUCT HEATER INSTALLATION OPERATION MAINTENANCE MANUAL WWW RENEWAIRE COM RH D Series RH W Series Model RH D Shown LR 30551...

Страница 2: ...e tension l int rieur de l unit est d installer et d ouvrir un sectionneur distance et de v rifier que l alimentation est coup e avec un voltm tre Reportez vous au sch ma lectrique de l unit Suivez to...

Страница 3: ...d Serial Number Electric Duct Heater Model Electric Duct Heater Type D or W R H Locate the RenewAire unit label to be found on the outside of the appliance NOTE This information is for purposes of ide...

Страница 4: ...8 6 3 RH D 208 240 VAC 8 10 AND 11 5 KW 19 6 4 RH W 120 VAC 19 6 5 RH W 208 240 VAC 3 4 5 6 KW 20 6 6 RH W 208 240 VAC 8 10 11 5 KW 20 7 0 MAINTENANCE 21 7 1 RH D ANNUAL MAINTENANCE 21 7 2 RH W ANNUAL...

Страница 5: ...rection with no changes to the unit hardware 1 3 SAFETY FEATURES 1 3 1 Low Air Flow Modulation Shut Off The heater has a thermistor air flow sensor that will detect any overheating condition caused by...

Страница 6: ...10 4240 l l l 131339 RH D TER 10 5208 l l l 131340 RH D TER 10 5240 l l l 131341 RH D TER 10 6240 l l l 131342 RH D TER 10 8240 l l l 131343 RH D TER 10 10240 l l l 131361 RH D TER 10 12240 l l l 1313...

Страница 7: ...rovided by an on board transformer The controller has a potentiometer to set the desired output air temperature from the unit and heat output is modulated by the controller which causes the SSR to pro...

Страница 8: ...ls by the SSR which is controlled by the on board controller Wall Thermostat typ RH W Heater typ RH W Controls typ 2 2 1 CTH291 Thermostat The CTH291 Thermostat is an 0 10 VDC output dual mode device...

Страница 9: ...ount occupancy sensors as options for the Electric Duct Heater Either device must be hard wired to the CTH291 thermostat and powered by an external 24 VAC source RenewAire offers a commercial grade ti...

Страница 10: ...N OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 10 DIMENSIONED DRAWINGS 3 0 DIMENSIONED DRAWINGS 3 1 RH D AND RH W WITH 6 DUCT COLLAR 3 2 RH D AND RH W WITH 8 DUCT COLLAR RH D and RH W 6 Duct Collar...

Страница 11: ...27 4499 INSTALLATION OPERATION AND MAINTENANCE MANUAL RENEWAIRE COM DIMENSIONED DRAWINGS 3 3 RH D AND RH W WITH 10 DUCT COLLAR 3 4 RH D AND RH W WITH 12 DUCT COLLAR RH D 12 Duct Collar Dimensioned Dwg...

Страница 12: ...re a minimum of 1 2 inch clearance for cooling of the control box If any heater is installed horizontally maintain a minimum of 1 2 inch clearance above and beneath the unit In addition any heater tha...

Страница 13: ...H W ONLY High voltage electric service is to be brought into the unit through one of the factory provided knockouts located on the side of the control box Wiring is to be terminated on the terminal bl...

Страница 14: ...2 X 4 electrical junction box Open the thermostat housing by removing two screws on the bottom of the thermostat and lift the cover off Pull low voltage wiring through the opening in the back of the...

Страница 15: ...6 in this manual DIP SWITCH POSITIONS SWITCH 1 3 6 2 5 4 7 OFF O C INTERNAL SENSOR RH W ROOM APPLICATION REVERSE ACTING OUTPUT NOT USED 0 10 VDC NOT USED ON 0 F NOT USED NOT USED NOT USED FULL SET PO...

Страница 16: ...to press either the UP or DOWN arrow Blinks whenever a call for heat is being sent to the heater controller Ambient temperature if not blinking When either UP or DOWN arrow is pressed briefly the curr...

Страница 17: ...ugh one of the factory provided knockouts located on the side of the control box See the dimensioned drawings in Section 3 0 of this manual Terminate Thermostat Wiring on Terminal Block Grounding Lug...

Страница 18: ...COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 18 WIRING SCHEMATICS 6 1 RH D 120 VAC 6 2 RH D 208 240 VAC 1 2 3 4 5 AND 6 KW 6 0 WIRING SCHEMATICS RH D 120 VAC Wiring Schematic RH D...

Страница 19: ...ERS 19 1 800 627 4499 INSTALLATION OPERATION AND MAINTENANCE MANUAL RENEWAIRE COM WIRING SCHEMATICS 6 3 RH D 208 240 VAC 8 10 AND 11 5 KW RH D 208 240 VAC Wiring Schematic 8 10 11 5 KW 6 4 RH W 120 VA...

Страница 20: ...COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 20 WIRING SCHEMATICS 6 6 RH W 208 240 VAC 8 10 11 5 KW RH W 208 240 VAC Wiring Schematic 8 10 11 5 KW 6 5 RH W 208 240 VAC 3 4 5 6 KW...

Страница 21: ...eded airflow the heater will work at half the capacity This prevents overheating of the elements which would damage them For testing purposes remove the Airflow sensor AFS from the terminals A and A W...

Страница 22: ...emperature is lower than the lower bracket of the temperature range 3 Power has to be switch off and on RESET after dip switch is changed Example If dip switch 3 is set to external sensor ON and no se...

Страница 23: ...ion Useful diagnostic testing process in the PSSR testing procedure to force relays on and off for troubleshooting purposes Make sure the automatic and manual thermal reset are in the closed position...

Страница 24: ...a proportional output from the heater The controller requires a minimum of 0 1 VDC to initiate heating The automatic reset cut out 1250 F and the manual reset cut out 2000 F will cut off power to the...

Страница 25: ...CT HEATERS 25 1 800 627 4499 INSTALLATION OPERATION AND MAINTENANCE MANUAL RENEWAIRE COM MAINTENANCE 10 0 REPAIR PARTS 10 1 RH D 1 2 3 4 5 6 KW REPAIR PARTS RH D 1 2 3 4 5 6 KW Repair Parts 10 2 RH D...

Страница 26: ...ERS RENEWAIRE COM INSTALLATION OPERATION AND MAINTENANCE MANUAL 1 800 627 4499 26 MAINTENANCE 10 3 RH W 1 2 3 4 5 6 KW REPAIR PARTS RH W 1 2 3 4 5 6 KW Repair Parts RH W 8 10 11 5 KW Repair Parts 10 4...

Страница 27: ...lvanized steel Round duct collars High voltage terminal block connections Grounding lug Mounting flanges Note Electric duct heater designed for indoor ductwork installation only SERIES RH Electric Duc...

Страница 28: ...in significant energy savings Our ERVs are competitively priced simple to install easy to use and maintain and have a quick payback They also enjoy the industry s best warranty with the lowest claims...

Отзывы: