8. Decommissioning

8.1 Dementling the inverter

·Disconnect the inverter from DC input and AC output.
·Disconnect battery wiring.
·Wait for 5 minutes for de-energizing.
·Disconnect communication and optional connection wiring.

·Remove the inverter from the bracket.

8.2 Packaging

If possible, please pack the inverter with the original packaging.
If it is no longer available, you can also use an equivalent carton that meets the following requirements.
·Suitable for loads more than 25kg.

·With handle.
·Can be fully closed.

8.3 Storage

Store the inverter in dry place where ambient temperatures are always between -20 °C - +60 °C.

8.4 Disposal

When the inverter or other related components need to be disposed. Have it carried out according to local waste handling regulations. 

Please be sure to deliver wasted inverters and packing materials to certain site, where can assist relevant department to dispose and 

recycle.

Remark

If your inverter's information panel is not displaying a Fault light, check the following list to make sure that the present state of the 

installation allows proper operation of the unit.

·

Is the inverter located in a clean, dry, and adequately ventilated place?

·

Have the DC input breakers been opened?

·

Are the cables adequately sized and short enough?

·

Are the input and output connections and wiring in good condition?

·

Are the configurations settings correct for your particular installation?

·

Are the display panel and the communications cable properly connected and undamaged?

Contact Renac Power Customer Service for further assistance. Please be prepared to describe details of your system installation and 

provide the model and serial number of the unit.

Mgr EEPROM Fault

Meter Lost Fault

Dsp Lost Fault

BMS Protect OV

BMS Protect LV

BMS Protect ChrOC

The manager eeprom is fault. 
• Disconnect PV, grid and battery, then reconnect. 

• Or seek help from us, if not go back to normal state.

The communication between meter and Inverter is interrupted. 
• Check if the communication cable between meter and Inverter is correctly and well 

connected.

SCI communication fault
•Disconnect solar power PV+ , PV- and battery, reconnect them.
•Or seek help from us, if cannot go back to normal state.

BMS Cell Fault

BMS Other Fault

Battery cell error

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery other error

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery over voltage protect

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery under voltage protect

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery over current  charging protect

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

BMS Volt Fault

BMS Tepr Fault

BMS IN_COM Fault

BMS Dcov Fault

BMS RV Fault

BMS Relay Fault

Battery voltage sensor error

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery temperature sensor error

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

BMS internal communication fault.
• Disconnect battery, check wiring between inverter and battery

battery internal wiring 

then reconnect. 

• Or seek help from us, if not go back to normal state.

Battery input over voltage error

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery input transposition error

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

The battery relay is fault. 
• Disconnect battery, then reconnect. 

• Or seek help from us, if not go back to normal state. 

BMS Protect DishargeOC

BMS Protect TemHigh

BMS Protect TemLow

Battery over current discharging protect

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery temperature is high

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Battery temperature is low

• Wait for 5 minutes,, check again.
• Or seek help from us, if not go back to normal state.

Содержание A1-HV Series

Страница 1: ...A1 HV 3 0 A1 HV 3 68 A1 HV 5 0 A1 HV 6 0 UserManual Series A1 HV...

Страница 2: ...3 Installationprecaution 17 5 4 Availablespace 18 5 5 Preparation 18 5 6 Installationsteps 20 5 7 ElectricalWiringConnection 23 5 7 1 PVWiringConnection 24 5 7 2 InternalElectricalConnectionoftheBatte...

Страница 3: ...Target group This manual is intended for quali ed electrical technical personnel who are responsible for All in one ESS installation and commissioning in the energy storage system 1 3 Symbols used 1 4...

Страница 4: ...ersonal protective equipment including rubber gloves and protetive boots during the installation or maintenance Battery Module Leakage lf the battery modules leak electrolytes contact with the leaking...

Страница 5: ...er and battery power is insufficient the system will take power from grid to support loads PV Energy Storage System Keep the battery modules away from children Observe the documents Observe all docume...

Страница 6: ...res the battery will has enough energy to supply during a grid outage The back up load could be supported by PV and battery in the event of a blackout 1 Generated solar energy 2 Load consumption 3 Sto...

Страница 7: ...T BAT RS485 port Parallel communication Add Description Object Safety vent BAT connector CAN communication connector 1 2 3 Description Object CAN communication connector BAT connector 4 5 Description...

Страница 8: ...Grid Regulation Safety Regulation Certi cations Standards EMC EN 61000 6 1 EN 61000 6 2 EN 61000 6 3 EN 61000 6 4 EN 61000 4 16 EN 61000 4 18 EN 61000 4 29 3680 16 6000 26 1 3000 13 5000 21 7 220 230...

Страница 9: ...er bracket Bracket2 connect bracket1 and bracket3 Bracket1 connect BMC600 and bracket2 Frame1 it is used to x the inverter covert and inverter Frame2 It is used to x the terminal cover and inverter In...

Страница 10: ...ck that if the relating accessories and the materials are here you can see the accessories list in the table The instruction manual is an integral part of the unit and should therefore be read and kep...

Страница 11: ...ment overalls safe shoes protective gloves helmets goggles Do not walk or stand beneath or in the proximity of the load Avoid sudden movements and jolts when unloading and positioning the unit Interna...

Страница 12: ...fatigue or ageing This should be calculated by inspection of the design data of supporting material and consulting construction engineer 1 Take the BMC and base out of the package 2 Loose the two scre...

Страница 13: ...cket and hang the N1 HV inverter Transportation of the inverter needs at least 2 people each one needs to use the handles at the sides of the inverter Hang the inverter over the bracket move the inver...

Страница 14: ...act assembly is seated correctly PV string connection AC output connection Battery connection Battery power connection Battery communication connection EPS connection Earth connection Communication co...

Страница 15: ...A The litz wire ends have to be visible in the spring 5 Close the spring Make sure that the spring is snapped in B 6 Push the insert into the sleeve C 7 Tighten the cable gland to 2Nm D Use a suitable...

Страница 16: ...ual current of 30mA or higher is recommended There are two AC terminals and the assembly steps for both are the same just need to check one for Grid another for EPS The AC cable and micro breaker spec...

Страница 17: ...on the earthling connector Screw the screw of the earthling connector 3 Fully insert the conductors to the corresponding terminal and tighten the screws with the torque 0 8 Nm Pull cables outward to c...

Страница 18: ...he inverter in one of the Demand Response Modes DRMs de ned by the standard DRM 0 Operate the disconnection device DRM 1 Do not consume power DRM 2 Do not consume at more than 50 of rated power DRM 3...

Страница 19: ...Lower Fast 47 00Hz OK Grid Volt Protect Freq Protect Volt Protect Vac Lower Fast 000 0V OK Volt Protect Vac Lower Slow 180 0V OK Volt Protect Vac Upper Slow 260 0V OK Volt Protect Vac Upper Fast 265 0...

Страница 20: ...nd down button to review the parameter Press ESC to return to Status E EPS BMS Vbat V Ibat A Vchr V BMS Vdis V Ichr A Idis A Solar Vpv1 V Vpv2 V Solar Ipv1 A Ipv2 A Solar Ppv1 W Ppv2 W PV Conf Multi T...

Страница 21: ...0V OK Volt Protect Vac Upper Fast 265 0V OK Volt Protect Vac 10M Avg 255 0V OK Grid Volt Protect Freq Protect Press up or down button to select different work modes Press OK to con rm C Work Mode Sett...

Страница 22: ...tem Switch SysSwitch Turn On OK Menu History Setting SysSwitch This interface shows the information of the inverter such as series number and software version This section contains information and pro...

Страница 23: ...rectly connected Or seek help from us The residual current is high Please check if the insulation of electric wires is damaged Wait for a while to check if back to normal Or seek for help from us AD S...

Страница 24: ...communication between meter and Inverter is interrupted Check if the communication cable between meter and Inverter is correctly and well connected SCI communication fault Disconnect solar power PV P...

Страница 25: ...R T E C H N O L O G Y C O LT D Tel 86 0512 66677278 info renacpower com renacpo er com SMARTENERGYFORBETTERLIFE 422 00003 00 Block C 12 No 20 Datong Road Comprehensive Bonded Zone Suzhou Hi Tech Dist...

Отзывы: