Contents

This operating manual is a translation of the German original.

These operating manual must be read carefully before c
ommissioning/using the unit!

These instructions are part of the unit and must always be kept near 
to the site of installation or on the unit.

Subject to changes; errors and typographical errors excepted!

Dehumidification

4-6

Safety information

6

Unit description

7

Installation

8

Commissioning

9

Care and maintenance

10

Troubleshooting

11

Refrigeration circuit

12

Electrical wiring diagram SLE 40-80

13

Diagram of unit SLE 40-80

14

Spare parts list SLE 40-80

15

Maintenance log

16

Intended use

17

Customer service and warranty

17

Environmental protection and recycling

17

Unit dimensions

18

Technical data

19

3

Содержание SLE 40

Страница 1: ...Assembly and operating instructions Read the instructions prior to performing any task REMKO SLE series SLE 40 SLE 60 SLE 80 Pool dehumidifiers Edition GB N11...

Страница 2: ......

Страница 3: ...Subject to changes errors and typographical errors excepted Dehumidification 4 6 Safety information 6 Unit description 7 Installation 8 Commissioning 9 Care and maintenance 10 Troubleshooting 11 Refri...

Страница 4: ...ur es caping from buildings or materials is absorbed by the ambient air This increases their moisture content and ultimately results in corrosion mould rot peeling of paint coat ings and other unwante...

Страница 5: ...ncrete 140 190 l m lime sand bricks 180 270 l m The drying out of moist materials e g masonry takes place as fol lows The contained moisture moves from the inside of the material to its surface Evapor...

Страница 6: ...essed in a rise of temperature The time necessary for drying normally does not depend only on the unit capacity but is rather determined by the rate at which the material or parts of the build ing rel...

Страница 7: ...the cold evaporator heat is extracted from the room air and cooled to below the dew point The water vapour contained in the room air deposits as condensate or frost on the evaporator gills At the con...

Страница 8: ...n A solid or flexible drain con nection can be connected The drain hose must always be installed with a minimum gradi ent of 2 to enable the water to drain unhindered from the drip tray Alternatively...

Страница 9: ...trol The following functions are controlled monitored and displayed Safety Monitoring On off The LED display is located on the side of the unit The LED shows constant green when the unit is connected...

Страница 10: ...eaner whereby the condenser should be thorough ly cleaned If the evaporator gills are heavily fouled they should be cleaned carefully with soapy water Do not use a direct water jet e g high pressure c...

Страница 11: ...filter suction If the unit does not start after 45 min utes the following must be checked Check that the fan fans is are op erating Check whether the suction filter is clogged Check that the suction a...

Страница 12: ...alve 5 Dry filter 6 Solenoid valve 7 Fan 8 Non return valve Legend 1 Compressor 2 Evaporator 3 Condenser 4 Thermal expansion valve 5 Dry filter 6 Solenoid valve 7 Fan We reserve the right to make dime...

Страница 13: ...mper can be connected between terminals 25 and 26 The fan or fans then operate with out any control and monitoring in a continuous mode External hygrostat accessories Remove the both jumper at the ter...

Страница 14: ...the right to make dimensional and design changes in the interest of technical advances Diagram of unit SLE 40 80 4 8 25 1 3 12 28 27 20 16 38 2 9 11 15 24 30 35 18 22 7 6 5 Fig REMKO SLE 80 14 REMKO...

Страница 15: ...ndensate tray complete 1109149 1109170 1109182 11 Suction filter 1109150 1109171 1109183 12 Front panel 1109151 1109172 1109184 15 Evaporator sensor metal 1109160 1109160 1109111 16 Condenser sensor 1...

Страница 16: ...ture 17 Date Signature 18 Date Signature 19 Date Signature 20 Date Signature Remarks Model Serial No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned externally Unit cleaned internally...

Страница 17: ...nly high quality materials are used the majority of which are recyclable Make your contribution towards environmental protection by disposing of your old unit in an environmentally friendly manner Onl...

Страница 18: ...ktions nderungen die dem technischen Fortschritt dienen bleiben uns vorbehalten A 800 675 315 B 140 130 A A A A 50 90 35 22 30 52 14 Series Dimensions in mm A B SLE 40 950 890 SLE 60 1260 1190 SLE 80...

Страница 19: ...ity kg 0 6 0 95 1 6 Max air capacity m3 h 250 500 750 Sound pressure level LpA 1m 2 dB A 47 49 51 Power supply V Hz 230 1 50 Enclosure class IP X4 Max power consumption kW 0 72 1 05 1 65 Max rated pow...

Страница 20: ...40 r F 60 r F 80 r F A B C A B C Capacity diagram SLE 40 0 5 10 15 20 25 30 35 40 0 0 5 1 1 5 2 2 5 3 3 5 40 r F 60 r F 80 r F A B C A B C Capacity diagram SLE 60 Room temperature C Dehumidification...

Страница 21: ...21 0 5 10 15 20 25 30 35 40 0 1 2 3 4 5 40 r F 60 r F 80 r F A B C A B C Capacity diagram SLE 80 Room temperature C Dehumidification capacity l h...