Electrical wiring
8.1 General notes
A mains cable must be installed as the power
supply to the outdoor unit and a control line to the
indoor unit, with appropriate protection.
DANGER!
All electrical installation work is to be per-
formed by specialist companies. Disconnect
the power supply when connecting the elec-
trical terminals.
WARNING!
All electric lines are in accordance VDE regula-
tions to dimension and to lay.
NOTICE!
The electrical connection for the units must be
made at a separate feedpoint with a residual
current device in accordance with local regula-
tions and should be laid out by an electrician.
We recommend using shielded wires for the
control lines.
Check all plugged and clamped terminals to
verify that they are seated correctly and make
permanent contact. Tighten as required.
8.2 Connecting the indoor unit
The unit requires a six-wired control line from the
indoor unit to the outdoor unit.
n
We recommend installing a main / repair switch
on the building close to the indoor unit. This is
the responsibility of the customer.
n
Power is supplied to the outdoor unit, the
indoor unit is supplied via the control line from
the outdoor unit to the indoor unit.
n
The terminal blocks for establishing the con-
nections are located inside the unit.
n
If an optional condensate pump is used as an
accessory in conjunction with the unit, it may
be necessary to install an additional relay with
a higher contact rating after the switch-off con-
tact on the pump to switch off the compressor.
Make the connection as follows:
1.
The connection terminal block is located on
the right inside the unit (Fig. 47).
2.
Connect the unit to the control line from the
outdoor unit. See “Electrical wiring diagram”.
3.
Re-assemble the unit.
2
1
2
1
Fig. 47: Connecting the indoor unit
1: Electrical connection (terminal box)
2: Connection of refrigerant lines
REMKO RXT...DC
36
Содержание RXT 1053 DC
Страница 62: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm REMKO RXT DC 62 ...
Страница 63: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm 63 ...
Страница 70: ...No Designation 31 Cooling fin 32 Fin motor 33 Refrigerant connections cover REMKO RXT DC 70 ...
Страница 77: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 77 ...
Страница 80: ...No Designation 31 Crankcase heating 32 Terminal block cover 33 Side panel right REMKO RXT DC 80 ...
Страница 82: ...REMKO RXT DC 82 ...
Страница 83: ......