5.6 Minimum clearances
Observe the minimum clearances to allow access
for maintenance and repair work and facilitate
optimum air distribution.
Minimum clearances, outdoor units
RXT 523-1403 DC AT
2
1
A
B
C
D
E
Fig. 35: Minimum clearances, outdoor units
1: Air inlet / 2: Air outlet
Measure-
ments
(mm)
RXT 523-1403 DC AT
A
300
B
2000
C
600
D
200
E
400
Minimum clearances, indoor units
RXT 523-1403 DC IT
>1000mm
> 35mm
>35mm
> 35mm
Fig. 36: Minimum clearances, indoor units (all
measurements in mm)
A: Wall installation / B: Ceiling installation
5.7 Connection variants
The following connection variants can be used for
the refrigerant, condensate and control lines.
A
1
2
3
Fig. 37: Connection variants
A: Refrigerant piping
1: Outlet on the wall, right
2: Outlet through the wall, right
3: Outlet on the wall, down
5.8 Oil return measures
If the outdoor unit is installed at a higher level than
the indoor unit, suitable oil return measures must
be taken. Usually, an oil pump bend is installed for
every 5 metres of height difference.
1
A
B
2
Fig. 38: Oil return measures
A: Outdoor unit
B: Indoor unit
1: 1 x oil pump bend in suction pipe to outdoor
unit every 5 metres of height difference, radius:
50 mm
2: Max. 10 m
29
Содержание RXT 1053 DC
Страница 62: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm REMKO RXT DC 62 ...
Страница 63: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm 63 ...
Страница 70: ...No Designation 31 Cooling fin 32 Fin motor 33 Refrigerant connections cover REMKO RXT DC 70 ...
Страница 77: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 77 ...
Страница 80: ...No Designation 31 Crankcase heating 32 Terminal block cover 33 Side panel right REMKO RXT DC 80 ...
Страница 82: ...REMKO RXT DC 82 ...
Страница 83: ......