The system has been manufactured using state-of-the-art production methods and in house tested many times to 
ensure the 

unit

 is 100% in working order. If malfunctions should occur, please check the system as detailed in the list 

below. For installations with an indoor-outdoor system, observe the chapter “Trouble-shooting and customer serv-
ice” in both operating manuals.
Please inform your dealer if the system is still not working correctly after all the function checks have been per-
formed.

Touble-shooting and customer service

Code Alarm type

A1

Antifreeze alarm medium cycle

B2

Medium volume in the system too 

low; Water volume too low

Increase the medium temperature above 

+4°C; set the antifreeze setpoind

AHt

Excessive temperature at start

B1 / P16 Medium inlet temperature too high Reduce medium inlet

ALt

Insufficient/or excess temperature at 

start C/H

B1 / P19 Medium inlet temperature too high Reduce medium inlet

E1

Temperature 

probe medium inlet 

defec

tive

B1

Medium 

inlet

 probe defective

Check resistance at B1

E2

Temperature probe medium outlet 

defective

B2

Medium outlet probe defective

Check resistance at B2

E3

Temperature probe condenser defec-

tive

B3

Condenser probe defective

Check resistance at B3

E4

Pressure tranceducer refrigerant 

cycle defective

Bn/V+

Ambient temperature probe 

pressure transducer defective

Check voltage at B4

EHS

High supply voltage controller

Supply voltage too high

Check the voltage of the 

 transformer (both sides)

ELS

Low supply voltage controller

Tr

Supply voltage too low

Check the voltage of the 

 transformer (both sides)

EP1

EEPROM driver defective

Internal controller error

Replace the controller

EPb

EEPROM alarm at start

Config.

Internal controller error

Replace the controller

EPr

EEPROM alarm during operation

Config.

  Internal controller error

Replace the controller

FL

Flow 

switch

 has responded

ID1

Differential switch / Flow switch 

is activated

Are the following points OK:

- Medium flow rate 

- No air in the medium cycle 

- Circulation pump 

- Operation of the flow switch 

- Shut-off valves open 

- Medium pressure too low

Ht

Excessive temperature medium inlet B1 / P16 Is the medium inlet temperature 

above 50°C?

Reduce temperature of the medium

HP1

Pressure switch HD refrigerant cycle

ID3

refrigerant pressure too high

clean the condenser, check the conden-

ser fan, fan speed control and 4-way-

valve 

HP1

Tranceducer cycle excess pressure

Bn/V+

refrigerant pressure too high

clean the condenser, check the conden-

ser fan, fan speed control and 4-way-

valve

LP1

Pressure switch ND refrigerant cycle

ID4

ambient or medium temp. too low, 

refrigerant cycle leaky

Reports

LA

General reports

P08

D1

Report defrosting

Defrost cycle active

dF1-2

Defrosting time exce

eded

Defrosting 

period

Time of defrost cycle too long

Reset 

1. Alarms with automatic reset: 

The reset is carried out automatically.

2. Alarms with manual reset: 

The reset can only be carried out by a specialist after the reason for the alarm has been solved.

3. Alarms with semi-manual reset:  The reset is first carried out automatically, afterwards only a manual reset is possible by a specialist, after the reason for the alarm 

 

 

 

has been solved.

Alarm indicated by code

Содержание RVS 100H

Страница 1: ...tand By mode safety equipment is active but no operat ing mode is set Key Using this key the current menu can be resetted Key This key is used for selecting or e g to open close the set point or parameter Key Prolonged pressing 5 sec allows to switch between the operating modes Cooling and Stand by Short pressing displays the current values of the temperature probes B1 to B3 and the pressure tranc...

Страница 2: ...B3 16 Calibration B4 21 Digital filter 22 Input limit 23 Unit of measurement C F A01 Set point frost protection A02 Hysteresis frost protection A03 Time delay frost protection A04 Set point medium heating A05 Hysteresis medium heating A06 Probe medium heating A07 min antifreeze protection setting C01 min working time compressor C02 min down time compressor C03 Time delay On On compressor C04 Time ...

Страница 3: ...tage controller Tr Supply voltage too low Check the voltage of the transformer both sides EP1 EEPROM driver defective Internal controller error Replace the controller EPb EEPROM alarm at start Config Internal controller error Replace the controller EPr EEPROM alarm during operation Config Internal controller error Replace the controller FL Flow switch has responded ID1 Differential switch Flow swi...

Страница 4: ... FR Motor overload protection HP High pressure switch LP Low pressure switch M1 Compressor M2 Circulation pump M3 4 Condenser fan 1 2 RC1 Compressor crank case heater RF1 Defrost heater TA1 Transformer 230 24V TR1 Pressure transducer TS Temperature controller TX1 2Thermal contact fan 1 2 RVS 100H RVS 150H Probe inlet High pressure switch Probe outlet Low pressure switch Four way valve Enable conta...

Отзывы: