8.3 DIP switch, functions
Switch
Function
Setting
1)
Description
SW1_1
Control behav-
iour in cooling
mode
1 2
SW1
ON
The cooling request is terminated when the measured tempera-
ture actual value is equal to the set temperature setpoint value
(factory setting
1 2
SW1
ON
Cooling request is terminated when measured temperature
actual value is 2 °C lower than the set temperature setpoint
value
SW1_2
E-valve position
in stand-by mode
(heating opera-
tion)
1 2
SW1
ON
Injection valve stops at 96 steps (factory setting, greater
opening degree for oil return in larger systems)
1 2
SW1
ON
Injection valve stops at 72 steps (smaller opening degree for oil
return with smaller systems)
SW2
Non functional
SW3_1
Addressing
mode
1 2
SW3
ON
Save unit address (factory setting)
1 2
SW3
ON
Reset the unit address
SW3_2
Non functional
SW4
Fan behaviour in
heating mode
1 2
SW4
ON
After reaching the setpoint, the fan switches off for 4 minutes
and back on again for 1 minute. This procedure is repeated
(factory setting)
1 2
SW4
ON
After reaching the setpoint, the fan switches off for 8 minutes
and back on again for 1 minute. This procedure is repeated
1 2
SW4
ON
After reaching the setpoint, the fan switches off for 12 minutes
and back on again for 1 minute. This procedure is repeated
1 2
SW4
ON
After reaching the setpoint, the fan switches off for 16 minutes
and back on again for 1 minute. This procedure is repeated
REMKO MXV series
26