Series
LWM 80
LWM 110
LWM 150
Heater for anti-freeze protection power
supply (optional)
V/Ph/Hz
230/1~/50
Max. current consumption per phase
A
5.8
4.7
6.6
Rated current consumption for A7/W35
A
5.30
2.57
3.27
Rated power consumption for A7/W35
kW
1.22
1.60
2.04
Rated power consumption for A2/W35
kW
1.06
1.57
2.03
Max. power consumption
kW
1.3
3.2
4.5
Power factor at A7/W35 (cosφ)
--
0.9
Customer-provided electrical protection
A slow-
acting
16
3 x 20
Refrigerant
R454B
3)
Refrigerant, basic capacity
kg
1.3
1.4
1.6
Medium flow rate
water(according to EN 14511, at ∆t 5 K)
m
3
/h
1.1
1.4
1.6
Pressure loss (heating system), outdoor
kPa
80
70
60
Max. airflow volume
m
3
/h
3000
3500
4000
Max. operating pressure, water
bar
3
Hydraulic connection,
inlet/return flow (flat-sealing)
Inches (DN)
1 1/4 (32)
Recommended diameter for copper
piping to be used by the customer
mm
28
Max. sound power level in acc. with
DIN EN 12102:2008-09 and ISO 9614-2
dB(A)
54
56
58
Sound pressure level, LpA
4)
dB(A)
32
34
36
Tonality
dB(A)
0
Sound power level/sound pressure
levelnight operations/lowering mode
dB(A)
47/25
49/27
51/29
Dimensions (height/width/depth)
mm
1600 x 1000 x 850
Enclosure class
--
IP X4
Weight
kg
200
220
1)
COP = coefficient of performance in accordance with EN 14511, VDE tested, rated compressor frequency
60 Hz
2)
EER = energy efficiency ratio in accordance with EN 14511, rated compressor frequency 60 Hz
3)
Contains greenhouse gas according to Kyoto protocol, GWP 466
4)
Distance 5 m, VDE tested, A7/W55, with half-spherical propagation
Information provided without guarantee! We reserve the right to make technical changes within the frame-
work of technical advancement.
REMKO LWM series
8