background image

Before commissioning

Anti-freeze protection for the medium

If a water-glycol mixture is used, it is to be pre-

mixed before being put in the system. The desired

concentration is then to be checked.

Bleeding the system

n

Air may still be in the pipe lines after the leak

testing. This is carried during operation of the

circulation pump to the automatic bleeding

valves or to the cold water drain. In this case it

is necessary to bleed the system again.

n

The non-circulating pressure must then be

adjusted to the required system pressure.

 NOTICE!

During manual bleeding, any glycol mixtures

which escape must be disposed of separately.

Do not feed them into the condensate tray!

Diaphragm expansion vessel

n

The preliminary pressure for the diaphragm

expansion vessel must be adjusted individually

to the system layout, the volume of the medium

and the installation site.

Valves for hydronic balancing

n

The calculated excess pressure in the pipe net-

work layout at the individual cold water outlets

must be adjusted with the valves for hydronic

balancing.

Safety valve

n

The safety valves and their correct function

must be checked.

n

The drain line for the valves is to be checked

for function and leak tightness.

Commissioning

 NOTICE!

Commissioning should only be performed by

specially trained personnel and documented

after the certificate has been issued.

 NOTICE!

Observe the manuals for the unit and all other

components when commissioning the entire

system.

Function test for cooling operating mode

1.

Switch the power supply on.

2.

Open all shut-off valves if necessary.

3.

Switch on the chiller and the corresponding

circulation pump. The outlet temperature

must be b4 and +18 °C.

4.

Use the controller to switch on the unit and

select the cooling mode, maximum fan speed

and lowest target temperature.

5.

Measure and record all the required values in

the commissioning report and check the

safety functions.

6.

Check the unit control system using the func-

tions described in the "Operation" chapter.

7.

Check that the condensate drainage line is

functioning correctly by pouring distilled

water into the condensate tray. A bottle with

a spout is recommended for pouring the

water into the condensate tray.

Function test of heating operating mode

1.

Switch the power supply on.

2.

Open all shut-off valves if necessary.

3.

Switch on the heating system and the corre-

sponding circulation pump. The outlet tem-

perature must lie b35 and +70 °C.

4.

Use the controller to switch on the unit and

select the heating mode, maximum fan

speed and highest target temperature.

5.

Measure and record all the required values in

the commissioning report and check the

safety functions.

6.

Check the unit control system using the func-

tions described in the "Operation" chapter.

 

 

 

 

 

27

Содержание KWK 125 ZW

Страница 1: ...ad the instructions prior to performing any task REMKO KWK ZW series KWK 125 ZW KWK 165 ZW KWK 205 ZW KWK 255 ZW KWK 305 ZW Cold water wall and ceiling units 0256 2020 02 Edition 1 en_GB KWK 355 ZW KW...

Страница 2: ...rating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject to modifications No li...

Страница 3: ...Technical data 7 2 1 Unit data KWK 125 255 ZW 7 2 2 Unit data KWK 305 455 ZW 9 2 3 Unit data KWK 535 725 ZW 11 2 4 Unit dimensions 13 3 Design and function 14 3 1 Unit description 14 3 2 System layout...

Страница 4: ...fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This comb...

Страница 5: ...e structures walls or floors n Mobile units must be set up securely on suit able surfaces and in an upright position Sta tionary units must be permanently installed for operation n The units and compo...

Страница 6: ...nd recycling Disposal of packaging All products are packed for transport in environ mentally friendly materials Make a valuable contri bution to reducing waste and sustaining raw mate rials Only dispo...

Страница 7: ...33 40 31 39 47 Power supply V Ph Hz 230 1 50 Enclosure class IP X0 Electrical rated power consumption 1 W 35 39 47 51 Electrical rated current consumption 1 A 0 15 0 17 0 20 0 22 Operating medium max...

Страница 8: ...number 1962 1963 1964 1965 EDP no 1664300 1664310 1664320 1664330 1 Air inlet temperature TK 27 C FK 19 C medium inlet 7 medium outlet 12 C 0 glycol concentra tion max air flow volume 2 Air inlet temp...

Страница 9: ...Power supply V Ph Hz 230 1 50 Enclosure class IP X0 Electrical rated power consumption 1 W 59 71 97 Electrical rated current consumption 1 A 0 26 0 31 0 42 Operating medium max 35 ethylene glycol max...

Страница 10: ...r 1966 1967 1968 EDP no 1664340 1664350 1664360 1 Air inlet temperature TK 27 C FK 19 C medium inlet 7 medium outlet 12 C 0 glycol concentra tion max air flow volume 2 Air inlet temperature TK 20 C me...

Страница 11: ...32 41 51 Power supply V Ph Hz 230 1 50 Enclosure class IP X0 Electrical rated power consumption 1 W 107 120 139 Electrical rated current consumption 1 A 0 47 0 52 0 60 Operating medium max 35 ethylen...

Страница 12: ...er 1969 1970 1971 EDP no 1664370 1664380 1664390 1 Air inlet temperature TK 27 C FK 19 C medium inlet 7 medium outlet 12 C 0 glycol concentra tion max air flow volume 2 Air inlet temperature TK 20 C m...

Страница 13: ...m Dimen sion KWK 125 ZW KWK 165 ZW KWK 205 ZW KWK 255 ZW KWK 305 ZW KWK 355 ZW KWK 455 ZW KWK 535 ZW KWK 595 ZW KWK 725 ZW A 545 545 745 745 945 945 1145 1145 1345 1345 B 425 425 625 625 825 825 1025...

Страница 14: ...rature regulation or via the building management system The unit consists of a fin heat exchanger circula tion fan and two condensate trays for horizontal and vertical installation The available acces...

Страница 15: ...e cooled operating medium is then fed in once again to the unit medium circuit With 2 conductor systems which are used for cooling or heating the heating capacity of cold water air con ditioning syste...

Страница 16: ...2 1 3 6 5 4 B1 B2 B3 1 1 3 3 4 4 C 7 8 9 10 Fig 5 Example of system layout of 4 conductor system cold water air conditioning system A Outdoor area B1 3 Indoor area 1 2 3 C Heating room 1 Chilled heati...

Страница 17: ...d must be observed Fig 6 Precision room temperature controller sur face mounted installation Fig 7 Room temperature controller surface mounted installation Example controls 1 2 Fig 8 Individual contro...

Страница 18: ...te drainage line In dual systems with cooling and heating modes the requirements of the current energy savings ordinance EnEV are to be complied with n Seal off open refrigerant piping with suitable c...

Страница 19: ...ctions on the new connection side 5 Feed the connections through the newly cre ated holes up to the stop 2 2 2 Heat exchanger mounting bolts 6 Place the tear resistant plastic film on the pipe bend si...

Страница 20: ...a depth of at least 300 cm n of the heat exchanger with openings of the unit width and a depth of at least 400 cm Air guidance Various duct components are available as accessories for the units The po...

Страница 21: ...components provided by the customer are to be used the dimensions of the air inlet and outlet open ings shown below can be adopted for laying out the components 106 186 A A 1 2 Fig 13 Dimensions of d...

Страница 22: ...d towards the centre of the room 1 Mark the mounting points according to the mounting s dimensions on structurally acceptable building components and secure the unit 2 Check again that the unit is lev...

Страница 23: ...ed off and the medium is fed past the heat exchanger through the bypass The bypass serves to ensure the minimum medium flow rate for the chiller The time between being fully open and fully closed can...

Страница 24: ...condensate tray Horizontal mounting The condensate drainage line can be connected directly to the condensate tray If a valve assembly is used the condensate is conveyed to the unit s pan and is draine...

Страница 25: ...and ensure that the line is durably leak tight NOTICE The condensate drainage connection of the condensate tray which is not used must be per manently sealed a cap or similar A 1 B 1 Fig 15 Condensat...

Страница 26: ...r making the connections and the plug are located behind the unit s housing on the right side of the unit Proceed as follows to establish the connection 1 Open the unit cover 2 Insert the cables into...

Страница 27: ...pecially trained personnel and documented after the certificate has been issued NOTICE Observe the manuals for the unit and all other components when commissioning the entire system Function test for...

Страница 28: ...using the controller 3 Switch off the power supply to the unit 4 Check the unit for visible signs of damage and clean it as described in the Care and maintenance chapter Permanent shutdown Ensure tha...

Страница 29: ...function Check the pump and clean it if necessary Regulation not activated Has the operating mode controller been correctly set Check the setting and oper ation Electrical surges caused by thunderstor...

Страница 30: ...ined away and has col lected in the condensate drainage line Is there an incline on the condensate drainage line and is it clear Route the condensate drainage line with an incline and clean it Condens...

Страница 31: ...rior to long shut down periods Maintenance n It is recommended that you take out a mainte nance contract with an annual service from an appropriate specialist firm This enables you to ensure the opera...

Страница 32: ...properly in the air before fitting it back into the unit 7 Carefully insert the filter Ensure that it locates correctly 8 Switch the power supply back on Fig 19 Cleaning with a vacuum cleaner Fig 20...

Страница 33: ...clean the fan Pro ceed as follows 1 Disconnect the power supply to the unit 2 Loosen the screws on the cover 1 3 Remove the cover from the unit 4 Clean the filter fan as described above and re assembl...

Страница 34: ...parts 13 1 Exploded view of the unit KWK 125 KWK 725 ZW 5 1 2 3 4 Fig 22 Exploded view of the unit We reserve the right to modify the dimensions and design as part of the ongoing technical developmen...

Страница 35: ...RTANT To ensure the correct delivery of spare parts please always the device type with the corresponding serial number see type plate No Designation 1 Air filter 2 Valve unit incl control board 3 Heat...

Страница 36: ...25 M Maintenance 31 Malfunctions Checks 29 Possible causes 29 Remedial measures 29 Minimum clearances 19 O Ordering spare parts 35 S Safety Dangers of failure to observe the safety notes 4 General 4...

Страница 37: ...37...

Страница 38: ...REMKO KWK ZW series 38...

Страница 39: ......

Страница 40: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Отзывы: