Electrical wiring
8.1 General notes
A protected power supply cable is to be connected
to the indoor unit and a five-core control line to the
outdoor unit respectively.
DANGER!
All electrical installation work is to be performed
by specialist companies. Disconnect the power
supply when connecting the electrical terminals.
WARNING!
All electric lines are in accordance VDE regula-
tions to dimension and to lay.
NOTICE!
The electrical connection for the units must be
made at a separate feedpoint with a residual
current device in accordance with local regula-
tions and should be laid out by an electrician.
We recommend using shielded wires for the
control lines.
Check all plugged and clamped terminals to
verify that they are seated correctly and make
permanent contact. Tighten as required.
8.2 Connecting the indoor unit
n
We recommend that a mains/repair switch be
installed near the outdoor unit.
n
The terminal blocks for making the connections
are located at the rear of the unit. When the
unit is installed, measurements can be made
from the front by removing the cover.
n
If a condensate pump, which is available as an
accessory, is used in conjunction with the unit,
refer to the electrical wiring diagram (Fig. 34).
Make the connection as follows:
1.
Choose the power supply cross-section in
accordance with the specifications!
2.
Open the air inlet grill.
3.
Remove the covers on the right-hand side
4.
Connect the customer-laid power supply and
control line to the terminals (Fig. 31). See
also the “Electrical wiring diagram” (Fig. 33).
5.
Re-assemble the unit.
2
1
4
3
1
Fig. 31: Connecting the indoor unit
1: Cover
2: Strain relief
3: Terminal block for the power supply and control
line
4: Control line to outdoor unit
REMKO JBW...DC