5.6 Connection of the indoor unit when the refrigerant piping is installed
under the plaster
If the customer routes the refrigerant piping to the unit underneath the plaster, observe the following note.
The principal connection options can be found in the "Connection variants for the indoor unit" and "Wall
bracket" chapters.
If the refrigerant piping is routed underneath the plaster, ensure that the customer-fitted refrigerant piping
does not protrude from the wall at a 90° angle. As a result of the required bending radius, the unit would then
be very difficult to connect or would possibly be impossible to fasten to the wall mount.
For this reason, route the customer-fitted refrigerant piping with as flat an angle as possible (<30°) out of the
wall, from the left and into the unit. This enables direct connection of the refrigerant piping (see Fig. 20).
NOTICE!
The flare connection should be implemented in the unit in the case of under-plaster installations. A
detachable connection below the level of the plaster is not generally permitted!
Fig. 20: Under the plaster installation (View from above)
REMKO ATY
20