User level - #SETTING menu
Parameter
Adjustment range Description
Factory setting
Customer
setting
SUM/WIN
15 to 30 °C
Used to set the outside temperature
above which heating will be shut down.
4
The heating pumps are shut down.
4
The burner will only start for
domestic hot water needs.
4
The symbol
p
appears.
22 °C
NO
Heating is never shut down automatically
CALIBR. OUT
Outside sensor calibration: Used to
correct the outside temperature
Outside temperature
CALIBR. ROOM B
(1)(1)
Calibration of the room sensor on
circuit B: Is used to set a room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room temperature
of circuit B
OFFSET ROOM B
(1)
-5.0 to +5.0 °C
Room offset on circuit B: Is used to set a
room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
0.0
ANTIFR. ROOM B
0.5 to 20 °C
Room temperature at which the
antifreeze mode is activated on circuit B
6 °C
CALIBR. ROOM C
(2)(1)
Calibration of the room sensor on
circuit C: Is used to set a room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room temperature
of circuit C
OFFSET ROOM C
(3)
(1)
-5.0 to +5.0 °C
Room offset on circuit C: Is used to set a
room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
0.0
ANTIFR. ROOM C
(4)
0.5 to 20 °C
Room temperature antifreeze activation
on circuit C
6 °C
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter is only displayed if a room sensor is connected to the circuit concerned
(3) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence
(4) The parameter is only displayed if the circuit concerned is actually connected
5.6.3.
Professional settings
1. Access the installer level: Press key
-
for around 5 seconds.
2. To set the following parameters:
4
Turn the rotary button to scroll through the menus or
modify a value.
4
Press the rotary button to access the menu selected
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer
to the chapter: "Browsing in the menus", page 31.
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
M
g
m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
iSense Pro DIN - AD280
5. Operating the appliance
12/04/2011 - 300025649-001-B
40