![REMEHA E-HP AW 168 Cool Plus B Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/remeha/e-hp-aw-168-cool-plus-b/e-hp-aw-168-cool-plus-b_installation-and-user-manual_1436991011.webp)
Unit
44 Cool Ace B
88 Cool Ace B
168 Cool Ace B
Nominal current (based on air 7 and temper
ature of 55 °C of the water supply)
A
19.1
38.2
2x 43.2
Connection to boiler
Inch
1 1/2"
2"
2 1/2"
Weight
kg
460
790
2300
Refrigerant weight
kg
14
18
36 (2x18)
(1) In case a supply temperature below 17 °C is requested, an external 4-way valve must be used.
(2) In accordance with ISO 9614-2 under condition A7/W55.
(3) The accumulated starting current is calculated with the stating current of the second compressor and the maximum operating current
(MCC) of the first compressor, seen as the worst-case scenario.
Tab.4
Technical parameters
E-HP AW
E-HP AW 44
(Cool)
E-HP AW 88
E-HP AW 168
(Cool)
Air-to-water heat pump
Yes
Yes
Yes
Water-to-water heat pump
No
No
No
Brine-to-water heat pump
No
No
No
Low-temperature heat pump
No
No
Yes
Equipped with a supplementary heater
No
No
No
Heat pump combination heater
No
No
No
Rated heat output under average climate condi
tions
Prated
kW
23
53
112
Rated heat output under colder climate condi
tions
Prated
kW
-
-
-
Rated heat output under warmer climate condi
tions
Prated
kW
-
-
-
Declared capacity for heating for part load at in
door temperature 20 °C and outdoor temperature
T
j
T
j
= -7 °C
Pdh
kW
19.2
46.8
98.6
T
j
= +2 °C
Pdh
kW
29.8
59.5
131.0
T
j
= +7 °C
Pdh
kW
34.1
68.3
155.2
T
j
= +12 °C
Pdh
kW
38.6
77.2
180.8
T
j
= bivalent temperature
Pdh
kW
20.0
46.8
98.8
T
j
= operation limit temperature
Pdh
kW
20.0
43.6
94.3
T
j
= -15 °C (if TOL < -20 °C)
Pdh
kW
-
-
-
Bivalent temperature
T
biv
°C
-10
-7
-10
Cycling interval capacity for heating
Pcych
kW
-
-
-
Degradation co-efficient
Cdh
—
0.99
0.99
0.99
Seasonal space heating energy efficiency under
average climate conditions
ƞ
s
%
161
168
174
Seasonal space heating energy efficiency under
colder climate conditions
ƞ
s
%
-
-
-
Seasonal space heating energy efficiency under
warmer climate conditions
ƞ
s
%
-
-
-
Declared coefficient of performance or primary
energy ratio for part load at indoor temperature
20 °C and outdoor temperature
T
j
T
j
= -7 °C
COPd
-
2.82
3.29
3.30
T
j
= +2 °C
COPd
-
4.10
4.23
4.43
T
j
= +7 °C
COPd
-
4.85
4.93
5.23
T
j
= +12 °C
COPd
-
5.55
5.43
6.03
T
j
= bivalent temperature
COPd
-
2.82
3.29
3.30
T
j
= operation limit temperature
COPd
-
2.82
3.02
3.10
3 Technical specifications
7697291 - v.05 - 11032022