background image

Time Relay

MT-TUA-17S-11-9240

Instruction

Manual

Caution, Hazards

Time relays must be installed by qualified electricians. All and

any electrical connections of the time relay shall comply with

the appropriate safety standards.

Disposal of Electrical Waste

All electrical waste should be

disposed of in compliance with

current WEEE regulations.

Description of Relay:

Multifunction time relay

MT-TUA-17S-11-9240

10 time functions

8 time ranges

Cadnium - free contacts

AC/DC input voltages

Module width: 17.5mm

Direct mounting on 35mm din rail in accordance with PN-EN 60715 (wiring: 1 x 2.5mm

2

, 2 x 1.5mm

2

)

Application: in low voltage systems

Compliance with standard PN-EN 61812-1

Recognition, certification, directives:

Connection Diagram:

A2 N (-)

S

L (+)

Supply voltage:

12.....240V AC/DC
AC: 50/60Hz

A1

Relay Features:

Supply terminals (A1, A2)

and control contact

terminal (S)

Green LED U ON

Indication of supply voltage U

Yellow LED R

ON/OFF

Output relay status

Time adjusting dial

Range and function

ON/OFF adjusting dial

Function adjusting dial

Output terminals

(15, 16, 18)

Output Circuit - Contact Data

Number and type of contacts

1P / 1CO (Changeover)

Contact material

AgNi

Max. switching voltage

400V AC / 300V DC

Rated Load

AC1: 16A / 250V AC

Min. breaking capacity

0.3W 5V, 5mA

Input Control Circuit

Rated Voltage

12...240V AC/DC AC 50/60 Hz terminals (+) A1 - (-) A2

Overvoltage category

II

Insulation pollution degree

1

Dielectric strength

Input - output: 2 500V AC

Contact clearance: 1 000 V AC

General Data

Dimensions (L x W x H)

90

x 17.5 x 63.5mm (weight: 64g)

Storage / operating temperature

- 40 to + 70

o

C / - 20 to + 45

o

C

Cover protection category

IP20 PN-EN 60529

Time Module Data

Functions

E, Wu, Bp, Bi, T, R, Ws, Wa, Esa, B, (ON/OFF

)

Time ranges

1s

; 10s; 1 min.; 1 h; 10h; 1 d; 10 d

Setting accuracy

+ 5%

Repeatability

+ 5%

Technical Data:

Type of insulation: Basic

Type of clearance: micro-disconnection

Length with 35mm rail taps: 98.8mm

Permanent switching ON and OFF

For first range set point (1s) setting accuracy and repeatability are smaller than

the given ones in technical parameters (significant influence of the operational

relay operating time, processor start time, and at the moment of supply switching

as referred to the AC supply course).

For the minimum to maximum direction of the time adjust dial.

Relpol_Multi_Timer_Instructions_Final:Layout 1  7/1/11  09:43  Page 2