Installing the New Water Heater (cont’d)

The combustion and ventilation air flow must not be obstructed.

All vent gases must be completely vented to the outdoors of

the structure (dwelling). Install only the draft hood provided

with the new water heater and no other draft hood.

The water heater must be connected to a roof jack: The vent

pipe from the water heater to the roof jack must be no less

than the diameter of the draft hood outlet (min. 3 inches) on

the water heater.

This water heater may be installed with single wall or Type B

vent pipe connection to the draft hood and the following

U.L. listed roof jacks not furnished.

Van Dyke Ind. No. 987

Vent Line No. 2073

White Metal Products 3RJ

There must be a minimum clearance of 12 inches between

the top of the draft hood and the top of the enclosure.

The draft hood and combustion air inlet to the water heater

must be in the same atmospheric pressure zone. Do not sep-

arate by a wall, shelf, ceiling, partition, or any other means.

There must be a minimum of 6 inch clearance between sin-

gle wall vent pipe and any combustible material. Fill and

seal any clearance between single wall vent pipe and com-

bustible material with mortar mix, cement, or other noncom-

bustible substance. For other than single wall, follow vent

pipe manufacturer’s clearance specifications.

11

Filling the Water Heater

To fill the water heater with water:

1. Close the water heater drain valve by turning the han-

dle to the right (clockwise). The drain valve is on the

lower front of the water heater.

2. Open the cold water supply valve to the water heater.

NOTE: The cold water supply valve must be left open

when the water heater is in use.

3. To insure complete filling of the tank, allow air to exit

by opening the nearest hot water faucet. Allow water

to run until a constant flow is obtained. This will let air

out of the water heater and the piping.

4. Check all new water piping for leaks. Repair as needed.

DRAFT

HOOD

DRAFT HOOD

VENT

VENT CAP

VENT TO

OUTDOORS

DRAFT

HOOD

SCREW

DRAFT HOOD INSTALLATION

ROOF JACK

Venting

1. Place the draft hood legs in the receiving holes on the

top of the water heater. The legs will snap in the holes

to give a tight fit.

2. Place the vent pipe over the draft hood. With the vent

pipe in position, drill a small hole through both the

vent pipe and draft hood. Secure them together with a

sheet metal screw.

CAUTION

Never use this water heater unless it is completely filled

with water. To prevent damage to the tank, the tank must

be filled with water. Water must flow from the hot water

faucet before turning “ON” gas to the water heater.

WARNING

To insure proper venting of this gas-fired water heater, the cor-

rect vent pipe diameter must be utilized. Any additions or dele-

tions of other gas appliances on a common vent with this water

heater may adversely affect the operation of the water heater.

Consult the local gas utility if any such changes are planned.

WARNING

The water heater with draft hood installed must be connected

to a roof jack which terminates to the outdoors. Never operate

the water heater unless it is vented to the outdoors and has

adequate air supply to avoid risks of improper operation,

explosion or asphyxiation.

WARNING

Obstructed or deteriorated vent systems may present serious

health risk or asphyxiation.

WARNING

The vent pipe from the water heater must be no less than

the diameter of the draft hood outlet on the water heater.

WARNING

Failure to have required clearances between vent piping

and combustible material will result in a fire hazard.

WARNING

VENT DAMPERS - Any vent damper, whether it is operated ther-

mally or otherwise must be removed if its use inhibits proper

drafting of the water heater.

Thermally Operated Vent Dampers: Gas-fired water heaters hav-

ing thermal efficiency in excess of 80% may produce a relatively

low flue gas temperature. Such temperatures may not be high

enough to properly open thermally operated vent dampers. This

would cause spillage of flue gases and may cause carbon monox-

ide poisoning.

Vent dampers must bear evidence of certification as complying

with the current edition of the American National Standard ANSI

Z21.68 (ANSI Z21.66 & 67, respectively, cover electrically and

mechanically actuated vent dampers).

Before installation of any vent damper, consult the local  gas util-

ity for further information.

Содержание 184123-000

Страница 1: ... phone Follow the gas suppli er s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Improper installation adjustment ...

Страница 2: ...ated gas in the area Search for odor of gas by sniffing at ground level in the vicinity of the appli ance If odor is detected follow steps indicated at For Your Safety on the cover page of this manual then leave the premises WARNING Improper installation adjustment alteration service or maintenance can cause DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE Refer to this manual for assis tance or cal...

Страница 3: ...oors Never operate the water heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation WARNING Obstructed or deteriorated vent systems may present a serious health risk or asphyxiation WARNING Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors Spray can pro...

Страница 4: ... Propane L P Gas To Natural Gas 14 Installation Checklist 15 Lighting 16 17 Temperature Regulation 18 For Your Information 19 20 Start Up Conditions 19 Draft Hood Operation 19 Condensation 19 Smoke Odor 19 Thermal Expansion 19 Strange Sounds 19 Operational Conditions 19 20 Smelly Water 19 20 Air In Hot Water Faucets 20 High Temperature Shut Off System 20 Not Enough or No Hot Water 20 Water Is Too ...

Страница 5: ...se DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fired water heater It also contains warnings through out the manu al that you must read and be aware of All warnings and all instructions are essential to the proper opera tion of the water heater and your safety Since we can not put everything on the fi...

Страница 6: ...m requires water at temperatures higher than required for other uses the hot water system may require a means such as a mixing valve to be installed to temper the water at certain points of use Some peo ple are more likely to be permanently injured by hot water than others these include the elderly children the infirm or the physically mentally handicapped Before immersing yourself or anyone else ...

Страница 7: ...consult these manufacturers for correct sizing If the opening is covered by louvers or screen the total free area must be 32 square inches Locating the New Water Heater When a drain pan is required an exterior door with lou vered openings must be used as shown in figure 1 page 6 INSTALLATION CLEARANCES TOP VIEW 1 MIN 1 MIN 4 MIN 1 MIN NOTE DOOR MUST BE ON OUTSIDE WALL OF MANUFACTURED HOME Figure 3...

Страница 8: ...on or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this warning may result in a fire hazard WARNING Minimum clearances between the water heater and combustible and noncombustible construction are 1 at the sides and rear 4 at the front and 6 from the vent pipe Clearance from the top of the draft hood is 12 Refer to the label on t...

Страница 9: ...ystem shall be subjected to a pres sure test The test shall be made by subjecting the sys tem to air or water at 100 psi for 15 minutes without loss of pressure When air pressure is used the water heater shall not be connected during the test WHEN AIR TESTING REMOVE THE WATER LINES FROM THE WATER HEATER HOT OUTLET COLD INLET 9 WARNING This water heater shall not be connected to any heating systems...

Страница 10: ...g must not be blocked or reduced in size under any circumstances Excessive length over 30 feet or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between the relief valve and the tank Do not connect tubing directly to discharge drain unless a 6 air gap is provided To prevent bodily injury hazard to life...

Страница 11: ...od legs in the receiving holes on the top of the water heater The legs will snap in the holes to give a tight fit 2 Place the vent pipe over the draft hood With the vent pipe in position drill a small hole through both the vent pipe and draft hood Secure them together with a sheet metal screw CAUTION Never use this water heater unless it is completely filled with water To prevent damage to the tan...

Страница 12: ... chemical vapors Spray can propellants cleaning solvents refrigerator and air conditioner refrigerants swimming pool chemicals calcium and sodium chloride waxes bleach and process chemicals are typical compounds which are potentially corrosive WARNING Make sure the gas supplied is the same type listed on the model rating plate The inlet gas pressure must not exceed 10 5 in water column 2 6kPa for ...

Страница 13: ...d from PILOT to OFF unless knob is depressed slightly DO NOT FORCE Step 11 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety in formation on For Your Safety label If you don t smell gas go to the next step Step 12 Find pilot follow metal tube from gas control The pilot is located in front of the burner See Figure 7 page 14 Step 13 If you don t smell gas tur...

Страница 14: ...ilot orifice G brass color and in Step 8 turn control screw B in Figure 4 clockwise to stop Screw must be in OUT posi tion for Natural gas See Instruction Label for orifice sizes Maximum Supply Pressure 10 5 W C For Nat Gas 13 W C for Propane L P Gas Minimum Supply Pressure 5 W C for Nat Gas 11 W C For Propane L P Gas Installing the New Water Heater cont d B A GAS CONTROL KNOB TEMPERATURE ADJ DIAL...

Страница 15: ...URE RELIEF VALVE TEE SHUTOFF VALVE DISCHARGE PIPE Do not cap or plug Must terminate beneath manufactured home MODEL RATING PLATE 6 Is there proper clearance between the water heater and anything that might catch fire See the Locating the New Water Heater section 7 Do you have adequate ventilation so that the water heater will operate properly See the Locating the New Water Heater section 8 Is the ...

Страница 16: ...e attempting to light or relight the water heater s pilot or turning on a nearby electrical light switch be absolutely sure there is no accumulated gas in the area Search for odor of gas by sniffing at ground level in the vicinity of the appliance If odor is detected follow the steps indicated at For Your Safety on the cover page of this manual then leave the premises WARNING AN ODORANT IS ADDED T...

Страница 17: ...his label If you don t smell gas go to the next step 6 Remove or open inner door located below the gas control unit Figure 11 7 Find pilot follow metal tube from gas control The pilot is located in front of the burner 8 If you don t smell gas turn knob on gas control counter clockwise to PILOT position Figure 9 9 Push in control knob all the way and hold down Immediately light the pilot with a mat...

Страница 18: ...RNING HOTTER WATER CAN SCALD Water heaters are intended to produce hot water Water heated to a temperature which will satisfy clothes washing dish washing and other sanitizing needs can scald and permanently injure you upon contact Some people are more likely to be permanently injured by hot water than others These include the elderly children the infirm or physically mentally handicapped If anyon...

Страница 19: ... others have installed devices such as pressure reducing valves check valves back flow preventers etc to control these types of problems When these devices are not equipped with an internal by pass and no other measures are taken the devices cause the water system to be closed As water is heat ed it expands thermal expansion and closed systems do not allow for the expansion of heated water The wat...

Страница 20: ...eat the water and seem like less hot water 9 If you cannot find what is wrong call the local gas utility and or plumbing contractor WATER IS TOO HOT 1 The temperature adjustment dial may be set too high See the Temperature Adjustment section NOTE A period of time is necessary after an adjust ment has been made for the water temperature to reach the new temperature setting 2 If lower temperature se...

Страница 21: ...G Obstructions and deteriorated vent systems may pre sent serious health risk or asphyxiation WARNING Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chem ical vapors Spray can propellants cleaning solvents refrigerator and air conditioner refrigerants swimming pool chemicals calcium and sodium chloride waxes bleach and process chemicals are ty...

Страница 22: ...r heater Failure to install and maintain a new properly listed tempera ture pressure relief valve will release the manufacturer from any claim which might result from excessive temperature or pressure TEMPERATURE PRESSURE RELIEF VALVE DISCHARGE PIPE 22 WARNING When checking the temperature pressure relief valve oper ation make sure that 1 no one is in front of or around the outlet of the temperatu...

Страница 23: ...form and drip into the fire or run on the floor This is common at the time of startup after installation and when incoming water is cold Water in the water heater bottom or on the floor may be from condensation loose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other a...

Страница 24: ...Illustrated Now that you have purchased this Water Heater should a need ever exist for repair parts or service simply contact the com pany it was purchased from or direct from the manufacturer listed on the model rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on request or parts will be shipped at prevailing price and...

Отзывы: