C. Connecting the Neutral and Ground Wire

1.

Find the white wire (Neutral) and the green wire (ground)

among the wires from the transfer switch that you have
inserted into the load center.

2.

Strip approximately 5/8” from the end of the white wire.

Locate the neutral bar and partially unscrew a terminal
screw on the bar. Insert the stripped end of the wire into
the side of the bar under the screw and retighten the screw.
(Figure 4)

3.

Locate the ground bar. (It should be labeled.)  Connect the

green wire to the ground bar in the same way as in step
#2. In service entrance load centers, the ground bar and
neutral bar are frequently the same; if so, the ground and
neutral wires can be connected to either.

D. Installing 120 Volt Circuits

This section provides instructions for connecting the wires
from your transfer switch to the circuit breakers in your load
center which control your appliances.

You should refer to the load planning you did previously to
insure that side #1 and side #2 of the transfer switch are
balanced. Wire the circuits, starting with toggle Switch A.

If you will not be installing any 240 Volt or multi-wire circuits,
remove the factory-installed handle tie(s) on the unit by
loosening the setscrews on the tie.

Lets assume that, according to your load balancing plan, you
will use Switch A to supply power to the refrigerator (Figure 5)

1.

Turn off the refrigerator circuit breaker. Disconnect the wire

that is attached to the circuit breaker.

2.

Find the black and red wires from the transfer switch

marked A.

3.

Cut the red wire at a length convenient for it to reach to the

refrigerator circuit breaker. Strip 5/8” from the end of the
wire. Connect the red wire to the refrigerator circuit breaker
and retighten the screw on the breaker.

4.

Cut the black wire from the transfer switch to a length

convenient for attaching it to the wire you removed from the
refrigerator circuit breaker in #1. Strip 5/8” from the end of
the wire.

5.

Insert both wires—the one removed from the refrigerator

circuit breaker and the black wire for Switch A—into a
yellow wire connecter. Tighten the connection and push
the connected wires back into the wiring compartment of
the load center.

Page 7

Failure to properly install a multi-wire branch
circuit could result in overloading the neutral wire.

If a selected circuit is part of a multi-wire branch circuit, insure the
other branch circuit that shares the neutral is also connected to the
transfer switch. The two circuits must be connected to opposing legs
(phases) of the generator power and a handle tie must be installed on
the switch handles so that both legs are transferred at the same time.

When Installing 120 Volt Circuits

Figure 4

The transfer switch circuits with 20 Amp breakers must be connected only to
branch circuits with 20 Amp breakers in the load center. Do not connect transfer
switch circuits to any branch circuits greater than 20 Amps.
NOTE: The transfer switch circuits with 15 Amp breakers can be connected to
branch circuits with either 15 or 20 Amp breakers in the load center.

Figure 5

Wires from
Switch A

Ground Wire
(Green)

This completes the connection of Switch A for your refrigerator.
Label Switch A as “REFRIGERATOR” on the identification pad on
top of the transfer switch.

6.

Repeat Steps 1 through 5 for each of the remaining switches
on your transfer switch according to your load balancing plan,
taking into account the following:

See the next section for installing 240-Volt Circuits

Remember to “Balance the Load”, dividing appliances
with higher wattages between the left and right side of
the transfer switch

WARNING

WARNING

Содержание 31406CRK

Страница 1: ...8 Completing the Installation 8 Installing and Wiring the Power Inlet Box 9 Wiring the Power Inlet Box to the Transfer Switch 9 Installing an Optional Power Inlet 10 Finishing Up 10 Operating Instruc...

Страница 2: ...connectors Installation and Operating Instructions SAFETY SYMBOLS USED IN THIS MANUAL Danger indicates an imminently hazardous situation that if not avoided could result in death or serious injury War...

Страница 3: ...n emergency 2 Finding the essential circuit breakers that control these devices 3 Creating a map of all of the other electrical devices plugged into or wired into these circuits A tear off Home Circui...

Страница 4: ...Each transfer switch circuit controlled by a toggle switch has a built in corresponding 15 or 20 Amp push to rest circuit breaker that protects the branch circuit when the toggle switch is in the GEN...

Страница 5: ...plan the set up of your transfer switch Use the running watts of your appliances rather than starting watts when dividing them between the two halves of the transfer switch Check your appliances for...

Страница 6: ...lt Double Pole Circuit Breaker Toggles C D Together Generator 5 500 Running Watts 6 200 Peak Watts Transfer Switch Model 6 Circuits Side One Appliance Additional Toggle Main Appliance Running Start Up...

Страница 7: ...er Figure 3 3 Remove the cover of your load center Keep in mind that the wires on the utility side of the main breaker are still live and if contacted could cause serious injury or death If available...

Страница 8: ...eaker and retighten the screw on the breaker 4 Cut the black wire from the transfer switch to a length convenient for attaching it to the wire you removed from the refrigerator circuit breaker in 1 St...

Страница 9: ...er of the load center 2 If you have not already done so fill in the chart on the top of the transfer switch to identify your emergency circuits and the toggle switches they correspond to 3 Do not turn...

Страница 10: ...X and the black wire into the hole marked Y 8 Replace the cover of the power inlet box and tighten the screw H Wiring the Power Inlet Box to the Transfer Switch All Reliance Controls transfer switches...

Страница 11: ...n all of the circuit breakers in your load center 2 Turn on the main breaker 3 Position all switches on the transfer switch to the LINE position 4 IMPORTANT In order to insure that all wiring connecti...

Страница 12: ...4 6155 to locate the distributor nearest you Power Cords Connect generator power outlets with outdoor power inlet boxes or accessory power inlets PC20100 PC20200 3 0 PC30100 PC30200 3 0 10 foot cord w...

Страница 13: ...mponent s or ii repair or replace the Switch Reliance s obligation is strictly limited to said repair or replacement of the Switch and Reliance shall not be liable for any incidental special or conseq...

Страница 14: ...PING CHART This Toggle Switch on My Generator Transfer Switch A B C D E F Controls these essential appliances I will need during a power outage So I need to turn off these other devices which are on t...

Страница 15: ......

Страница 16: ...Reliance Controls Customer Service 800 439 5745 Website www reliancecontrols com 03 04 21...

Отзывы: