Application

Model RFC series sprinklers are intended for installation where 
residential sprinklers are permitted or required by NFPA 13, 
NFPA 13R, and NFPA 13D. The sprinklers are concealed pendent 
residential sprinklers.

Model RFC 30, RFC43, and RFC49 sprinklers are available in or-
dinary temperature classification for installation where the Maxi-
mum Ceiling Temperature does not exceed 100 °F (38 °C). Model 
RFC58 sprinklers are available in either ordinary or intermediate 
temperature classification for installation where the Maximum 
Ceiling Temperature does not exceed 100 °F (38 °C) or 150 °F 
(66 °C), respectively.

Do not exceed the maximum recommended torque. Exceeding 
the maximum recommended torque may cause leakage or im-
pairment of the sprinkler. Use care when inserting or removing the 
wrench from the sprinkler to avoid damage to the sprinkler.

Install the cover plate by hand by pushing the cover plate into the 
cup and turning the cover in the clockwise direction until it is tight 
against the ceiling.

Installation

Model RFC series sprinklers are intended to be installed in ac-
cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the 
requirements of applicable authorities having jurisdiction. Model 
RFC series sprinklers must not be installed in ceilings with positive 
pressure in the space above. Ensure that the 4 slots in the cup are 
open and unobstructed following installation. Model RFC series 
sprinklers are shipped with a protective cap that should remain on 
the sprinkler until installed. The protective cap should be replaced 
following installation of the sprinkler and permanently removed 
only when the cover plate is installed and the sprinkler system is 
placed in service following construction.

Model RFC series sprinklers are installed with the Model FC 
wrench. The use of any other wrench to installed Model RFC 
series sprinklers is not permitted and may damage the sprinkler. 
Temporarily remove the protective cap during installation of the 
sprinkler. Insert the Model FC wrench over the sprinkler until the 
wrench engages the body. Do not wrench any other part of the 
sprinkler/cup assembly. The Model FC wrench is designed to be 
turned with a standard 1/2" square drive. Tighten the sprinkler 
into the fitting after applying a PTFE based thread sealant to the 
sprinkler’s threads. Recommended installation torque is 8 to 18 ft/
lb (11 to 24 N-m).

Installation Dimensions

Table J

Notes:

 

1.   Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method prior to instal-

lation. A 1/2" x 1/2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing sprinklers. 

2.   For use with 165 °F (74 °C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100 °F (38 °C).
3.   For use with 212 °F (100 °C) temperature rated sprinklers with the Maximum Ceiling Temperature does not exceed 150 °F (66 °C).

Sprinkler 

Model

Cover 

Plate 

Model

Cover Plate 

Diameter

inch

(mm)

Recommended 

Hole Diameter  

in Ceiling

inch

(mm)

Cover Plate 
Adjustment

inch

(mm)

Min. to Max. 

Face of  

Fitting  

to Ceiling

(1)

inch

(mm)

Min. to Max. 

Dropped Deflector 

Distance below 

Ceiling

inch

(mm)

Cover Plate 

Temperature 

Rating

RFC30
RFC43
RFC49

RFC

3-5/16

(84)

2-5/8

(67)

1/2

(13)

1-1/2 to 2

(38 to 51)

1/2 to 1

(13 to 25)

135 °F

(57 °C)

RFC58

RFC

3-5/16

(84)

2-5/8

(67)

3/4

(19)

1-1/2 to 2-1/4

(38 to 57)

1/4 to 1

(6 to 25)

135 °F

(2)

(57 °C)

or 165 °F

(3)

(74 °C)

Page 6 of 7

www.reliablesprinkler.com

Bulletin 006 Rev. K
February 2017

Table H

Cover Plate Finishes

(1) 

Notes:

 

1.   Paint or any other coating applied over the factory finish will void all approvals and warranties.
2.   Custom color paint is semi-gloss, unless specified otherwise.
3.   Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side. Cover plates are not listed 

or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.

Standard Finishes

Special Application Finishes

White Polyester

Off White Paint

Black Paint

Raw Brass

Chrome Plated

Bright Brass

Finished Bronze

Black Plated

Satin Chrome

Stainless Steel 

Clad

(3)

Custom Color Paint

(2)

Содержание RFC Series

Страница 1: ...operating ele ment Sprinklers with a 165 F 74 C temperature rating are ordinary temperature classification and should be used with a 135 F 57 C temperature rated cover plate Sprinklers with a 212 F 10...

Страница 2: ...essure Max Coverage Area ft x ft m x m Flow gpm l min Pressure psi bar 12x12 3 6x3 6 9 34 9 0 0 62 14x14 4 3x4 3 10 38 11 0 0 76 Table B Model RFC30 Sprinkler Hydraulic Design Criteria Figure 1 Model...

Страница 3: ...12x12 3 6x3 6 12 45 7 8 0 54 14x14 4 3x4 3 13 49 9 1 0 63 16x16 4 9x4 9 13 49 9 1 0 63 18x18 5 5x5 5 18 68 17 5 1 21 20x20 6 1x6 1 21 79 23 8 1 64 Table C Model RFC43 Sprinkler Hydraulic Design Crite...

Страница 4: ...m l min Pressure psi bar 16x16 4 9x4 9 13 49 0 7 0 0 48 18x18 5 5x5 5 17 64 3 12 0 0 83 20x20 6 1x6 1 20 75 7 16 7 1 15 Table D Model RFC49 Sprinkler Hydraulic Design Criteria Figure 3 Model RFC49 Spr...

Страница 5: ...16 60 6 7 6 0 53 18x18 5 5x5 5 18 68 1 9 6 0 66 20x20 6 1x6 1 20 75 7 11 9 0 82 Table E Model RFC58 Sprinkler Hydraulic Design Criteria Figure 4 Model RFC58 Sprinkler Components and Dimensions Sensit...

Страница 6: ...t the Model FC wrench over the sprinkler until the wrench engages the body Do not wrench any other part of the sprinkler cup assembly The Model FC wrench is designed to be turned with a standard 1 2 s...

Страница 7: ...ock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers Prior to installation sprinklers should be maintained in the original cartons and packaging un...

Отзывы: