RASCOFLEX Technical & Installation Instruction
R0029B
Suggested Methods of Proper Hose Alignment & Examples of Improper Methods:
NOTICE
Check that the flexible hose from the branch-line connection to the sprinkler location
is the correct length. Ensure that the maximum numbers of specified bends with the
minimum bend radius are adhered to. Use a radius tool to ensure the proper minimum
bend radius of Approval Agencies, which is 75 mm, in case of LPCB. In addition, the
radius of the flexible hose must NOT fall in the non-corrugated ends.