Note:
The F1 Res 76 will use a 1” x ¾” reducer.
FP push-on/thread-off escutcheon
Fig. 3
Fig. 4
4.
Model F1 Res 30, 49, 58 & 76 CCP Pendent
•
Model F1 Res 30, 49, 58 & 76
Recessed Pendent / FP
•
Technical Data: F1 Res 76 Pendent and Recessed Pendent
Thread
Size
Nominal Ori
fi
ce
Inch (mm)
Sprinkler
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient Temp.
K
Factor
Sprinkler
Length
Inch (mm)
°F
°C
°F
°C
3
/
4
” NPT
(R½)
17
/
32
” (13.5)
155
175
68
79
175 (12)
100
150
38
66
7.6
2.25 (57)
Max.
Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identi
fi
cation
Number (SIN)
12 x 12 (3,6 x 3,6)
21 (79.5)
7.6 (0,53)
R7618
14 x 14 (4,3 x 4,3)
21 (79.5)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
21 (79.5)
7.6 (0,53)
18 x 18 (5,5 x 5,5)
21 (79.5)
7.6 (0,53)
20 x 20 (6,1 x 6,1)
23 (87.1)
9.2 (0,63)