Temperature Ratings and Approvals

Temperature 

Classification

Temperature

Rating

Link

Color

Frame

Color

Maximum Ambient

Temperature

Approvals

Sprinkler

Identification 

Number

(SIN)

°F

°C

°F

°C

Ordinary

165

74

Black

Uncolored

100

38

cULus, FM, VdS, LPCB, CNBOP

RA1914

Intermediate

212

100

White

White

150

66

cULus, FM, VdS, LPCB, CNBOP

Installation Data

Sprinkler Type

Thread Size

Nominal K-

Factor

Maximum

Working Pressure

Finish

US

Metric

Pendent

¾” (R¾)

16.8

240

175 psi (12.1 bar)

Bronze

Installation Criteria

The following general guidelines are provided for 
information only. NFPA and, where applicable, FM 
Global standards shall be consulted for complete de-
sign and installation criteria.

Orientation:

 Pendent, deflector should be parallel 

with the ceiling or roof.

System Type:

 Wet Pipe Systems Only.

Maximum area of coverage:

 100 ft

2

 (9.3m

2

), greater 

coverage areas are allowable in some cases.

Minimum area of coverage:

 64 ft

2

 (5.8m

2

).

Maximum slope ceiling:

 2/12 pitch (9.5°).

Maximum spacing:

 12 ft (3.7m) for building heights 

up to 30 ft (9.1m) and 10 feet (3.1m) for building 
heights greater than 30 ft (9.1m). 

Minimum spacing:

 8 feet (2.4m).

Deflector distance from walls:

 At least 4 inches 

(102mm) from walls, and no more than one-half the 
allowable distance permitted between sprinklers.

Deflector to Top of Storage:

 at least 36 in (900mm).

Deflector to ceiling Distance:

 6 - 14 in (150 - 350mm) 

per NFPA 13.

Center Line of Thermal Sensing
Element To Ceiling Distance:

 2 - 13 in (50 - 330mm)  

for smooth ceilings or 4 - 13 in (100 - 330mm) for non-
smooth ceilings per FM Data Sheet 2-0.

Maintenance

The Model JL-17 ESFR Sprinkler should be inspected 

and the sprinkler system maintained in accordance with 
NFPA 25.  Do not clean sprinkler with soap and water, 
ammonia or any other cleaning fluid.  Replace any sprin-
kler that has been painted (other than factory applied) or 
damaged in any way.  A stock of spare sprinklers should 
be maintained to allow quick replacement of damaged or 
operated sprinklers.  Prior to installation, sprinklers should 
be maintained in the original cartons and packaging until 
used, to minimize the potential for damage to sprinklers 
that would cause improper operation or non-operation. 

Once operated, automatic sprinklers cannot be reassem-

bled and reused. New sprinklers of the same size, type 
and temperature rating must be installed. A cabinet of re-
placement sprinklers should be provided for this purpose.

Model JL-17 ESFR Sprinkler Specification

Sprinklers shall be Early Suppression Fast Response 

(ESFR) pendent sprinklers specifically tested and [cULus 
Listed] [FM Approved] [VdS Approved] [LPCB Approved] 
for commodity storage applications.  Sprinkler frame and 
deflector to be of bronze construction.  Fusible link assem-
bly shall utilize the strut and lever principle of operation with 
approved fast response black-painted or white-painted 
beryllium-nickel thermal element. Water seal shall consist 
of a PTFE coated Bellville spring washer and brass cap as-
sembly containing no plastic parts.  ESFR sprinklers shall 
have a nominal K-factor of 16.8 (240 metric) with [¾” NPT] 
[ISO 7-R¾] threaded end connections.  Sprinkler tempera-
ture rating shall be [Ordinary 165°F (74°C)] [Intermediate 
212°F (100°C)].  ESFR pendent sprinklers shall be Reliable 
Model JL-17 (Bulletin 019).

Ordering Information

Specify

:

1.  Sprinkler: Model JL-17
2.  Temperature rating: [Ordinary 165°F (74°C)] 

  

 

 

[Intermediate 212°F (100°C)]

3.  Thread type: [

3

/

4

” NPT] [ISO 7-R

3

/