Note: The Model FP, F1, or F2 may be used for ordinary hazard occupancies.  For light hazard occupancies, the Model FP or F2 
recessed escutcheon must be used.  Model J112 and JL112 sprinklers with Model F1 recessed escutcheon are not listed for use 
in light hazard occupancies.

Bulletin 172
May 2019

Page 6 of 7

www.reliablesprinkler.com

The Model J112 and JL112 pendent and upright sprinklers are cULus Listed for installation under concrete tee construction in ac-
cordance with the following specific application criteria:

• 

Max. Tee Depth: 2’- 6” (0.8m)

• 

Max. Tee Stem Spacing: 7’- 6” (2.3m)

• 

Min. Tee Stem Spacing: 3’- 0” (0.9m)

• 

Max. Tee Length: 32’- 0” (9.8m) or baffles not less than the depth of the tees must be installed so that the longitudinal space 
between baffles does not exceed 32ft (9.8m) in length.

• 

Max. Deflector distance below Tee: 1” (25mm)

• 

Comply with obstructions to the Sprinkler Discharge Pattern Development requirements of the NFPA13 where deflector is lo-
cated above bottom of tee.

  Model J112 and JL112 Specific Application Criteria for Use Under Concrete Tee Construction                       cULus Listed

Figure 7

Model F1/F2 Escutcheon 
Installation Dimensions

Figure 6

Model FP Escutcheon 
Installation Dimensions

Figure 5

Application and Installation for Use Under Concrete Tee

1” (25mm) max. 

1” (25mm) max. 

2’-6” (0.8m) 

max.

7’-6” (2.3m) max.

3’-0” (0.9m) min.

Содержание J112 Pendent

Страница 1: ...112 Upright sprinklers use a fusible link operating element Model J112 Pendent and Model JL112 Pendent sprinklers are cULus Listed for use with the Model F2 and Model FP recessed escutch eons which pr...

Страница 2: ...adjustment FP 1 2 13mm adjustment Listings and Approvals cULus Listed cULus Listed as Corrosion Resistant with White Polyester Black Polyester and ENT finish only Max Spacing ft x ft m x m Light Hazar...

Страница 3: ...2 13mm adjustment FP 1 2 13mm adjustment Listings and Approvals cULus Listed Chrome and white polyester finish is supplied with white link regardless of temperature rating Max Spacing ft x ft m x m Li...

Страница 4: ...sted cULus Listed as Corrosion Resistant with White Polyester Black Polyester and ENT finish only Max Spacing ft x ft m x m Light Hazard Ordinary Hazard Group 1 Ordinary Hazard Group 2 Flow gpm l m Pr...

Страница 5: ...ULus Listed Chrome and white polyester finish is supplied with white link regardless of temperature rating Max Spacing ft x ft m x m Light Hazard Ordinary Hazard Group 1 Ordinary Hazard Group 2 Flow g...

Страница 6: ...em Spacing 7 6 2 3m Min Tee Stem Spacing 3 0 0 9m Max Tee Length 32 0 9 8m or baffles not less than the depth of the tees must be installed so that the longitudinal space between baffles does not exce...

Страница 7: ...in accordance with NFPA 25 Do not clean sprinklers with soap and water ammo nia or any other cleaning fluids Remove dust by gentle vacu uming Replace any sprinkler which has been painted other than fa...

Отзывы: