The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Finishes
Standard Finishes
Bronze
Reliable’s Model GL 112 QR sprinkler must be installed ac-
cording to NFPA Standards or the appropriate Factory Mutual
Loss Prevention Data Sheets for all area/density methods of de-
sign as well as the Authority Having Jurisdiction.
* For sprinkler standards prior to 1999 edition of NFPA 13,
use NFPA standards 231, 231C, 231D & 231F.
Maintenance
Model GL 112 QR Sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gentle vac-
uuming. Remove any sprinkler which has been painted (other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation.
Ordering Information
Specify:
1. Sprinkler
Model
2. Temperature
Rating
3. Finishes
Use only the Model H sprinkler wrench for sprinkler removal and
installation. Any other type of wrench may damage the sprinkler.
Model H Sprinkler
Note:
Sprinklers should be
tightened between 14-20 ft/
lbs (19-27,1 N·m) torque.
Sprinklers not tightened to
recommended torque may
cause leakage or impairment of the sprinklers. Damage sprinklers must
be replaced immediately.