Revision lines indicate updated or new data.

EG. Printed in U.S.A. 11/13

P/N 9999970181

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory 

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.

Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly 

qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

Technical Data

Sprinkler Model

Thread 

Size

Ori

fi

 ce 

Size

Temperature

Rating

Max.

Ambient 

Temp.

Maximum 

Sprinkler 

Spacing

Maximum 
Coverage 

Area

Approvals

Sprinkler 

Identi

fi

 cation 

Number

(SIN)

°F

°C

°F

°C

GFR VELO–ECOH 

Upright  

(1)

¾” NPT 

(R¾)

0.70” 

(18mm)

165

74

100

38

20 ft.

(6.1 m)

400 ft.

2

 

(37.2 m

2

)

1,2

R6553

212

100

150

66

(1)

 Minimum Spacing Between GFR VELO-ECOH Upright Sprinklers is 12 feet (3.6m).

Minimum Flow Requirements

Spacing 

(1)

Coverage 

Area

NFPA 13 - 1991 & Later

NFPA 13 - 1989 & Earlier

Nominal

Factor

Ordinary Hazard 1  Ordinary Hazard 2 Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 3

0.15 gpm/ft

(6.1L/min/m

2

)

Density

0.20 gpm/ft

2

(8.1 L/min/m

2

)

Density

0.16 gpm/ft

2

(6.5 L/min/m

2

Density

0.19 gpm/ft

2

(7.7 L/min/m

2

Density

0.21 gpm/ft

2

(8.25 L/min/m

2

Density

Flow

Pressure

Flow

Pressure

Flow

Pressure

Flow

Pressure

Flow

Pressure

US Metric

gpm 

(L/min)

psi

(bar)

gpm

(L/min)

psi

(bar)

gpm

(L/min)

psi

(bar)

gpm

(L/min)

psi

(bar) 

gpm

(L/min)

psi

(bar)

20 ft. x 20 ft.

(6.1m x 6.1m)

400 ft.

(37.2m

2

)

60.0

(227)

18.4
(1,3)

80.0

(302)

32.7
(2,3)

64.0 

(242)

20.9
(1,5)

76.0

(287)

29.5
(2,1)

84.0 

(318)

36.0
(2,5)

14

200

(1)

 For spacing and coverage areas less than 20 ft. x 20 ft. (6.1m x 6.1m) and 400 ft

2

, the flows and

  pressures for the 20 ft. x 20 ft. (6.1m x 6.1m) spacing and 400 ft

2

 (37.2m

2

) area must be used.

Ordering Information

Specify:

1. Sprinkler Model
2. Temperature Rating
3. Sprinkler Finish

Finishes

Standard Finishes

Bronze
Chrome Plated

(1)

 Other colors and finishes are available

    on special order. Consult factory for

    details.

Model H Sprinkler Wrench

Use Model H Wrench for Model GFR VELO–ECOH 
Upright Sprinkler removal and installation.

Maintenance

Model GFR VELO-ECOH Upright Extended Coverage 

Sprinklers should be inspected and the sprinkler system 
maintained in accordance with NFPA 25.  Do not clean 
sprinklers with soap and water, ammonia or any other clean-
ing fluids.  Remove dust by using a soft brush or gentle vac-
uuming.  Remove any sprinkler that has been painted (other 
than factory applied) or damaged in any way.  A stock of 
spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers.  Prior to 
installation, sprinklers should be maintained in the original 
cartons and packaging until used to minimize the potential 
for damage to sprinklers that would cause improper opera-
tion or non-operation.

Patents: U.S. Patent No. 6,446,732