2.

Technical Data:

Ori

fi

 ce

Size

“K” Factor

Thread

Size

Maximum

Ambient

Temperature

Maximum Water 

Working Pressure

Sprinkler

Identi

fi

 cation

Number

(SIN)

Approvals

US

Metric

17

/

32

” (20mm)

8.0

115

¾” NPT (R¾)

100°F (38°C)

175 PSI (12 bar)

RA4762

1

Coverage Area

Flow Rate

Pressure

Max. Coverage 

Area 

Width x Length

De

fl

 ector to Ceiling

Dimension

Temperature Rating

gpm

L/min

psi

bar

ft. x ft.

m x m

inches

mm

Sprinkler

Cover

31

117.3

15.0

1,03

14 x 22

4.3 x 6.7

4 - 6

102 - 152

165°F (74°C)

135°F (57°C)

35

132.5

19.1

1,3

14 x 22

4.3 x 6.7

6 - 12

152 - 305

35

132.5

19.1

1,3

14 x 24

4.3 x 7.3

4 - 6

102 - 152

39

147.6

23.8

1,6

14 x 24

4.3 x 7.3 

6 - 12

152 -305

26

98.4

10.6

0,7

16 x 16

4.9 x 4.9

4 - 12

 102 - 305

29

109.8

13.1

0,9

16 x 18

4.9 x 5.5

4 - 12

102 - 305

32

121.1

16.0

1,1

16 x 20

4.9 x 6.1

4 - 12

102 - 305

36

136.2

20.2

1,4

16 x 22

4.9 x 6.7

4 - 12

102 - 305

39

147.6

23.8

1,6

16 x 24

4.9 x 7.3 

4 - 12 

102 - 305

33

124.9

17.0

1,2

18 x 18

5.5 x 5.5

4 - 12

102 - 305

36

136.2

20.2

1,4

18 x 20

5.5 x 6.1

4 - 12

102 - 305

40

151.4

25.0

1,7

18 x 22

5.5 x 6.7

4 - 12

102 - 305

Approval Type

Quick Response Extended Coverage - Light Hazard Horizontal Sidewall.
Minimum spacing between sprinklers - 8 feet (2.4m). 
Install below smooth, flat, horizontal ceilings only AS DEFINED BY THE NFPA 13 STANDARD.