background image

Note:

 The sprinkler can protrudes ¼” when escutcheon is in nominal position.  Escutcheon adjustment provides -¼” (-6mm) to +1¼”  (+32mm) “A” 

dimension adjustment range.

Fig. 5

7.

Model F3-80 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon (SIN RA6032)

“A” Dim.

2” to 48” (51mm to 1219mm) in 1/4” (6mm) increments for 1” connections or 
2” to 36” (51mm to 914mm) in 1/4” (6mm) increments for 3/4” connections

Содержание F3-80 Dry Horizontal Sidewall

Страница 1: ...able in this Bulletin for available temperature rat ings Model F3 80 Dry sprinklers are intended for installa tion on wet pipe dry pipe or preaction sprinkler systems in accordance with NFPA 13 Model...

Страница 2: ...range 135 F 57 C 135 F 57 C 100 F 38 C cULus NYC Red 155 F 68 C Intermediate Yellow 175 F 79 C 165 F 74 C 150 F 66 C Intermediate Green 200 F 93 C 165 F 74 C 150 F 66 C High Blue 286 F 141 C None 225...

Страница 3: ...en escutcheon is in nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 1 Model F3 80 Dry Pendent Sprinkler with Standard Escutcheon SIN RA6012 A Dim 2 to 36...

Страница 4: ...HB Extended Escutcheon SIN RA6012 A Dim 3 to 36 89mm to 914mm in 1 4 6mm increments Note The sprinkler can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment provides 12 7mm to...

Страница 5: ...dent sprinkler with the Model FP escutcheon in ceilings which have positive pressure in the space above Fig 3 5 Model F3 80 Dry Pendent Sprinkler with Model FP Recessed Escutcheon SIN RA6012 A Dim 31...

Страница 6: ...del CCP Cover Plate SIN RA6012 A Dim 31 2 to 36 89mm to 914mm in 1 4 6mm increments Note Do not install the Model F3 80 Dry Pendent sprinkler with the Model CCP cover plate in ceilings which have posi...

Страница 7: ...ustment provides 6mm to 1 32mm A dimension adjustment range Fig 5 7 Model F3 80 Dry Horizontal Sidewall Sprinkler with Standard Escutcheon SIN RA6032 A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments...

Страница 8: ...31 2 to 48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note The sprinkler can protrudes 1 when escutcheon is in nominal po...

Страница 9: ...48 89mm to 1219mm in 1 4 6mm increments for 1 connections or 3 to 36 89mm to 914mm in 1 4 6mm increments for 3 4 connections Note Do not install the Model F3 80 Dry Horizontal Sidewall sprinkler with...

Страница 10: ...10 Fig 8...

Страница 11: ...Fig 9 11...

Страница 12: ...Fig 11 Model XLO2 Wrench Fig 10 Model F3R Wrench 12...

Страница 13: ...Fig 12 13...

Страница 14: ...he es cutcheon or cover plate option selected 2 Apply pipe joint compound or PTFE tape to the male threads of the sprinkler s inlet fitting 3 Install the sprinkler in the fitting using the installatio...

Страница 15: ...een the bulb supporting cup and the wrenching boss Do not replace this wax with a substitute substance An Alternate substance may interfere with proper operation of the sprinkler Do not clean sprinkle...

Отзывы: