Model F1FR56-300 Pendent Sprinkler

SIN RA2614

 

Technical Specifications

 Style:

Pendent
Recessed Pendent
Concealed Pendent

 Threads:

 1/2” NPT or ISO 7-R1/2

 Nominal K-Factor:

 5.6 (80 metric)

 Max. Working Pressure:

 300 psi (20.7 bar)

 

Material Specifications

 Thermal Sensor:

 3 mm Glass Bulb

 Sprinkler Frame:

 Brass Alloy

 Cap:

 Bronze Alloy

 Sealing Washer:

 Nickel with PTFE

 Load Screw:

 Copper Alloy

 Deflector:

 Brass Alloy

 

Sprinkler Finishes 

(See Table B)

 

Sensitivity

Quick response

Temperature Ratings

(1)

 135°F (57°C)
 155°F (68°C)
 175°F (79°C)
 200°F (93°C)
 286°F (141°C)

 

 

Recessed Escutcheons

 Model F1
 Model F2
 Model FP

 
Cover Plate

 Model CCP

Guards & Shields (New Frames)

(2)

F-1 Guard

F-8 Guard with Shield
S-1 Shield

Guards and Shields (Legacy Frames)

(2)

D-1 Guard
D-5 Guard with Shield
S-1 Shield

Sprinkler Wrenches

Model W2 (non-recessed)
Model W4 (recessed or concealed)
Model J (new frame with guard installed)
Model JD (legacy frame with guard 
installed)

Listings and Approvals

 cULus Listed

Notes:

1.  286°F (141°C) temperature rated sprinkler not listed for recessed or concealed use.
2.  Not suitable for recessed or concealed pendent installation.

Model F1FR56-300 Pendent Sprinkler Components and Dimensions

Figure 2

F1FR_HALF_PEND_INT

Deflector

Glass Bulb

(3 mm)

Wrench Flat

Threads

3 1/4" [83mm]

2 1/4" [57mm]

1" [25mm]

Load Screw

Cap/Seal

Assembly

Shown with Optional S-1 Water

Shield (Ordered Separately)

Note: 

Please refer to Figure 4 for recessed and concealed installation.

Bulletin 077

October 2022

Page 3 of 8

www.reliablesprinkler.com

Содержание F1FR56-300 Series

Страница 1: ...lers are 300 psi 20 7 bar rated quick response standard spray automatic fire sprinklers utilizing a sensitive 3 0 mm glass bulb thermal element Pendent and horizontal sidewall sprinklers may be instal...

Страница 2: ...response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields New Frames F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frames C 3 Guard with Shield D...

Страница 3: ...rd F 8 Guard with Shield S 1 Shield Guards and Shields Legacy Frames 2 D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new fr...

Страница 4: ...3 F 7 Guard Guards Shields Legacy Frames 3 D 1 Guard Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J new frame with guard installed Model JD legacy frame with guard in...

Страница 5: ...Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protected area En...

Страница 6: ...djustment 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm 4 12 102 mm 305 mm Deflector to ceiling 9 16 14mm Note Model FP recessed assemblies may not be used where the pressure in the space behind t...

Страница 7: ...tallation sprinklers should remain in the original cartons and packaging until used This will minimize the potential for damage to sprinklers that could cause improper operation or non operation Do no...

Страница 8: ...inkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B CCP or SWC Cover Plate Temperature Rating 135 F 57 C For use with 135 F 57 C and...

Отзывы: