Models F1 & F1FR Pendent Sprinkler

with Model F1 Recessed Escutcheon

3/4" (19mm) Nominal Adjustment

2-7/8" (72 mm) Dia.

1-3/4"

(44 mm)

2-1/4"

(57 mm) Dia.

Hole in Ceiling

1-15/16"

(49 mm) Dia.

Minimum

Recess

Maximum

Recess

1"

(25 mm)

Face of Fitting

to Face of Ceiling

1-1/8" (29 mm) at
Max. Recess

3/8" (10 mm) at
Min. Recess

Models F1 & F1FR Pendent Sprinkler

with Model FP Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

1"

(25 mm)

2-5/16"

(59 mm) Dia.

Minimum

Recess

Maximum

Recess

1/2"

(12 mm)

3-3/16" (78 mm) Dia.

Face of Fitting

to Face of Ceiling

1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess

2-7/8" (72 mm) Dia.

1-3/4"

(44 mm)

Minimum

Recess

Maximum

Recess

1-1/4"

(32 mm)

Face of Fitting

to Face of Ceiling
7/8" (22 mm) at

Max. Recess
3/8" (10 mm) at
Min. Recess

2-1/4"

(57 mm) Dia.

Hole in Ceiling

1-15/16"

(49 mm) Dia.

2-1/2"

 (64 mm) Dia.

Hole in Ceiling

Models F1 & F1FR Pendent Sprinkler

with Model F2 Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

F1_REC_PEND

Reducing
Fitting

Reducing
Fitting

Reducing
Fitting

Note: Model FP recessed assemblies may not be used where the
pressure in the space above the ceiling is positive with respect to

the protected area. Ensure that the openings in the Model FP cup
are unobstructed following installation.

Vented Cup

Recessed Installation: Pendent Sprinklers

Figure 3

FP Escutcheon

F1 Escutcheon 

(F2 similar)

Bulletin 073

October 2022

Page 4 of 6

www.reliablesprinkler.com