Installation
Quick response sprinkler are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Model F1FR Recessed QREC Sprinklers are to be in-
stalled as shown. The Model F1 or F2 Escutcheons illustrat-
ed are the only recessed escutcheons to be used with the
Model F1FR Sprinklers. The use of any other recessed es-
cutcheon will void all approvals and negate all warranties.
When installing Model F1FR QREC Sprinklers, use the
Model D Sprinkler Wrench. When installing Model F1FR
QREC Recessed Pendent or Sidewall Sprinklers, use the
Model GFR1 Sprinkler Wrench. Any other type of wrench
may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and in-
stallation. REMOVE THIS PROTECTION AT THE TIME THE
SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE
PROTECTION. Removal of the protectors before this time
may leave the bulb vulnerable to damage. RASCO wrench-
es are designed to install sprinklers when covers are in
place. REMOVE PROTECTORS BY UNDOING THE CLASP
BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.
Maintenance
The Models F1FR QREC and F1FR QREC Recessed Sprin-
klers should be inspected and the sprinkler system main-
tained in accordance with NFPA 25. Do not clean sprinklers
with soap and water, ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming.
Remove any sprinkler which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage
to sprinklers that would cause improper operation or non-
operation.
Temperature Ratings
Classification
Sprinkler
Rating
Maximum
Ambient Temp.
Bulb
Color
°F
°C
°F
°C
Ordinary
Ordinary
Intermediate
135
155
175
57
68
79
100
100
150
38
38
66
Orange
Red
Yellow
Sprinkler Types
Extended Coverage Pendent
Extended Coverage Sidewall
• EC-9 HSW Deflector
Recessed Extended Coverage Pendent
Recessed Extended Coverage Sidewall
• EC-9 HSW Deflector
Finishes
(1)
Standard Finishes
(1)
Sprinkler
Escutcheon
Bronze
Chrome
White & Black Polyester
(3)
Brass
Chrome
White
Special Application Finishes
Sprinkler
(2)
Escutcheon
Electroless Nickel
PTFE(Teflon
®
)*
(3)
Bright Brass
Black Plating
Black Paint
Off White Satin
Chrome
Electroless Nickel
PTFE (Teflon
®
)*
Bright Brass
Black Plating
Black Paint
Off White
Chrome Dull
(1)
Other colors and finishes are available on special order. Consult
factory for details.
(2)
FM Approval limited to bronze, bright and satin chrome plated,
and polyester coated only.
(3)
cULus Listed Corrosion Resistant Sprinkler
Escutcheon Data
Escutcheon
Model
Adjustment
“A”
Dimension
Face of Fitting
to Ceiling or
Wall Dimension
F1
3
/
4
” (19mm)
3
/
4
” (19mm)
(1)
1
3
/
8
” (35mm)
(2)
3
/
16
” (5mm) -
15
/
16
” (24mm)
F2
1
/
2
” (13mm)
1” (25mm)
(1)
1
9
/
16
” (40mm)
(2)
3
/
16
” (5mm) -
11/
16
” (18mm)
(1)
EC Pendent
(2)
EC HSW
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note:
When Model F1FR Recessed sprinklers are or-
dered, the sprinklers and escutcheons are pack-
aged separately.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588
Sales Offices
(800) 848-6051
Sales Fax
(914) 829-2042
Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 01/14 P/N 9999970142
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
*DuPont Registered Trademark