background image

Installation

Quick response sprinkler are intended for installation as 

specified in NFPA 13.  Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.

The Model F1FR Recessed QREC Sprinklers are to be in-

stalled as shown.  The Model F1 or F2 Escutcheons illustrat-
ed are the only recessed escutcheons to be used with the 
Model F1FR Sprinklers.  The use of any other recessed es-
cutcheon will void all approvals and negate all warranties.

When installing Model F1FR QREC Sprinklers, use the 

Model D Sprinkler Wrench.  When installing Model F1FR 
QREC Recessed Pendent or Sidewall Sprinklers, use the 
Model GFR1 Sprinkler Wrench.  Any other type of wrench 
may damage these sprinklers.

Glass bulb sprinklers have orange bulb protectors to 

minimize bulb damage during shipping, handling and in-
stallation. REMOVE THIS PROTECTION AT THE TIME THE 
SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE 
PROTECTION. Removal of the protectors before this time 
may leave the bulb vulnerable to damage. RASCO wrench-
es are designed to install sprinklers when covers are in 
place. REMOVE PROTECTORS BY UNDOING THE CLASP 
BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.

Maintenance

The Models F1FR QREC and F1FR QREC Recessed Sprin-

klers should be inspected and the sprinkler system main-
tained in accordance with NFPA 25.  Do not clean sprinklers 
with soap and water, ammonia or any other cleaning fluids.  
Remove dust by using a soft brush or gentle vacuuming.  
Remove any sprinkler which has been painted (other than 
factory applied) or damaged in any way.  A stock of spare 
sprinklers should be maintained to allow quick replacement 
of damaged or operated sprinklers.  Prior to installation, 
sprinklers should be maintained in the original cartons and 
packaging until used to minimize the potential for damage 
to sprinklers that would cause improper operation or non-
operation.

Temperature Ratings

Classification

Sprinkler

Rating

Maximum

Ambient Temp.

Bulb 

Color

°F

°C

°F

°C

Ordinary
Ordinary

Intermediate

135
155
175

57
68
79

100
100
150

38
38
66

Orange

 Red

Yellow

Sprinkler Types 

Extended Coverage Pendent
Extended Coverage Sidewall

•  EC-9 HSW Deflector

Recessed Extended Coverage Pendent
Recessed Extended Coverage Sidewall

•  EC-9 HSW Deflector

Finishes

(1)

Standard Finishes

(1)

Sprinkler

Escutcheon

Bronze

Chrome 

White & Black Polyester

(3)

Brass  

Chrome 

White

Special Application Finishes
Sprinkler

(2)

Escutcheon

Electroless Nickel

PTFE(Teflon

®

)*

(3)

Bright Brass

Black Plating

Black Paint

Off White Satin

Chrome

Electroless Nickel

PTFE (Teflon

®

)* 

Bright Brass

Black Plating

Black Paint

Off White

Chrome Dull

(1)

 Other colors and finishes are available on special order.  Consult

   factory for details.

(2)

 FM Approval limited to bronze, bright and satin chrome plated,

   and polyester coated only.

(3) 

cULus Listed Corrosion Resistant Sprinkler

Escutcheon Data

Escutcheon

Model

Adjustment

“A”

Dimension

Face of Fitting

to Ceiling or

Wall Dimension

F1

3

/

4

” (19mm)

 

3

/

4

” (19mm)

(1)

1

3

/

8

” (35mm)

(2)

3

/

16

” (5mm) - 

15

/

16

” (24mm)

F2

1

/

2

”  (13mm)

1”  (25mm)

(1)

1

9

/

16

” (40mm)

(2)

3

/

16

” (5mm) - 

11/

16

” (18mm)

(1)

 EC Pendent

(2)

 EC HSW

Ordering Information

Specify:

1.  Sprinkler Model
2.  Sprinkler Type
3.  Orifice Size 
4.  Deflector Type
5.  Temperature Rating
6.  Sprinkler Finish
7.  Escutcheon Type
8.  Escutcheon Finish (where applicable)

Note:

 When Model F1FR Recessed sprinklers are or-

dered, the sprinklers and escutcheons are pack-
aged separately.

The Reliable Automatic Sprinkler Co., Inc.

(800) 431-1588    

Sales Offices

(800) 848-6051    

Sales Fax

(914) 829-2042    

Corporate Offices

www.reliablesprinkler.com   Internet Address

Manufactured by

Recycled

Paper

Revision lines indicate updated or new data.

EG. Printed in U.S.A. 01/14 P/N 9999970142

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory 

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly 

qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

*DuPont Registered Trademark

Отзывы: